| 1 | Taking down old cement pole with fitting complete all as specified and directed by Engineer-in-Charge. |
| 2 | M&L Hexagonal/Octagonal GI Pole 7m height including Base plate, bolt , nut & Suitable design bracket, necessary connector with control device & etc complete all as specified and directed by Engineer-in-Charge.Note:- Rate including Earth work and PCC measured and paid separately |
| 3 | S&F LED Street light 100W fitting complete with IP 65 and Surge Protection device complete all as specified and directed by Engineer-in-Charge. |
| 4 | Excavation in trenches not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out in hard/dense soil for complete all as specified and directed by Engineer-in-Charge. |
| 5 | Returning filling in soil including providing cable cushioning with riddled earth obtained from excavation, levelling watering and well ramming in layers not exceeding 25cm thick over the cushion layer complete all as specified and directed by Engineer-in-Charge. |
| 6 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 7 | Material and labour for DWC HDPE pipe of size 90/76 mm bore (OD X ID) for LT UG cable protection complete all as specified and directed by Engineer-in-Charge. |
| 8 | M & L for cutting Bitumen macadam / concrete foot path to a depth 0.75 mm with suitable mechanical cutter making good with cement concrete 1 : 2: 4 type B1 (20mm graded aggregate ) complete all as specified and directed by Engineer-in-Charge. |
| 9 | M&L for PCC 1:4:8, type D-2, (using 40 mm graded stone aggregate) for foundation, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 10 | Taking out old unserviceable LT under ground cable in sizes from trench and staging properly for disposable complete all as specified and directed by Engineer-in-Charge. |
| 11 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/ walls/ poles/ passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning including taking out old unserviceable cable for the following sizes complete all as specified and directed by Engineer-in-Charge. [a] 16 sq mm 4 core |
| 12 | [b] 25 sq mm 3.50 core |
| 13 | S&F in repair three core PVC insulated copper conductor 1.5 sqmm cable for making connection from light fitting complete all as specified and directed by Engineer-in-Charge. |
| 14 | Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300m complete all as specified and directed by Engineer-in-Charge. |
| 15 | M &L Point wiring(concealed) with 1.5 sqmm sigle core PVC insulated FRLS 1100 volts grade with copper conductor drawn in and incl non metallic rigid PVC conduit and all conduit accessories provision of MS terminal box suitable for modular frame and plates for housing Normal switches/ modular switches / sockets / regulators etc, including 1.5 Sqmm PVC insulated multistranded copper earth continuity conductor connecting to the common earth dolly etc complete all as specified and directed by Engineer-in-Charge for the following.Note: Rate quoted inclusive of Modular frame plates as per site requirement . |
| 16 | S&F Modular switch 1 way 6A, 1 module complete all as specified and directed by Engineer-in-Charge. |
| 17 | S&F Ceiling rose surface PVC insulated three plate \\"JUMBO\\" type 240 volts complete all as specified and directed by Engineer-in-Charge. |
| 18 | Rate inclusive of Cutting Brick/Stone wall for Hole Making Sutable fan size and finishing of wall with plasting and matching painting complete all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |