| 1 | Design, Supply, installation, testing & commissioning 46 HP outdoor unit with cooling of Variable Refrigerant Flow (VRF) system with multi indoor unit with outdoor units including individual controller for cooling type operation. Outdoor units equipped with highly efficient twin rotary compressors with inverter type compressor, special acryl precoated heat exchanger, low noise condenser fan, auto check function for connection error, having interconnected control wiring between indoor unit, outdoor unit & control panel and refrigerant piping housed in compact housing duly powder coated complete as required for trouble free operation, refrigerant should be R-410a complete all as specified and directed by Engineer-in-Charge. 01 No (Overall 46HP - Capacity & Numbers of the unit may vary) |
| 2 | Note for Out door unit:(i) Highly efficient Inverter Compressors: The unique design of the inverter compressor ensures that the refrigerant is directly injected in to the compressor chamber. The suction gas enters directly into the scroll, there is no super heat gain due to compressor motor assembly, this results in efficiency enhancement by upto 3%.(ii) VRF units are fitted with 100% inverter compressors. The unique logic of the system is that it optimally loads compressors in such a way that maximum efficiencies are achieved under any load condition. (iii) High COP and IPLV (Integrated Part Load Value).(iv) 100% capacity at 43 degree centigrade.(v) Non-stop operation even at 56 degree centigrade.(vi) Wide Operating Range: The system can operate from 10 degree centigrade to 56 degree centigrade in the cooling mode.(vii) Superior Accumulator Design: The VRF system is designed with the largest twin Accumulator in its class. This new design allows the system to perform seamlessly in low-load condition even below 30% without tripping.(viii) Weather Proof Outdoor Unit Design: Outdoor unit is specifically designed to handle extreme climatic conditions, corrosion and polluted atmosphere.* Powder coated GI sheet metal cabinets.* All hardware of anti-rust quality.* Conformal coating on PCBs to protect from dust and humidity.* Hydrophilic blue fin for better corrosion resistance.* Weather-proof enclosures for critical components.* Emergency Backup Operation, the compressor backup in outdoor units that have two compressors, the VRF system can function or maintenance down time of one compressor. |
| 3 | * Demand Control Mode or Economy Mode the capacity of the ODUs of the VRF can be set at 25%, 50% & 75% depending on the need.(ix) The system designed to operate across a wide voltage range from 320 volts to 460 volts resulting in high uptime even in erratic power conditions.Supply, installation, testing & commissioning indoor cassette unit of the following capacities, 4 way equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outdoor cabinet, drain pan and drain pump, cordless remote, cabling, vibration isolation, earthing, necessary supports etc as per specifications complete all as specified and directed by Engineer-in-Charge.2.3 TR Cassette Unit - 02 NosNote for Indoor units(a) Multi Level Filtration: Aesthetically superior with stylish design, very low noise, quiet operation, wide angle air flow to ensure even air distribution throughout the condition space.(b) Multi Speed fan: Various level of fan speed control are mus available for users comport and convenience.(c) Auto-Restart: Automatic re-start after power cut with all previous set parameters are restored.(d) Multimode functions: Various mode can be selected depending on the usage pattern and the comfort levels required. AUTO, COOL, DRY, SLEEP.(e) Flexible air flow patterns: Advanced louvers where swing can be adjusted to meet the needs air flow ventilation and direction required.(f) Cordless Remote Controller: Cordless remote controller having large LCD screen for better clarity, real time clock display, room temperature indication, displays of various mode-cool, fan, dry. Fan speed adjustable, inside room temperature adjustable from 16 degree to 30 degree centigrade.-10 Nos4.0 TR Cassette Unit - 08 Nos |
| 4 | Supply and Installation of Refnet joints (Refrigerant branch kit) for taking branches between various indoors as per VRF scheme drawings. The refnet joint set consists of both liquid and gas line branch kits complete all as specified and directed by Engineer-in-Charge.Indoor - 28 NosOutdoor - 02 Nos |
| 5 | VRF Central Controller - Supply, Installation, testing and commissioning of BMS compatible Network Interface and Central Remote Controller for monitoring and Controlling the VRF equipments in third party BMS as required basis. |
| 6 | VRF LOW SIDE WORKSInstallation , Testing, Commissioning and Handing over the VRF outdoor units -46.0 HP TOP DISCHARGE VRF ODU - 01 No Installation , Testing, Commissioning and Handing over of the following VRF Indoor Units : Cassette Unit.- 10 Nos |
| 7 | REFRIGERANT PIPING : Supply, Installation and Testing of Refrigerant piping, fittings and Y Branch with suitable thick tubular nitrile rubber insulation finished with laminated glass cloth.Suction line thickness - 19 mm and Liquid Line Thickness - 13 mm. All the tools and tackles required to install the refrigerant piping will have to be arranged by the vendor only without dependency on the client.Complete piping workmanship to be carried out as per recommended practice with the pipe sizes 1/4\\" to 1 5/8\\" of length -180RM ( Aprox) |
| 8 | Nitrogen Pressure Testing at site complete all as specified and directed by Engineer-in-Charge. |
| 9 | Supply and First Charging of R-410 additional refrigerant gas complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and installation of communication cable carried out with 2 core x 1.5 sqmm shielded cable including PVC conduit 225RM (Approx) complete all as specified and directed by Engineer-in-Charge. |
| 11 | VRF pipe protection finish for the exposed pipes (Suction & Liquid) : supply and application of one coat of Weatherprotekt coating, fixing 10 mil woven glass cloth, again one coat of Weatherprotekt coating and when finally dry complete with final coat of Weatherprotekt Coating complete all as specified and directed by Engineer-in-Charge. - 180RM (Approx). |
| 12 | Towards Charges for Anti Vibration Rubber Pads complete all as specified and directed by Engineer-in-Charge. - 02 Sets (Approx) |
| 13 | DRAIN PIPING : Supply, Installation and Testing of PVC heavy class drain piping insulated out of 9 mm thick Class O closed cell elastomeric nitrile rubber material finished with laminated glass cloth of approved make as per specification complete with supports, consumables, fittings, pipe sleeves, U trap & leak arresting of following sizes complete all as specified and directed by Engineer-in-Charge. Size 25 mm dia - 90RM (Approx)Size 32/40 mm dia -60RM (Approx) |
| 14 | CABLE TRAYS :Supply and erection of following sizes Hot Dip Galvanized perforated type 16G thick cable tray made out of sheet steel folded to required shape with adequate number of supports for Insulated refrigerant pipe and cable conduits - 300 mm width x 50 mm height (as required sizes) - 130RM ( Approx) complete all as specified and directed by Engineer-in-Charge. |
| 15 | Inland transportation to site, Lifting and placing at the designated space complete all as specified and directed by Engineer-in-Charge. - 01 Job |
| 16 | FABRICATED STEEL WORK :Supply, Fabrication , Cutting, Welding , Erection at site and painting of M. S. Angle structural steel work for outdoor unit location etc based on the approved drawings. The work should be carried out as per good manufacturing and installation practices in concurrence with approved drawing. Finally all steel work to be painted with one coat of zinc chromate primer and two coats of synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. required sizes / shapes -400Kgs (Approx) |
| 17 | Material and labour for providing maintenance free earthing with earth electrode of 50mm dia, 1.8mm thick ,3 mtr long, pure copperpipe, strips in pipe system fitted with pure copper strip 40X 6 mm from top to bottom, terminal hole of 12mm, pipe filled with conductive crystaline compound including 02 bags of earth life compound (25kgs each) as per IS 3043. Environmental test (salt mist test ), Bend test,Tensile strength , yeild /ratio ,electical resistivity test,complete with clamps, maintenence free,anti corrosive lead-free ,super conductive ,mineral based high grade earthing compound,to enhance soil conductivity.with resistence less than 0.5 ohms-meters, should be leach proof and sulphur free complete with earth inspection champer of dimension :width :320mm x 320mm , Height : 192 mm Weight :30 kgs, Including drilling of bore in any kind of soil complete all as specified and directed by Engineer-in-Charge.Note : THE RATE DEEMED INCLUSIVE OF SOIL RESITIVITY TEST, AS PER SOIL RESITIVITY TEST NO OF EARTH PITS TO BE DECIDE. i) Earth resitance value shall be less than 0.5 ohmsii) Copper strip 2x 3 mm for interconnection of earth pit (Brazing and copper bolt and nuts) shall be paid separtely under relavent item. |
| 18 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 19 | Excavation in trenches not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide and getting out in hard/dense soil complete all as specified and directed by Engineer-in-Charge. |
| 20 | Returning and refilling of excavated soil upto a depth of 30 cm after riddling the excavated soil for laying underground cables and post holes complete all as specified and directed by Engineer-in-Charge. |
| 21 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 22 | Material and labour for DWC HDPE pipe of size 90/76 mm bore (OD X ID) for LT UG cable protection complete all as specified and directed by Engineer-in-Charge. |
| 23 | Supply, install, testing & commissioning of factory made outdoor LT Panel board of sutiable size for 3 phase 415 volt of both side opening doubl door with push type metal lock, heavy duty wide hinges, seperate common across cable aley, made out 3 mm CRCA sheet with angle iron frame of size (50 x50 x 6 mm) and MC channel of size (75mm x 40mm) for panel base out door type , free standing cubical type totally enclosed weather dust and vermin proof with front and rear opening withlocking arrangment of 440 Volts , 3 Phase 4 wire 50 Hz having Copper Bus bar of capacity 300 Amps duly insulated with IP 54 protection,with powder coating including PCC foundation complete with following switches, space for 1 No vacant cubical suitable for 100 A, including LT XLPE cable end terminations with glands and lugs complete all as specified and directed by Engineer-in-Charge:Incoming:-i)MCCB 4P ,125A, 25KA adjustable type , 415 volts rating.- 1No.ii) On line 4 pole change over switch 125A, 415Viii) Multifunction LED meter complete with CT coil including set of indicating lamp RYB -1 set Bus - Bar 200 Amps capacity copper bus bar with sleeves. -4 Nos Out going - ii) MCCB, 3 pole, 25 KA ,fixed type, 415 volts 63 Amps rating.- 3 Nos . iv)Isolator TPN 32A - 1 No Please Enable Macros to View BoQ information |