| 1 | Decorative haritage pole in 4 Meter height. Pole upper section of length 3mtr is of dia 76mm and 1 meter bottom section of dia 114mm with decorative casting with base plate as per drawing. Provision for inside termination box with 4way connector & 1nos 6 AMPS MCB for local isolation with cover.Complete in all aspects with foundation bolts. |
| 2 | Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .A) Excavation of Pit for Foundation Size upto required B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. depth from Ground level C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. |
| 3 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .50mm |
| 4 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 16.0 Sq. mm 4 core |
| 5 | Add extra in item no. 60.1 to 60.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 6 | Providing & Fixing of IK08 IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with sand blast reflector. The System level Luminous efficacy ≥ 100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA. Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .Minimum lumen output 4500 lm Post top Luminarie |
| 7 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 2.5 Sq. mm 3 core |
| 8 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .16.0 Sq.mm |
| 9 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .10 SWG G.I. ( Hot Dipped ) Wire |
| 10 | Providing & Fixing of ISO certified company made TP&N 415 V AC-23A front handle operated switch disconnector fuse unit, cubical type, with metallic enclosure, as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 with HBC fuses including making connections with lugs, testing etc as required. Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .32 A Rating |
| 11 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRSingle pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating |
| 12 | Supply installation testing & commissioning of IK10 & IP65 3 phase 440V 50Hz , 7.5kw capacity centralized control and monitoring system panel (CCMS) made of fire retardent SMC steel material having lock system suitable for schedule on/off of Led & garden lights having following provision: *Dedicated control & metering unit. * pre programmed on/off schedule& remote on/off operation in case of bad weather/emergency /maintenance.Bypass faciltiy per phase. *Data capture of Energy consumption & other electrical data in real time & at pre deterimned interval. *RTC controller should be type tested in NABL approved lab & should be compitable with communication module 2G/4G which transmit data wirelessley and recorded to dedicated server or on cloud based architecture and aslo give command for schedule on/off of cluster of lights. Latiching relay/Bi-stable switch/isolation device should conferming to IEC-61-36/61037 & contactor also conferming to relevant IEC/IS standard13779.MCB conferming to IEC-62053/62054.With included pipe earthing as per IS:3043-1987 *Controller also have functional specification is for A) Lux sensor & Astronomical Clock mode :- 1)For switching ON---- < 60 lux for >30 sec or Twilight Duskwhichever is later 2)For switching OFF--->10 lux for >30 sec OR twilight Dawn whichever is earlier and B) for time schedule mode --- For switching ON/OFF---Time selected by user *Controller should connected to separate lithium battery to provide back up of minimum 8 hours in case of power outage. * unit should be supported by web/app based software package with detail information dashboard. * pole mounting/surface mounting stand. *inclusive of 2 year server & website hosting charges. Comprehensive on-site warranty of above Central Control & Monitoring System (CCMS)- Street Light Controller including SIM card or any other maintenance charges for 2 years. Please Enable Macros to View BoQ information |