| 1 | Supply, lnstallaion, Testing and Commissioning of standad 4.0 Mt High Decorative Pole as per drawing approved by department with top post LED Fiture, cable for light etc. Complete all accessories as required. As per direction of E/I. (AOR) 5 YearWaranty Make- Havells, Orent / Mayfair/ VAK/NERI |
| 2 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. DSR 11.3.1 i)Above 4.5 metre and upto 6.5 metre |
| 3 | ''S/L of Al. armoured cable PVC insulated Ar. served & sheathed cable 1100 V grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I.Complete in all respects . The armouring of the cable shall be properly connected with the earth conductor by clamps etc. UPPWD-2018, PS-501 b)- 16 sq. mm 4 core Make : Gloster/Universal/ Polycab/ Havells/ Diacab/Grandley/KEI |
| 4 | d)- 25 sq. mm 3.5 core |
| 5 | 'S/F of Plain or Pin type copper tin plated cable socket (Lug) to the cable lead, insulating with tape and making connector etc. Complete in all respects as per Direction of E/I UPPWD-2019, PS-504 'b)-16 sq. mm |
| 6 | c)-25 sq. mm |
| 7 | Supplying and laying of 90 mm dia (OD-90 mm & ID-76 mm nominal) size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required DSR-Electrical-2018, 14.16.2 Make-creator poly extrusion/duraline/rex/times/ narander plast/pioneer |
| 8 | S/F of 25x3 mm. G.I. Strip from earth electrode directly in the ground as required complete in all respects as per direction of E/I UPPWD-2018 (PS-716) |
| 9 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25mm x 3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. UPPWD-2018, PS 725B |
| 10 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000mm, outer pipe 50mm, inner pipe 25, terminal Dia 12 mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25 x 3 G.I . strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. UPPWD-2018, PS-725A |
| 11 | Supply and fixing following capacity of automaticstreet light cubicle control panel painted with anticorrosive alkali and acid proof paint consisting oftime switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN,complete in all respect. PSNO.807 i) 15 TPN |
| 12 | Cement concrete with 4 cm gauge approved stone ballast coarse sand & cement in the proportion of 8:4:1 including supply of all materials, labour, Tools & Plants etc. Required for proper completion of the work. (SOR) |
| 13 | Demolishing R.C.C. Work Manually by mechnical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of E/I. (AOR) |
| 14 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. 15.2.1 Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) 15.2.1 DSR(Civil)-2018 P-258 |
| 15 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required.bituminous portion (DSR-2018 Item No-16.13.1 ,P-272) |
| 16 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level-a)- 1:4:8 (1 Cement : 4 coarse sand(zone-III) : 8 graded stone aggregate 40 mm nominal size). (DSR Civil-18/I.No.-4.1.8/P-86) |
| 17 | b)- 1:2:4 (1 Cement : 2 coarse sand(zone-III) : 4 graded stone aggregate 20 mm nominal size). (DSR Civil-18/I.No.-4.1.3/P-86 ) |
| 18 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. (DSR-2018 (Elec.) Item No-12.42,P-43) Please Enable Macros to View BoQ information |