| 1 | EARTHING- Supplying,installation,testing & commissioning Of Earthing with copper earth plate 600 mm x 600mm x 3.15 mm thick ISI marked including accessories and providing masonary with cover plate having loccking arrangement and watering pipe etc (WITH charcoal and salt) as required as per direction of Engg.-in-Charge. |
| 2 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 3 | Providing and fixing 25 mm X 5 mm GI strip on surface or in recess for connections etc. as required. |
| 4 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 5 | Providing and fixing 50mm x 5 mm copper strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 6 | Providing and fixing 50mm x 6 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 7 | Supply and fixing of shock treatement charts duly laminated along with separate colour single line diagram laminated, to be fixed in Electrical control panel room. |
| 8 | Supply and fixing of first aid box with medicines complete with medicine with three years expiry date to be fixed in Electrical control panel room.. |
| 9 | Supplying of following Materials.- Supply installation of 33kV 3mm thick Class-C Rubber Mat as per IS-15652 and complete as per direction of Eng-in-charge.(Size-10mx1m) |
| 10 | Supply and fixing of Danger Board. |
| 11 | LIGHTNING ARRESTOR- Lightning Protection :- Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 12 | Supply of Roof conductor holder for parapet- PolyamideConductor holder:With M8 female thread or diameter 7mm, M8Screw to connect the conductor holder.Weather andtemperature resistant from -35 to +90 degree Celsius tested.Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 13 | Supply of Lightning counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6 in complete as per the direction of Engineer in charge. Make-OBO/Dehn/ABB |
| 14 | Supply of Polyamide roof cable holder for flat roof:DIN 48829 Form B1. Closed form with bottom. Filling weight1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 15 | Supply of Connector: For T cross and parallel connectors. Quickinstallation using hexagonal bolt M10X30 high-grade hot dipgalvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB |
| 16 | Supply of 1 mtr vertical air terminal with mounting accessorieson the flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical , mechanical and chemical as per IEC62561. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 17 | Supply of Vertical air terminal with accessories:Providing of Air terminalsas per IS-IEC -62305 part-3Nominal size Ø10/16 mm aluminium rod:2 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN48801) Suitable for high wind load.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 18 | Supply of Vertical air terminal with accessories:Providing of Air terminalsas per IS-IEC -62305 part-3Nominal size Ø10/16 mm aluminium rod:3 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN48801) Suitable for high wind load.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 19 | Supply for Providing of Stand for Fang Fix system 16 kg with base andclamp ,made up of frost resistant concrete and clamp testedupto 100KA lightning current . Make-OBO/Dehn/ABB |
| 20 | Supply for Providing of Stand for Fang Fix system 16 kg made up of frostresistant concrete. Make-OBO/Dehn/ABB |
| 21 | Supply of Test Joint (Folding Clamp) suitable to connect 8mmround conductor and max by 30x3 mm GI strip as specified indrawing and directed by Engineer.Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 22 | Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr HeightFor Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB |
| 23 | Supply of Galvanised Steel Flat 30X3 mm thickness from earthelectrode directly in ground as required. Flat conductor HotDipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 24 | Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 25 | Supply of flat conductor holder- Fit: FL 30, With mounting hole6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece fromhot-dip galvanised steel, Bottom section from polyamide, black.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 26 | Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB |
| 27 | Supply of UL Listed maintenance free ,Low carbon coppercoated earth rod of 3 metre electrode having diameter of 17.2mm with copper coating thickness of 250micron tested as perIEC 62561-2 Make-OBO/Dehn/ABB |
| 28 | Supply of universal clamp made of SS to connect rod with flatconductor Make-OBO/Dehn/ABB |
| 29 | Supply of Earth conductivity enhancing mineral compound shall be of 25kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB |
| 30 | Supply of The above arrangements shall be provided with Heavy dutyearth champer of 5000kg load bearing capacity to ensure thesafety of earthing system Make-OBO/Dehn/ABB |
| 31 | Installation of The above arrangements including all accessories as per Direction of Engg. In charge. |
| 32 | Supply delivery ,installation andcommissioning of LED Sign Board as per below specification of Box type Display Matter:-1-JUDICIAL ACADEMY CUTTACK (English Letter Red Color) Letter Height 24 Inch.2- (Odiya Letter Red Color) Letter Height 18 Inch3-Government of Odisha Logo (24X24 Inch) ACP Sheet:- Aluminum composite panel sheet(ACP) Outdoor type 3 mm (Viva, Alomax, Imperia Décor, Citi Bond ) Supporting of English Letter.Plastics Sheet: - 3mm Plastics Sheet (Yellow, Red) Color & Raising of 2.5 inch.(Gray) (Acast)L.E.D :- 0.3 to 1.5 Watts (Yellow, Red) Color (Samsung, GE, Osaram, Philips, LG) Power Supply: - SMPS (Switch mode Power Supply), RPS (Regulate Power Supply).In put Voltage 160 to 230 A.C./ Out put Voltage 12/24 Volts D.C. (Samsung, GE, Osaram, Philipes, LG). The panel should be supplied with astronomical timer and contactor for auto ON/OFF . The panel should be supplied with overvoltage and undervoltage relay with 20 kA TYPE 2 SPD.The panel should be outdoor type. The letter structure to be installed on the top of the building. It shall withstand 200 km/hr wind velocity, MS ANGLE with primer and paint as per need for sustainable fixture 2 inch Ms pipe fastened with concerte. The cost is inclusive of all the structures, LED light, timer control panel and all other accessories. Make-Cosign/Sign media |
| 33 | D.G. SET(500 KVA DG SET)- Supply, Transportation, erection, testing and commissioning of 3 Phase, 415V, 50Hz, water cooled multi cylinder diesel generator set with alternator of 500KVA ( Make -Kirloskar / Jakson/Mahindra/Captiva) out put contineous rating directly coupled Engine and Alternator with guard and mounted on a common base plate of Robust construction and complete with AMF panel having IP-52 protection, Acoustic Enclosure as per CPCB IV+ norms , sound absorbing material, to restrict sound level up to 75 dB up to 1 mtr distance and as per CPCB IV+ norms etc as per following specifications mentioned below. Warrentee period must be 2 years ALTERNATOR:The alternator of the output rating shall be 3 Phase, 415V, 50Hz, Ac , 0.8 P.F. lagging at 1500 RPM. The alternator is self excited, self regulated, and shall confirm to IS: 13364 of 1992 with regulation of +5% from no load to full load. degree of protections shall be IP21. ENGINE: Diesel Engine start, developing suitable BHP output at 1500 RPM with mechanical / electronic governing so as to enable the alternator to give 500KVA continuous output at 0.8 P.F. lagging at NTP conditions. The diesel engine shall be capable of providing 10% O/L for 1 Hr for every 12 Hrs of continuous running at full load. The engine with 1st filling of oil and Diesel etc.01. Exhaust pipe of required size and length with insulation or clading.02. Diesel tank suitable for 8 to 10 Hours running capacity.03. Residential Silencer.04. SMF Batteries with leads as per the Manufacturer standards. BASE PLATE: Common Base Plate of required size for mounting of Engine Alternator Set fabricated from MS Channerl and vibration damping arrangement with cushy foor mounting including paintng etc. as required. FOUNDATION: Suitable size Cement Concrete (1:2:4) foundation duly plastered and finished with neat coat Cement as required along with lightening protection system. , control cable of 15mtr 2.5sqmm 6core , civil foundation work. (The Manufacturing of DG set shall not in any case be more than six months old from the date of award of work) |
| 34 | S/I/T&Commissioning of Main LT indoor floor mounted TTA( Totally type tested standard) Type Main panel as per IEC:61439-I&II made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing.as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list. 80X10MM Separate Aluminium Earth bus bar should be installed.All the incomers shall have 65 kA 3P+N type 1+2 SPD with 125 A 4P MCCB, TMR based, 25kA, Ics=100%Icu. Mandatory provision of cable alley is to be given. ON/OFF/TRIP indication shall be given for all the feeders.Make of TTA panel-Schneider(Prisma)/Siemens(Siepan)/ABB(Ar2k). Incomer-1- 01 number 4p 1600A EDO TYPE ACB with 1. Micro Processer Based with Breaking capacity - Icu= Ics= Icw= 50kA for 1 sec having LSING Protection with Display-Current Metering with Last Trip Record Data. (Communication with On & Off Status indication for Remote Closing and Opening operation of breakers through Modbus RS485 protocol and uploading breaker status to Users Computer/SCADA.) (Make-Schneider(Masterpact NW) / ABB (E max2)/ Siemens (3WT) /Legrand (DMX3) . Incomer-2- 01 number 4p 1600A EDO TYPE ACB with 1. Micro Processer Based with Breaking capacity - Icu= Ics= Icw= 50kA for 1 sec having LSING Protection with Display-Current Metering with Last Trip Record Data. (Communication with On & Off Status indication for Remote Closing and Opening operation of breakers through Modbus RS485 protocol and uploading breaker status to Users Computer/SCADA.) (Make-Schneider(Masterpact NW) / ABB (E max2)/ Siemens (3WT) /Legrand (DMX3) . Incomer-3- 01 number 4p 800A EDO TYPE ACB with 1. Micro Processer Based with Breaking capacity - Icu= Ics= Icw= 50kA for 1 sec having LSING Protection with Display-Current Metering with Last Trip Record Data. (Communication with On & Off Status indication for Remote Closing and Opening operation of breakers through Modbus RS485 protocol and uploading breaker status to Users Computer/SCADA.) (Make-Schneider(Masterpact NW) / ABB (E max2)/ Siemens (3WT) /Legrand (DMX3) . Incomer-4- 01 number 4p 800A EDO TYPE ACB with 1. Micro Processer Based with Breaking capacity - Icu= Ics= Icw= 50kA for 1 sec having LSING Protection with Display-Current Metering with Last Trip Record Data. (Communication with On & Off Status indication for Remote Closing and Opening operation of breakers through Modbus RS485 protocol and uploading breaker status to Users Computer/SCADA.) (Make-Schneider(Masterpact NW) / ABB (E max2)/ Siemens (3WT) /Legrand (DMX3) ,Incomer from 40kWp solar PV- 01 numbers of 100A 4P Icu=100%Ics,25Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB Formula.Buscoupler- 01 number 4p 1600A EDO TYPE ACB with 1. Micro Processer Based with Breaking capacity - Icu= Ics= Icw= 50kA for 1 sec having LSING Protection with Display-Current Metering with Last Trip Record Data. (Communication with On & Off Status indication for Remote Closing and Opening operation of breakers through Modbus RS485 protocol and uploading breaker status to Users Computer/SCADA.) (Make-Schneider(Masterpact NW) / ABB (E max2)/ Siemens (3WT) /Legrand (DMX3) .1 No - PLC based logic contrller for 2 nos DG Set & 2 nos Transformer with Announciation system, auto syncronisation, auto load sharing. Out going- 04 numbers of 630A (40% to 100% In rated)4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB Formula . Out going- 04 numbers of 400A (40% to 100% In rated) 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB Formula, Out going- 06 numbers of 250A (40% to 100% In rated) 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB Formula, Out going- 04 numbers of 160A 4P MCCB,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA), Out going- 08 numbers of 125A 4P MCCB,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA), Out going- 06 numbers of 100-63A 4P MCCB,,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA), Instrument- (i) 18 numbers phase indicating lamp with toggle switch & HRC fuse., (ii) 06 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data., 5 no. 3P+N 65kA type 1+2 SPD with125 A 4P MCCB, TMR based, 25kA, Ics=100%Icu.(Make of SPD-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN) ( Make of MCCB -LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA)(iii) All the MCCB outgoing feeders shall have digital ammeter with class 1 CT of suitable rating. Make-Legrand/ABB/Siemens/Schneider(iv) All the incoming, outgoing feeders and bus coupler shall have ON/OFF/TRIP indication. |
| 35 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5 core x 300 sq mm Aluminium armoured Cable.(FOR Main PANEL) |
| 36 | 3.5 core x 240 sq mm Aluminium armoured Cable.(FOR DG incomer) |
| 37 | Supplying and making end termination with brass double compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge.3.5 core x 240 sq mm brass double compression gland and aluminium lugs |
| 38 | 3.5 core x 300 sq mm brass double compression gland and aluminium lugs Please Enable Macros to View BoQ information |