Tender For Re-Electrification Of C Type Flat At Fact Udl Township 2026
Tender Value
Ref. Documents
Estimated cost
Bid Submission
16 Jul 2026
7 days left
EMD
12000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ernakulam → Kerala
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Re-Electrification Of C Type Flat At Fact Udl Township 2026
BOQ
| Sl. No. | Item Description |
| 1 | RE-ELECTRIFICATION OF C TYPE FLAT AT FACT UDL TOWNSHIP 2026 |
| 2 | Supply, Erection,Termination and connection of the 6 way, 3ph, 415V Horizontal double door MCB DB Having following specification: 1) 63 A, 4 pole Isolator-1 No.2) 63 A 4 pole RCCB with 30 mA sensitivity -1 No.2) 40 A 2 pole isolators- 6 Nos. 3) 6A SP B curve MCB -1 No. The contractor's scope also includes mounting of DB using suitable frame fabricated by MS angle frame (25 x 25 x 6), epoxy painted (primer+2 coats) and properly fixing on wall. The incoming PVC armoured cable (upto 4 X 50 sqmm), outgoing flexible copper cables of 4 sqmm, earth cables of size 2.5 sq mm for power circuit and outgoing cable for staircase lighting shall be glanded/terminated and connected using suitable cable lugs/clamps/ties. All Required structural items, DB with DP/MCBs, flexible glands, suitable pvc pipes etc, shall be in the scope of the contractor. Existing incoming armoured cable can be used for main supply from Piller Box. If incomer cable length is not adequate for termination in DB, cable should be jointed with copper/aluminum flexible cable of size similer to incomer cable by proper lug/ferrules by providing suitable joint box near DB. All unused ways in DB shall be covered using dummy plates. *** For approved makes refer ST&C. |
| 3 | Supply, Erection, Termination and connection of the 18 way, single phase, 230V Horizontal double door MCB lighting DB having 1) 40A DP isolators as incomers- 1 No. 2) 40A RCCB with 30 mA sensitivity -1 No. . 3) 6 A SP C curve MCBs - 5 Nos. 4) 16A SP C curve MCBs - 6 Nos. single phase out going circuits.LDB shall be mounted properly concealed on the wall by the contractor. Incomer for this DB should drawn through ISI marked pipe size not less than 20mm from main DB fixed in the ground floor by using suitable metal saddles spacing not less than 50 cm.The contractor shall use 4 sq.mm cables for the phase and neutral conductors, and 2.5 sq.mm cables for the earth connection. All Required items for this Work Shall Be in the scope of the Contractor Including the proper plastering / cementing and finishing of the wall after fixing of the DB. The contractor can use 25 mm ISI marked conduit pipe, if required for routing and drawing of cables.Unsed ways in DB shall be covered using dummy plates if any.*** For approved makes refer ST&C. |
| 4 | Open pipe point wiring with individual control for light/Fan/Bell/Staircase lights/6 A modular plug sockets separately mounted for TV points/Modular switches, using Flexible copper cables 1.5 sqmm for control and neutral connection, through pvc conduits of size not less than 20 mm using metal saddles with spacing not exceeding 50 cm as per relevant drawings or instructions from FACT Engineer in Charge. The work shall include wiring along roof/beam/column/ceiling using clamps and drawing wires as required, preparation and fixing of modular switch boards,switches,cover plates,dummy plates etc fixing of ceiling roses on suitable junction boxes, modular step type regulators for fan, drawing of 1.5 sqmm earth wires of flexible copper wire of green color for body earthing of metal clad items, connecting, testing and commissioning. For wire length greater than 10 m shall be considered as half point. All the materials for this Work shall be in the Scope of the contractor (Selection of the switch boards in rooms shall be in the form of requirements to particular room for fans/lights/sockets etc). Supply to Switchbox from DB are considered as a Point. Also in case of any two way control of equipment is done also considered as two point. The contractor shall draw 2.5 sq.mm FRLS copper flexible cable for phase / neutral conductors, and 1.5 sq.mm FRLS copper cable for earthing, from the DB to the respective switchboards,complete with necessary terminations.The contractor can use 25 mm ISI marked conduit pipe, if required for routing and drawing of cables.*** For approved makes refer ST&C. |
| 5 | Open pipe point wiring with individual control for 16 A power sockets and 16 A DP switch for ACs using Flexible copper cables of size 2.5 sqmm for control and neutral connection through pvc conduits not less than 20 mm using metal saddles with spacing not exceeding 50 cm as per relevant drawings or instructions from FACT Engineer in Charge. The work shall include wiring along roof/beam/column/ceiling using clamps and drawing wires as required. Preparation and fixing of modular switch boards, switches, cover plates, dummy plates etc, drawing of 1.5 sq mm earth wires of flexible copper wire of green color for body earthing of metal clad items, connecting, testing and commissioning. For wire length greater than 10 m shall be considered as half point. All the materials for this Work shall be in the scope of the contractor. If additional power sockets are required in same Switch Boards that shall be considered as half point.The contractor shall draw 2.5 sq.mm FRLS flexible copper cable for phase and neutral conductors, and 1.5 sq.mm FRLS flexible copper cable for earthing, from the DB to the respective switchboards, complete with necessary terminations. After completion of the work, the contractor shall carry out proper plastering and ensure neat finishing of all affected surfaces, including painting to match the existing finish. All such restoration works shall be carried out to the satisfaction and approval of the Engineer-in-Charge.*** For approved makes refer ST&C. |
| 6 | Supply of 6A modular switches as spares for the work specified in Schedule No. 3. The brand and type of switches shall be identical to those used in the work specified under Schedule No. 3 |
| 7 | Supply of 6A modular sockets as spares for the work specified in Schedule No. 3. The brand and type of sockets shall be identical to those used in the work specified under Schedule No. 3 |
| 8 | Supply of Modular step type regulators as spares for the work specified in Schedule No. 3. The brand and type of Regulators shall be identical to those used in the work specified under Schedule No. 3 |
| 9 | Supply of 16A Modular Switches as spares for the work specified in Schedule No. 4. The brand and type of Modular Switches shall be identical to those used in the work specified under Schedule No. 4. |
| 10 | Supply of 16A Modular Sockets as spares for the work specified in Schedule No. 4. The brand and type of Modular Sockets shall be identical to those used in the work specified under Schedule No. 4. |
| 11 | Supply of 16A Modular DP switches as spares for the work specified in Schedule No. 4. The brand and type of 16A Modular DP switches shall be identical to those used in the work specified under Schedule No. 4. |
| 12 | Supply and Installation of 20 W 4ft LED tube fittings with required clamps/fastners. All materials such as LED Fittings, clamps and fastners required for this work are in the scope of the contractor.Light output shall be white in colour.*** For approved makes refer ST&C. |
| 13 | Supply of 20 W 4ft LED tube fittings with required clamps/fastners as spares for the work specified in Schedule No 11. All materials such as LED Fittings, clamps and fastners required for this work are in the scope of the contractor. Light output shall be white in colour.*** For approved makes refer ST&C. |
| 14 | Supply and Installation of Calling Bells with polycarbonate body material and electronic type. Required clamps / fastners etc for this work are in the scope of the contractor. Calling Bell of Reputed Make having alarm range of atleast 10 meter.*** For approved makes refer ST&C. |
| 15 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with BLDCMotor, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery min 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.*** For approved makes refer ST&C. |
| 16 | Supply and installation of Angle Batten Holders for Rooms, Bathrooms, Stores and Work area. All material required for the work including the Angle Batten and 15 Watt LED bulbs of reputed make Shall be supplied by the Contractor.*** For approved makes refer ST&C. |
| 17 | Complete installation,commissioning and erection of Earthing System shall be in the scope of contractor. It includes, excavation, making of earth pit, fixing of electrode with back fill earthing compound, fixing of earth pit cover, any other minor civil work as per instruction of engineer-in-charge and site requirement. The earthing system shall be complete in all respect. The earth resistance shall be as per IS 3043.Erection of earth electrodes, laying 2 runs of 1 x 16 Sq.mm Aluminium PVC cable for earth cable, from earthing pit to corresponding 3 phase DB, clamping ,connection and commissioning of maintenance free copper bonded earthling systems of DB -at suitable locations .Installation of earthing system as per the specified condition mentioned above and supply of All required materials for this work such as maintenance free copper bonded earthing system approved by Kerala State Electrical Inspectorate,comprising of 3 m long, dia not less than 17 mm earth electrode of low carbon steel with 250 micron copper bonding on outer surface with associated items like environment friendly carbon based back fill compound hardware, clamps, binding wires, connection lugs, anticorrosive paint, bitumen,Sand ,cement ,Bricks and required length of 1 x 16 Sq.mm flexible Al PVC cable etc as required for this work shall be in the scope of the contractor. Earthing wire shall run throughout its length and properly bonded where possible to get uniform grounding effect. |
| 18 | Rerouting of Power Cables up to 4*50 Sq.mm from Existing 3 phase DB to New DB Location as per the instruction of FACT Engineer -in - Charge |
| 19 | Excavation of new cable trench of size 300 mm * 300 mm [width x depth] in ordinary soils for laying cables. The scope of work also includes proper refilling and consolidating of the trench using excavated earth soil after completion of cable laying. The indicated depth and width is approximate and may vary as per site requirement. |
| 20 | Supply of double‑pole (single phase and neutral) RCCB, 240 V, 40 A, sensitivity 30 mA, short‑circuit capacity 10 kA, with test button for regular inspection, ISI certified, conforming to IS 12640/IEC 61008‑1, suitable for DIN rail mounting, with trip indicator and polarity marking.*** For approved makes refer ST&C. |
| 21 | Supply of double‑pole (single phase and neutral) RCCB, 240 V, 63 A, sensitivity 30 mA, short‑circuit capacity 10 kA, with test button for regular inspection, ISI certified, conforming to IS 12640/IEC 61008‑1, suitable for DIN rail mounting, with trip indicator and polarity marking.*** For approved makes refer ST&C. |
| 22 | Supply of four pole (three phase and neutral) RCCB, 415 V, 63 A, sensitivity 30 mA, short‑circuit capacity 10 kA, with test button for regular inspection, ISI certified, conforming to IS 12640/IEC 61008‑1, suitable for DIN rail mounting, with trip indicator and polarity marking.*** For approved makes refer ST&C. |
| 23 | Supply of PVC Flexible Copper Cable, 2C x 1.5 SQ. MM, 1100V grade, Multi Stranded, Plain copper, PVC insulated, Category 02 for outdoor application as per IS 694:2010 or latest.*** For approved makes refer ST&C. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jun 25, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysJul 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender