| 1 | Taking down old unsv Street light / flood light fittings in any position of any capacity for Repair by replacement of unsv spares ( SPD / Driver / Mcpcb etc ) and re-fixing the same in existing location.Note:- Spares for repair of street light fittings will be measured and paid under respective items. |
| 2 | S&F MCB, SP 10-32 Amps, 'C' Curve with breaking capacity 10 KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed. |
| 3 | Supply and fixing in replacement of automatic street light switch using infrared sensor based nature switch for automatic switching of street lights.Nature switch operation should be based on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off > 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs.The sensor along with suitable power contactors incoming outgoing MCBS SP and and automanual (sensor bypass selection option should be enclosed in a pole /wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 8 KW with circuit wiring min 10 sqmm copper wire 63 Amps contactor and suitable MCBs at both positions at incoming and out goings of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt(4 Nos) for fixing on pole / walll complete all as directed including taking down old one . Make: Healer Enterprises/Swadeep/Indo Asian |
| 4 | S&F in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete, lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection and impact resistance of IK07 with 10 KV Built-in-Surge Protection Device, road way light fitting with high power LED as light source of capacity 90 watts with suitable drivers, > 120 Lm/W efficacy,Operating voltage:120–270V AC, 50Hz etc and connecting with 1.5 Sqmm copper conductor PVC insulated three core weather proof cable etc, fixing to wall/pole , complete all as specified and directed. |
| 5 | All as per item No-4 above but 70 watts. |
| 6 | All as per item No-4 above but 60 watts. |
| 7 | S&F in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrossion resistant complete with driver and lamp die-cast aluminium IP66 flood light, suitable for highlighting architectural facade and general purpose lighting, with high power LED as light source of capacity 100 watts with suitable drivers etc and connecting with 4.0 Sqmm aluminium conductor PVC insulated twin core weather proof cable,Operation Voltage-120–270V AC, 50Hz,System efficiency>110/120 lumens/watt, 10kv SPD etc, fixing to wall/pole complete all as specified and directed. |
| 8 | All as per item No-5 above but 120 watts. |
| 9 | All as per item No-5 above but 150 watts. |
| 10 | All as per item No-5 above but 200 watts. |
| 11 | Supply, fixing, in replacement connecting and testing post top light fitting in spherical shape polycarbonate PMMA clear diffuser and IP65 protection, new generation energy saving and environmental friendly long life aesthetically desinged aluminium decorative luminaires with high power LED as light source of capacity 1X40 watts, fixed to Pole/Wall in any position including taking down old existing street light fitting of any type and capacity complete all as specified and directed. |
| 12 | Supply, fixing, in replacement connecting and testing post top light fitting in spherical shape polycarbonate PMMA clear diffuser and IP65 protection, new generation energy saving and environmental friendly long life aesthetically desinged aluminium decorative luminaires with high power LED as light source of capacity 1X25 watts, fixed to Pole/Wall in any position including taking down old existing street light fitting of any type and capacity complete all as specified and directed. |
| 13 | M&L for painting the existing LT steel poles of 9.0 Mtr long including cross arms, clamps, street light junction boxes etc with 1 coats of aluminium paint including throughly cleaning the existing surface, writing of pole numbers in yellow circle 15 cm with black paint on poles. Painting the poles up to 1.5 Mtr height with alternate bands 30 cm height (3 Nos black and 2 Nos Yellow) from ground level, complete all as specified and directed. |
| 14 | M&L for Painting the existing LT PCC poles with 1 coats of Cement base paint including painting of cross arms, clamps, etc with one coat of aluminium paint and providing alternative band of 30 cm width (3 black and 2 yellow) from bottom of pole to 1.5 metres height , writing of pole numbers in yellow circle15 cm with black paint on poles complete all as specified and directed. |
| 15 | S&F in replacement PVC insulated unsheathed/ sheathed cable with stranded Aluminium conductor 1100 Volts grade, flat twin core service cable of size 4 Sqmm conforming to IS:694/1990 with latest amendments ISI including disconnecting/taking out existing unsv/damaged old service cable complete all as specified and directed. Make : Richa/havells or equivalent. |
| 16 | All as per item No-10 above but of size 6 Sqmm complete all as specified and directed. |
| 17 | All as per item No-10 above but of size 10 Sqmm complete all as specified and directed. |
| 18 | S&F in replacement hot press moulded SMC junction/terminal box of size with internal diamensions of 200 x 140 x 95 mm with hinged door, incl provision of 2 way connector 415 Volts made out of polycarbonate or bakelite and 1 No MCB of 6 Amps with DIN bar, drilling holes for cable connections, connecting incoming and or out going cables by providing suitable size of cable lugs/glands, fixed on pole by means of clamps made out of MS flat iron of size 25mm x 3 mm 2 Set including dismantling of old unserviceable cable complete all as specified and directed. |
| 19 | Supply and fixing lantren of dia 60 cm for fixing of flood light, cap type to be fixed on the top of 9 m SP-31 Steel pole , made of MS pipe medium grade dia greater than the top dia of the pole of length 0.35 M supported by MS flat iron of size 50X6 mm 8 nos including two coat of aliminium painting over a coat of red oxide primer complete all as specified and directed. |
| 20 | Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) both in foundation and coping of poles complete all as specified iand directed and applying two coats of aluminium paint to pole surface complete all as specified and directed. Please Enable Macros to View BoQ information |
| 21 | Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) both in foundation and coping of poles complete all as specified iand directed and applying two coats of aluminium paint to pole surface complete all as specified and directed. Please Enable Macros to View BoQ information |