| 1 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 2 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm. |
| 3 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 4 | Supplying, Installation, testing and commissioning of earth pit of minimum dia. 100 mm size 3 mtr. Deep in hard rock soil, through machine or by any suitable means. Earth electrode consisting of 3 mtr. Long and 50 mm Dia. Size G.I electrode surrounded by highly conductive black fill compound chemical 2 bags (25 kg each) with necessary masonry encloser for 300 mm x 300 mm size GI earth pit cover complete as required. |
| 5 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 6 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 8 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a) 3 x 1.5 sq. mm |
| 9 | Fabrication, Supplying, Installation, testing, Commissioning of 12 metres semi high mast System with its accessorles Mast shaft shall be in one section, hot dip galvanized 4mm thick(Single dip) Inside & out sides & suitable for wind velocity as per IS 875 part .There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For semi High Mast head frame ,2 point suspension system ,5 X 2.5 sqmm Copper conductor with steel wire rope 5mm dia. (7/19 construction) single drum winch galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminaries symmetrically and its control gears boxes and lighting finial ,the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia - 3700 mm (approx.) - 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the semi high mast considering the safe soil bearing capacity at site as 10 T/sqm at 2 mts. Depth with all material i/c 4 Nos. S.P MCB, 1 No. Double pole 16 Amp. MCB etc as reqd. Logo/Name .of manufacturer shall be either embossed or Rivited plate on the pole. galvanization as per relevant IS. |
| 10 | Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size 25mmx 75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh i/c MV danger plate and grounding the protection system in suitable quality of CC etc as reqd. |
| 11 | Fabrication, supply & erection of 5.0 mtr height, minimum 3 mm thick, bottom dia of 130 mm & top dia of 70mm, base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplylng and fixing of 6 mm thick laminated mounted sheet inside the window and i/c providing and welding 3 nos. Gl strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor - 4 nos. & shorting links on DIN channel i/c providing and flxing DIN channel of suitable length, 6 Amp. SPMCB 'C' Curve characteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be either embossed or Rivited plate on the pole Galvanization as per relevant IS code etc as required. |
| 12 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm(L) x 450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -960mm long (approx.) - 8 nos. and reinforcement of cold twisted bar of 8 mm dia - 1400 mm (approx.) - 6 nos. (with 150 mm spacing) as required with supplying and positioning of 4 nos foundation bolts size 16 mm dia, 600mm long, J type i/c 2 nos template anchor plates of size 225 mm x 225 mm x 3 mm and providing DWC HDPE pipe for cable entry & exit as required for 3 m and 5 mtr pole. |
| 13 | DSR Civil 2018 110.10:Providing and fixing name board made of MS Sheet 90x60cm, 1mm thick with frame of MS angle 50x50x6mm, two diagonal braces at the back of the sheet of MS flat 40x6mm, total height of the board above ground level 2.40m, length of legs below ground 0.30m embedded in CC block 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) 30x30x45cm including excavation and removal of surplus earth with in 50m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in-Charge. |
| 14 | LED Street light fixture, powder coated pressure die cast aluminum body (System lumen efficacy ≥120 <135 lm/Watt)- Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80, under voltage and over voltage protection, EMI EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)- 150 Watt |
| 15 | Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-45, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80 , under voltage and over voltage protection,EMI EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement, suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).- 72 Watt |
| 16 | Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 32 mm dia galvanised pipes with tightening bolts complete as required. |
| 17 | Providing and fixing of stainless steal name plate of size 6x8 sq inch made of 20 guage sheet including engraved name of arae repersentative duly painted along with SS clamp nut bolt etc. as required. |
| 18 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm |
| 19 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 20 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required. Water bound macadam. Please Enable Macros to View BoQ information |