| 1 | Supplying and drawing following size of FRLS/ HFFR PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit etc. as required. |
| 2 | 3X1.5sq.mm |
| 3 | Supplying and fixing 5A to 32A rating, 240/415V, 10kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 4 | Single Pole |
| 5 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 6 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. |
| 7 | 4 X 16 sq. mm (28mm) |
| 8 | 4 X 10 sq. mm (28mm) |
| 9 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of 100watt LED Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5sq mm FRLS/ HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 10 | Making RCC foundation of size 450mm x 450mm x 1200mm with 1:2:4 (1cement, 2 coarse sand, and 4stone aggregate of 20mm) complete with 8mm dia MS bar for reinforcement along with centering & shuttering. Providing & fixing of with pole base plate dimensions 4no. 16X400mm S.S/G.I bolt with proper tighten with double nuts, spring and plain washers, 40mm dia HDPE flexible pipe including excavation & refilling of soil, with ramming, curing etc. as required. |
| 11 | Making RCC foundation of size 450mm x 450mm x 700mm with 1:2:4 (1cement, 2 coarse sand, 4stone aggregate of 20mm) complete with 10mm dia MS bar for reinforcement along with centering & shuttering. Providing & fixing of with pole base plate dimensions 4no. 16X400mm S.S/G.I bolt with proper tighten with double nuts, spring and plain washers, 40mm dia HDPE flexible pipe including excavation & refilling of soil, with ramming, curing etc. as required. |
| 12 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size in the RCC/HUME/METAL Pipe as required. |
| 13 | 4 X 16 sq. mm |
| 14 | 4 X 10 sq. mm |
| 15 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size direct in ground with 40mm dia HDPE Pe63 Pn6 Pipe including excavation and refilling the trench etc. as required. |
| 16 | 4 X 16 sq. mm |
| 17 | 4 X 10 sq. mm |
| 18 | Supplying, Installation, Testing and Commissioning of 6 metre height steel pole are made out of galvanized mild steel tube haveing (90mm dia x 3mm thik x 4000mm height at top & 140mm dia x 4.8mm thik x 2000mm height at bottom with cast aluminium base plate of 300mmx300mmx12mm) complete with single / Double brackets of 300mm x 700mm x 4mm as suitable to the site location and as per the direction of Engineer-in-charge, made up of Galvanised Mild steel tubes with cast aluminium embellishments suitable for single/ double/ triple/ four side post/ top/ down luminaries and primer coated along with polyurethane painting with having service window at the bottom comprising four way 25 amp connector terminal etc. complete as required.Make (Pole & Bracket: Havells / Bajaj / Twinkle Lux Max 140-600, Twinkle Lux Max -BKT-37A or equivalent. |
| 19 | Supplying, Installation, Testing and Commissioning of 3 metre height steel pole are made out of galvanized mild steel tube having (90mm dia x 3mm thick x 2000mm height at top & 140mm dia x 4.8mm thick x 1000mm height at bottom with cast aluminium base plate of 300mmx300mmx12mm) complete as suitable to the site location and as per the direction of Engineer-in-charge, made up of Galvanised Mild steel tubes with cast aluminium embellishments for single/ double/ triple/ four side post/ top/ down luminaries and primer coated along with polyurethane painting with having service window at the bottom comprising four way 25 amp connector terminal etc. complete as required.Make (Pole: Havells / Bajaj / Twinkle LuxMax 140-300 or equivalent. |
| 20 | Supplying, installation, testing and commissioning of 40w, LED Post Top fitting, 5700K, IP-65, output Voltage AC 100-270V, 50-60 HZ, energy saving, the fixture are made of die cast aluminum base and spun aluminium round top. LEDs are mounted directly on die cast aluminium heat sink. A thermoformed P.C diffuser is provided in clear / opal with high power LEDs complete with suitable dia reducer on existing pole etc. as required.( Havells LHEVBHP7PN6K040/ Polycab PCGLPT0140C/ Twinkle LUX-PT-153) or equivalent. Please Enable Macros to View BoQ information |