| 1 | Supply, Installation, Testing and commissioning of standard 4.0 mtr High decorative pole with top post LED Fixture and foundation etc. Complete all accessories as required by E/I (AOR)(Make - VAK/ NERI/Mayfair/K-lite/Kesslec) |
| 2 | Errection of matelic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : graded stone aggretage 40 mm nominal size) foundation including excavation and refilling etc. as required bove 4.5 mtr and upto 6.50 mtr DSR Electrical 2018/I No. 11.3.1 |
| 3 | Supply & fixing of 16 mtr High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 3 mm. Top dia minium 150 mm, Bottom dia 360 mm base plate 32 mm thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 to 12 luminaries & its control gear boxes 1.5 HP power tool moter, 3 point suspension system with steel wire rope 6 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc completee in all respect.. (PS No. 652).(Make - Bajaj/Valmont/Transrail) |
| 4 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 140 to 150 Watt. Confirming to IP 66 protection complete in all respect.. Complete in all respects. (PS No. 1454) Cat-AAA (Make - LT/Bajaj /Havells/Crompton/Philips/Wipro) |
| 5 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. P.S. No. 501 (Polycab, KEI Havell's, make) |
| 6 | (1) 16 Sq.mm. 4.0 Core (PS No. 501) |
| 7 | 2) 25 Sq.mm. 3.5Core (PS No. 501) |
| 8 | S/F of palm or pin type copper tin plated cable socket (lugs) to the cable leads, insulating with tape and making connection etc. complete in all respects as per direction of E/I. P.S No. 504. |
| 9 | a) 16 Sq.mm. |
| 10 | b) 25 Sq.mm. |
| 11 | S/Laying of 90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. Complete in all respects. as per DSR 2018 item no. 14.16.2 page no. 49 |
| 12 | S/Laying of 63 mm dia (OD 63 mm & ID 51 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench or Trenchless method if required but excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.1 page no. 49 |
| 13 | Supply and fixing of 40 Amp TPN capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint crossing of time switch TSO 100 series with contractors, HRC fuse, isolating swtich metering instrument & instrument box with CTs etc. in case of TPN, Complete in all respects. as per PS No. 807F |
| 14 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.(P.S. No 725A) |
| 15 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 3000mm, outer pipe 50mm, inner dia 25mm, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.(P.S. No 725B) |
| 16 | Supply & erection of overhead line with G.I. wire no. 8 to 4 SWG on poles/serivce bracket including binding etc. complete in all respect. as per PS No. 628 |
| 17 | Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.(AOR) |
| 18 | Laying old cement cocrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineerin-charge. (Old CC paver blocks shall be supplied by the department free of cost). |
| 19 | Providing and laying 60mm thick factory made cement concrete interlocking paver block kof M-30 grade made by block making machine with strong vibratory compaction of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of E/I (AOR) Please Enable Macros to View BoQ information |