| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work:REPAIR/ MAINT TO SERVO STABILIZER , UPS/INVERTERS AND OTHER EM EQUIPMENT’S UNDER, GE (U) UDHAMPUR. Contract No: GE/U-21/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | M&L for dehydration & filtration of voltage stabilizer by dehydration plant (bringing plant at site) including testing of sample before and after dehydration and filtration to achieved 40 KV at 2.5 mm gap complete all as specified and directed by Engr-in-Charge:-Note : (i) The filtration of the voltage stabilizer oil shall be carried out at different locations of GE (U) Udhampur(ii) The report before filtration & after filtration to be submitted by contractor .(iii) Oil for topping up will be measured and paid separately.(iv) Centrifuging Machine with all T&P & testing eqpt required for dehydration to be arranged by contractor. |
| 3 | Supply & toping up of new voltage stabilizer oil (in sealed barrel) conforming to IS 335 std having dielectric strength 40 KV at 2.5 mm gap after initial dehydration complete all as specified and directed by Engr-in-Charge:-Make : Savita/Castrol/Power True/Truoil. |
| 4 | M & L for rewinding 433 Volts LV coils of voltage stabilizer of using proper size super enameled copper wire suitable for working voltage 1.1 KV including three layer insulated material as per existing size of core including testing and commissioning complete all as specified and directed by Engr-in-Charge:-NOTE :-i). Oil filtration, supply of new oil will be measured separately.ii). All petty parts including nut, bolts, gasket minor weldings are deemed to be included the rate quoted.iii). The rate for taking out,refixing after repair, both side transportation, lifting /unloading of voltage stabilizer by crane /manual should be deemed to include in the rate quoted. |
| 5 | Supply and fixing in repair digital voltmeter, ranging from 0 to 500 Volts as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply and fixing in repair digital ammeter, ranging from 0 to 400 Amps (with CT of suitable ratio), as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply and fix in repairs Indicator Lamps (LED type) as per existing make and model, including providing necessary electrical connections (to accommodate in panel board) complete all as specified and directed by Engr-in-Charge. |
| 8 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (3 Kgs.)with copper wound RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 9 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (10 Kgs.) with copper wound , RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 10 | Dismantling and taking out old worn out reversible synchronous motor from the voltage stabilizer and supply and fix reversible servo motor (20 Kgs.) with copper wound RC, single phase 230 Volts as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply and fix in replacement of Transformer suitable for 20 to 50 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 12 | Supply and fix in replacement of Transformer suitable for 60/63 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 13 | Supply and fix in replacement of Transformer suitable for 100 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 14 | Supply and fix in replacement of Transformer suitable for 200 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply and fix in replacement of Transformer suitable for 300/400 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 16 | Supply and fix in replacement of Dimmer suitable for 20 to 60 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply and fix in replacement of Dimmer suitable for 100 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply and fix in replacement of Dimmer suitable for 120 to 200 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply and fix in replacement of Dimmer suitable for 250 to 400 KVA Servo voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 20 | Dismantling and taking out old worn out Push Button/ Auto manual switch/Micro Switch/ Potentio Meter/ Limit Switch/ Lever Switch from the voltage stabilizer and supply and fix new Push Button/ Auto manual switch/Micro Switch/ Potentio Meter/ Limit Switch/ Lever Switch suitable for voltage stabilizer capacity up to 400 KVA and testing as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 21 | Dismantling and taking out old worn out Trigger Transformer 9V/18V from the voltage stabilizer and supply and fix new Trigger Transformer 9V/18V suitable for voltage stabilizer capacity up to 400 KVA complete all as specified and directed by Engr-in-Charge. |
| 22 | Dismantling and taking out old worn out servo control panel from the voltage stabilizer and supply and fix new Servo Control panel suitable for voltage stabilizer capacity up to 400 KVA as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 23 | Dismantling and taking out old worn out servo control box from the voltage stabilizer and supply and fix new Servo Control Box suitable for voltage stabilizer capacity up to 400 KVA as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 24 | Dismantling and taking out defected PCB from the voltage stabilizer and supply and fix new Servo circuit card (PCB) suitable for voltage stabilizer capacity up to 400 KVA as per existing make and model complete all as specified and directed by Engr-in-Charge at site. |
| 25 | Supply and fix in repairs carbon brush of voltage stabilizer of capacity up to 400 KVA complete all as specified and directed by Engr-in-Charge. |
| 26 | M&L for spray painting of servo voltage stabilizer/isolation Transformer, preparation of old painted surfaces of steel body by brushing/cleaning stain, greasy spots with thinner outside of voltage stabilizer/Isolation transformer indoor/outdoor type capacity 10 KVA to 30 KVA to match with existing colour as per direction by Engr-in-Charge. |
| 27 | Description all as per ser item No 25.00 here-in-before, but capacity of 50 KVA to 100 KVA |
| 28 | Description all as per ser item No 25.00 here-in-before but capacity of 200 KVA to 400 KVA |
| 29 | Supply and fix in repair top cover gasket/cock sheet suitable for 10 KVA to 50 KVA Voltage Stabilizer/Isolation transformer complete all as specified and directed by Engr-in-Charge at site. |
| 30 | Description all as per ser item No 28.00 here-in-before but capacity of 60/63 KVA to 160 KVA |
| 31 | Description all as per ser item No 28.00 here-in-before but capacity of 200 KVA to 400 KVA |
| 32 | S & F in repairs control wiring of voltage stabilizer of capacity up to 400 KVA complete all as specified and directed by Engr-in-Charge. |
| 33 | Supply and fix in repairs high low voltage cut off circuit of voltage stabilizer as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 34 | Routine periodical maintenance/servicing as and when required and testing of voltage stabilizer/Isolation Transformer of capacity up to 400 KVA complete including all consumables items like cotton, waste cloth, kerosene oil etc.Maintenance will be carried out as all directed by Engr-in-Charge and comprising of the following :-(a) Greasing of all points.(b) Checking of servo(c) Checking of relays, selector switch, control switch, micro switch, carbon brush.(d) Checking of sensing trigger transformer, main transformer and dimmer.(e) Checking of ammeter, voltmeter contactor.(f) Checking and repairing of all internal wiring and connection of voltage stabilizer complete.(g) Checking of any leakage of oil.h) Repair/rewiring of broken/damaged control panel connection including measuring instruments, indicators, etc. |
| 35 | Routine periodical maintenance/servicing as and when required and testing of UPS 5 KVA to 30 KVA capacity single phase/ three phase complete including all consumables items like cotton, waste cloth, kerosene oil etc.Maintenance will be carried out as all directed by Engr-in-Charge and comprising of the following :-(a) Cleaning all parts and card.(b) Cleaning cooling fan.(c) Top up battery distil water |
| 36 | Supply and fix inreplacement of Batteries (VRLA / Li-ion / Tubular, depending on model) of capacity (12V, 50Ah–100 Ah) as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 37 | Supply and fix in replacement of Batteries (VRLA / Li-ion / Tubular, depending on model) of capacity 12 Volt 180/200Ah as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 38 | Supply and fix in replacement of Battery fuses / battery breaker (DC MCB/MCCB) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 39 | Supply and fix in replacement of Battery connectors, links, and cables suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 40 | Supply and fix in replacement of IGBT modules (in inverter & rectifier sections) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 41 | Supply and fix in replacement of Power diodes / rectifier bridges suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 42 | Supply and fix in replacement of Snubber circuits (resistor + capacitor assemblies) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 43 | Supply and fix in replacement of DC bus capacitors (electrolytic, high voltage) suitable for 15 to 30 KVA UPS UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 44 | Supply and fix in replacement of inverter driver boards / gate driver cards suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 45 | Supply and fix in replacement of Control PCB / DSP board (system logic) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 46 | Supply and fix in replacement of input & output contactors / relays suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed. |
| 47 | Supply and fix in replacement of Static switch module (SCRs / Triacs) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 48 | Supply and fix in replacement of input & output MCBs / MCCBs suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 49 | Supply and fix in replacement of Surge protection devices (SPDs) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 50 | Supply and fix in replacement of Current transformers (CTs) & voltage sensors suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 51 | Supply and fix in replacement of Cooling fans / blowers suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 52 | Supply and fix in replacement of Air filters suitable for 15 to 30 KVA UPS as per existing make and model ccomplete all as specified and directed by Engr-in-Charge. |
| 53 | Supply and fix in replacement of Heat sink compound / thermal pads suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 54 | Supply and fix in replacement of LCD / HMI display unit suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 55 | Supply and fix in replacement of Communication cards (SNMP, Modbus, RS-485, etc.) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 56 | Supply and fix in replacement of Control fuses (low-rating, PCB type) suitable for 15 to 30 KVA UPS UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 57 | Supply and fix in replacement of Cables and connectors (signal & power) suitable for 15 to 30 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 58 | Supply and fix in replacement of Battery fuses / battery breaker (DC MCB/MCCB) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 59 | Supply and fix in replacement of Battery connectors, links, and cables suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 60 | Supply and fix in replacement of IGBT modules (in inverter & rectifier sections) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 61 | Supply and fix in replacement of Power diodes / rectifier bridges as per existing make and model suitable for 05 to 10 KVA UPS complete all as specified and directed by Engr-in-Charge. |
| 62 | Supply and fix in replacement of Snubber circuits (resistor + capacitor assemblies) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 63 | Supply and fix in replacement of DC bus capacitors (electrolytic, high voltage) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 64 | Supply and fix in replacement of inverter driver boards / gate driver cards suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 65 | Supply and fix in replacement of Control PCB / DSP board (system logic) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 66 | Supply and fix in replacement of input & output contactors / relays suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 67 | Supply and fix in replacement of Static switch module (SCRs / Triacs) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 68 | Supply and fix in replacement of input & output MCBs / MCCBs suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 69 | Supply and fix in replacement of Surge protection devices (SPDs) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 70 | Supply and fix in replacement of Current transformers (CTs) & voltage sensors suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 71 | Supply and fix in replacement of Cooling fans / blowers (fail quite often, need spares) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 72 | Supply and fix in replacement of Air filters (if used) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 73 | Supply and fix in replacement of Heat sink compound / thermal pads suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 74 | Supply and fix in replacement of LCD / HMI display unit suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 75 | Supply and fix in replacement of Communication cards (SNMP, Modbus, RS-485, etc.) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 76 | Supply and fix in replacement of Control fuses (low-rating, PCB type) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 77 | Supply and fix in replacement of Cables and connectors (signal & power) suitable for 05 to 10 KVA UPS as per existing make and model complete all as specified and directed by Engr-in-Charge. |
| 78 | Attending breakdown for Servo Voltage stabilizer/ UPS detect fault related to breakdown by a service Engineer complete all as specified and directed by Engr-in-Charge.Note:- (a) Spares will be measured and paid separately under relevant items.(b) The break down complaint should be attended within 8 hours by the intimation of Engr-in-charge or concern JE E/M by telephonically / verbally. (c) Not attended of complaint within eight hours will lead to recovery from subsequent payment in the following manner :- (i) Not attending within 0 to 8 Hours - Rs. 2000.00 (ii) Not attending within 8 to 16 Hours- Rs. 2000.00 (iii) Not attending within 16 to 24 Hours- Rs. 2000.00 (iv) Not attending after24 Hours - Rs. 5,000.00 (v) The maximum recovery will be Rs. 50,000.00 plus the expenditure incurred for rectification of the same by any other means. |
| 79 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) double out door type, double door , floor mounted, compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,p owder coated, having front and rear openable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming :- (a) S&F MCCB FP 400 Amps 35 KA - 01 No (b) Copper Busbar with current rating capacity 600 Amps-04 Nos for out going not less than 1 MTR long mounted on insulators . |
| 80 | Supply, installation, commissioning and testing of factory made LT panel Board of Suitable size indoor type 415 Volts, dust proof,vermin proof made out of CRCA sheet duly compartmentalized panel with 2.00 mm thick CRCA sheet , conforming to IEC-61439 part I & II. The cubical shall have frame work bottom & 75 MM Base Frame. Aluminium main busbar of incomer switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase , 4 wire electric supply system and control wiring with multi stranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engineer-in-Charge. (Note : shall be mounted on PCC 1:2:4 type B-1 (with 20 mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item. :- Make:-dvepl/tricolite/adlice/Milestone. Panel builder should also be System intergrator/ Franchise Patner for principal Company of Switchgear company and should be approved in MES Note :- Panel should be TTA in accordance with IEC-61439 part I & II. |
| 81 | (a) Changeover switch 630A 04P-22 Nos. LK/Schneider/Legrand/ABB(c) Necessary Connection for changeover to changeover provided by Copper conductor of Size 120 Sqmm single core multistranded with copper lugs and same approved by Engr-in-Charge.(d) Drawing with marking of each DG Set shall be approved by Engr-in-Charge before placing the order.(e) Name plate for name DG Set shall provide in each Changeover Switch. |
| 82 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) double out door type, floor mounted, compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,p owder coated, having front and rear openable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming :- Copper Busbar with current rating capacity 1000 Amps-04 Nos not less than 1 MTR long mounted on insulators .Out Going :- 04 Nos separate outgoing busbar with 800Amps. |
| 83 | Loading, unloading and transportation of 500 kVA DG Set from Udhampur to OEM Authorized Dealer's Workshop at Jammu and back to Udhampur after carrying out repairs, including safe loading onto suitable hydraulic crane/trailer/truck, securing during transit, unloading at workshop, re-loading after repair, transportation back to site, unloading, positioning at designated location and all labour, T&P, fuel, toll taxes, insurance, transit risk, permits and incidental charges complete as directed by Engineer-in-Charge. |
| 84 | Dismantling of acoustic/weatherproof canopy of 500 kVA DG Set, disconnecting and dismantling engine from alternator and base frame including removal of coupling, guards, mounting bolts and associated accessories as required for carrying out repairs/overhauling, using chain pulley blocks, lifting tackles, hydraulic jacks and other necessary tools & plant. Reassembling and alignment of repaired engine with alternator and base frame, refitting canopy, coupling, guards, mounting bolts and all associated components, using chain pulley blocks, lifting tackles, hydraulic jacks and other required T&P, complete in all respects including labour, consumables and incidental charges and as directed by the Engineer-in-Charge. Note: The quoted rate shall be deemed to include only the cost of dismantling canopy, dismantling engine from alternator and base frame and reassembling, alignment of repaired engine of 500 kVA DG set for carrying out repairs/overhauling. |
| 85 | Overhauling of diesel engine of 500 kVA DG Set by inspection, calibration, machining, repair and replacement of minor components, consumables and wear parts required for restoration of the engine to OEM specifications. The work shall include reassembling the engine, refitting all components in their original positions with new gaskets, seals, O-rings, fasteners and fittings, carrying out alignment, adjustment and calibration, filling/replacement of lubricating oil, coolant and other consumables as required, conducting trial runs, load testing, testing and commissioning of the DG Set and ensuring satisfactory performance at rated parameters, complete in all respects and as specified and directed by the Engineer-in-Charge.Note: The quoted rate shall be deemed to include the cost of all minor parts, consumables, lubricants, coolant, filters, calibration charges, machining charges, OEM service charges, transportation, labour, testing and commissioning, whether specifically mentioned herein or otherwise required for successful completion of engine overhaul and restoration to OEM operating condition. Major components such as cylinder head assemblies, crankshaft, connecting rods, piston assemblies and other major engine parts shall be paid for separately. |
| 86 | Supply, laying, connection, testing and commissioning of PVC insulated, FRLS, copper conductor, 1100V grade, 150 Sqmm, single core, multi-stranded cable, conforming to relevant IS specifications, complete with all accessories, supports, saddles, clamps, ferrules, identification tags and termination, including making good disturbed surfaces, complete all as specified and directed by Engineer-in-Charge. |
| 87 | Supply and fixing of heavy-duty tinned copper compression lugs suitable for 150 Sqmm copper conductor cable, complete with crimping, insulation tape/heat-shrink sleeves, nuts, bolts, washers and all necessary accessories for proper termination, complete all as specified and directed by Engineer-in-Charge Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |