| 1 | Water pump installation |
| 2 | 90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point |
| 3 | 90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points |
| 4 | OD519799/2025-2026:supply,Conveyance, installation, testing and commissioning of ornamental wall light fittingsrobust &reliable LED Bulk head with IP 65 protection and IK 08 impact resistance(Philipsmake Model WT140W LED 7S CWPSU S1C-9405)or any other equivalent make directly onwall including giving Connections with required length of 16/0.20mm 3 core round copperconductor flex wire conforming to relevant ISS or with the extended original wiring, makinggood the damages, colour washing etc as require |
| 5 | 90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 6 | 90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps |
| 7 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 8 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 9 | 1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm |
| 10 | 2.3.1:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)6 way, Double door |
| 11 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 12 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 13 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 14 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 15 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 16 | OD519801/2025-2026:Motor starter for fully Automatic star Delta starter suitable for 15 HP Motor.including Volt /Ammeter selector switch etc(MUG 15 L&T or equilant make |
| 17 | OD520098/2025-2026:Supply conveyance installation testing and commissioning of 10 HP,3 phase submersible pump motor, 63/75 mm or nearest size suction /Delivery pipe, up to 140 meter head 43200-7200 lts LPH delivery(Kirlosker / cromption/ equilent make) in the existing open well, giving mechanical and electrical connection and trial run etc.as required. |
| 18 | OD521071/2025-2026:Supply conveyance and providing 80/110 mm GI hose coller |
| 19 | 90.14.24.4:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.4 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Capacitor suitable for direct connection to motors. |
| 20 | OD521067/2025-2026:Supply conveyance installation 63/75/90 mm HDPE flexible Pipe(6 to 10 Kg /cm |
| 21 | OD519805/2025-2026:Supply conveyance and providing 12 mm nylon rope. |
| 22 | 90.3.18.4:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.50 mm dia with clamps made from 25 x 3 mm MS flat |
| 23 | 90.6.6.3:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm |
| 24 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 25 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 26 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 27 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 28 | OD519807/2025-2026:Supply installation testing and commissioning of MS/CI 50/63/75 mm cast iron Non Return Valve |
| 29 | OD519804/2025-2026:Supply installation testing and commissioning of 50/63/75 mm cast iron ball Valve |
| 30 | OD519800/2025-2026:Supply and providing the 25 x 3mm brass bolt & nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required |
| 31 | OD519806/2025-2026:Supply and providing the 12 x 3 mm brass bolt & nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required |
| 32 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 33 | OD519803/2025-2026:Supply and providing earth lead from the test joint to the earth electrode using 25 x 3 mm GIstrips including cutting, drilling necessary holes (in case of strip) and fixing firmly with platetest joint etc as required |
| 34 | OD519812/2025-2026:Supply and providing test joint for the earthing system using 2 x 25 x 3 mm GI strip includingcutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc asrequired |
| 35 | OD519802/2025-2026:Supply, Providing and fixing following capacity TP&N disconnector fuse switch unit with ISI marked HRC fuses in sheet steel enclosure making connections, etc. as required.32 Amp TP & N |
| 36 | OD519866/2025-2026:supply conveyance installation of dust and vermin proof, wall mounting, thermoplastic meter box of following size suitable for fixing KSEB meter, fuse units, CT etc, hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit-.650x350x210mm |
| 37 | OD519797/2025-2026:Supply and fixing the following accessories in the existing meter board and giving connectionsetc.32 A, 415 V, 2 way neutral link mounted on DMC/ SMC base |
| 38 | OD519811/2025-2026:Supply and fixing the following accessories in the existing meter board and giving connectionsetc.32 A fuse holder with fuse link |
| 39 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 40 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 41 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 42 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 43 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 44 | OD520075/2025-2026:Supply and Providing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour Please Enable Macros to View BoQ information |