| 1 | M&L for Repair/Maintenance/servicing of ACB any capacity/any type by cleaning the ACB by using air blower, tightening of connection/controls, checking of all fuses, sealing of ACB at bottom, repairing of ACB at bottom, repairing of mechanical parts, oiling/greasing of all moving -parts and carrying out following checks for smooth functioning complete.(a) Visual Inspection,(b) Checking of funtional locks, interlocks, signaling devices. (c) Checking of suitablility and correct operations of protections, control instruments and electrical connection of the circuit breaker operating mechanism. (d) Checking of Tripping Mechanism operation. (e) checking of standard voltage at PT. (f) Checking of breaker ON/OFF operation manually and electrically. (g) relay setting. (h) Checking of IR value of ACB. |
| 2 | Supply and fix in repair Neutral CTs for ACB 1000A (NCT ) in existing make complete all as specified and directd |
| 3 | Supply and fix in repair Under Voltage Trip Device (UVT) for ACB 415/220V AC in existing make complete all as specified |
| 4 | Supply and fix in repair spring charging motor for ACB 110V/230V in existing make complete all as specified and directd by Engineer in charge |
| 5 | Supply and fix in repair shunt trip closing coil for ACB 110/220V/DC in existing make completer all as specifed and directed by Engineer in charge |
| 6 | Supply and fix in repair main CTs for ACB 1000/1250/1600A in existing make complete all as specified and directed by Engineer in charge |
| 7 | Supply and fix in repair adaptor type terminal for 3pole/4 pole ACB 1000/1250A in existing make complete all as specified and directed by Engineer in charge |
| 8 | Supply and fix in repair adaptor type terminal for 3pole/4 pole ACB 1600A in existing make complete all as specified and directed by Engineer in charge |
| 9 | Supply and fix in repair door inter lock for LT ACB any capacity and make complete all as specified and directed by Engineer in charge |
| 10 | Supply and fix in repair spring charging indication switch for ACB in existing make complete all as specified and directed by Engineer in charge |
| 11 | Supply and fix in repair trip indication switch for ACB in existing make complete all as specified and directed by Engineer in charge |
| 12 | Supply and fix in repair Earth falult relay for MCCB 400A in existing make complete all as specified and directed by Engineer in charge |
| 13 | Supply and fix in repair Earth falult relay for MCCB 500A to 800A in existing make complete all as specified and directed by Engineer in charge |
| 14 | Meterial and Labour for Repair/Maintenance/servicing of Automatic Power Factor correction capacitor banks, of any cpacity including repair/replacement of defective/un-serviceable parts during maintenance period, attending to breakdown as and when it is occurres,and testing of capacitor banks as per manufacture's instruction for smooth and effficient functioning of capacitor panels and Power Factor should always be maintained more than 0.95Note :- (i) The rate quoted shall be deemed to be included for taking out defective spares & fixing of new spares. (ii) Cost of spares required for replacing shall be measured and paid separately. |
| 15 | Supply only cylindrical type coapacitor 440 V 50 Hz 2 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 16 | Supply only heavy duty cylindrical type coapacitor 440 V 50 Hz 3 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 17 | Supply only heavy duty cylindrical type coapacitor 440 V 50 Hz 4 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 18 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 5 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 19 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 7.5 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 20 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 10 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 21 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 12.5 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 22 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 15 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 23 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 20 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 24 | Supply only heavy duty cylindrical type coapacitor 480 V 50 Hz 25 kVAr 3 PH complete all as specified and directed by Engineer in charge |
| 25 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire indoor type n, dust proof front operated with adequate air ventilation at sides and back fabricated out of 2 mm thick CRCA sheet single door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, suitable to accommodate and including the following mentioned fittings; floor mounted with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories all as specified and as directed comprising the following:- (i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 800 Amps for phases and neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment.(ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches.(iii) Voltmeter (iv) Ammeter (v) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) MCCB 630 Amps,415V, 4 Pole, 50 KA - 01 No (Incoming)(vi) MCCB 200 Amps, 415V, 4 pole,35 KA - 03Nos (Out going)(vii) MCCB 125 Amps, 415V, 4 pole, 25 KA - 05 Nos (Out going) |
| 26 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire Outdoor type n, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, suitable to accommodate and including the following mentioned fittings; floor mounted with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories all as specified and as directed comprising the following:- (i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 400 Amps for phases and neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment.(ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches.(iv) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) Change over swich 200 Amps,415V, 4 Pole, (Incoming)(vi) MCCB 200 Amps, 415V, 4 pole,35 KA - 01Nos (Incoming)(vii) MCCB 100 Amps, 415V, 4 pole, 25 KA - 03 Nos (Outgoing)(vii) MCCB 125 Amps, 415V, 4 pole, 25 KA - 02 Nos (Outgoing) |
| 27 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, suitable to accommodate and including the following mentioned fittings; floor mounted with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories all as specified and as directed comprising the following:- (i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 600 Amps for phases and 200 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment.(ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches.(iv) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) MCCB 400Amps, 415V, 4 pole,50 KA - 01Nos (vii) MCCB 160 Amps, 415V, 4 pole, 35 KA - 03 Nos (vii) MCCB 125 Amps, 415V, 4 pole, 25 KA - 02 Nos |
| 28 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 160 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts all as specified and as directed(a) 4 Pole 255 Amp power Contractor, AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB, 250 Amps 4 pole 35 KA 50 Hz - 02 Nos (c) Panel should be Internally prewired with suitable size of copper conductor PVC insulated cable with colour coding - 01 job (d) 2 pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element - PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j) Digital type DC Voltmeter, 0 to 30 VDC - 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted - 01 No including taking down old AMF panel |
| 29 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 30 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts all as specified and as directed(a) 4 Pole 63 Amp power Contractor, AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB, 63 Amps 4 pole 35 KA 50 Hz - 02 Nos (c) Panel should be Internally prewired with suitable size of copper conductor PVC insulated cable with colour coding - 01 job (d) 2 pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element - PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j) Digital type DC Voltmeter, 0 to 30 VDC - 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted - 01 No including taking down old AMF panel |
| 30 | Supply and installation, testing, commissioning, factory made, outdoor type, AMF Panel board, suitable for 100 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete , Multifunctional AMF Controller with digital display, battery charger 12/24 V all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts all as specified and as directed(a) 4 Pole 160 Amp power Contractor, AC 3 duty, coil voltage 230 VAC - 02 Nos (b) MCCB, 160 Amps 4 pole 35 KA 50 Hz - 02 Nos (c) Panel should be Internally prewired with suitable size of copper conductor PVC insulated cable with colour coding - 01 job (d) 2 pole DC supply ON/OFF selector switch , rated voltage 12 V DC rated current 16 A - 01 No(e) 2 pole 3 way selector switch for auto/manual /test, rated voltage 230 VAC , rated current 16 A - 02 Nos (f) Indicating lamp LED type , Size 22.5 mm voltage 240 VAC. DG ON indicating lamp , Mains MCCB ON indication lamp , SC Supply ON indicating lamp. - 06 Nos (g) push button with element - PB1 - Engine start , PB2 - Engine stop, PB3 - DG contactor ON, PB4 - DG contactor OFF, PB5 - Mains contactor ON, PB6 - Mains contactor OFF (h) Aux control relay with socket 3 C/O 24 VDC, 30 A - 04 Nos (j) Digital type DC Voltmeter, 0 to 30 VDC - 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted - 01 No including taking down old AMF panel |
| 31 | Taking out / down old existing LT 1100 volt grade cables of size 120 Sqmm 3.5 core to 70 Sqmm 3.5 core , aluminium conductor, XLPE, armoured, removal to store for re-use or for credit, complete all as specified and directed Note : Excavation shall be measured and paid for separately |
| 32 | Relaying, jointing, testing and commissioning, already taken out existing LT under ground cables XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor cross sectional area 120 Sqmm 3.5 core to 70 Sqmm 3.5 core, 1100 volts grade, laid in trenches, along poles or passing through pipes or laid under floor or through/on walls etc, complete all as specified and directed. |
| 33 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm 3.5 core aluminum conductor 1100volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Returning filling & removal of earth, sand cushioning and bricks for protection of cable shall be measured and paid separately. |
| 34 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm 3.5 core aluminum conductor 1100volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Returning filling & removal of earth, sand cushioning and bricks for protection of cable shall be measured and paid separately. |
| 35 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 70 Sqmm 3.5 core aluminum conductor 1100volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Returning filling & removal of earth, sand cushioning and bricks for protection of cable shall be measured and paid separately. |
| 36 | Supply and laying / fixing , GI pipe light grade 100mm dia bore for cable protection fixed to pole/wall or laid under floor/roadv /pavement, including flat iron clamp, nut, bolt, wahser etc of required size and taking out old & removal, complete all as specified and directed.Note: Boring of holes under road etc. shall be measured and paid separately. |
| 37 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed. |
| 38 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. |
| 39 | Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed. |
| 40 | Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment. |
| 41 | Supplying and laying un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge |
| 42 | Laying only old un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge |
| 43 | Supply and fix in repairs MCCBs 200 Amp, Four Pole, breaking capacity 35 KA, 415 V - 50 Hz, fixed thermal and Fixed magnetic setting type, fixed in existing panel & connecting complete all as specified & directed |
| 44 | Supply and fix in repairs MCCBs 250 Amp, Four Pole, breaking capacity 35 KA, 415 V - 50 Hz, fixed thermal and Fixed magnetic setting type, fixed in existing panel & connecting complete all as specified & directed . Please Enable Macros to View BoQ information |
| 45 | Supply and fix in repairs MCCBs 250 Amp, Four Pole, breaking capacity 35 KA, 415 V - 50 Hz, fixed thermal and Fixed magnetic setting type, fixed in existing panel & connecting complete all as specified & directed . Please Enable Macros to View BoQ information |