| 1 | Supply,Installation, Testing and commissioning of 11 kV VCB Panel Board(outgoing) (12 kV, 1250A, 25 kA, indoor, with O/C, E/F relays (Preferably ABB/REF615) (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port with necessary circuitry for the SCADA/DMS MFT's CMRs etc as per the existing setup of SCADA in vogue in the department .(The new panel should be in alignment with the existing panel set) CT Ratio 600-300/5A |
| 2 | Supply,installation,testing and commissioning of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) |
| 3 | Providing and laying of 11 kV 3-Core XLPE 300 mm² armoured, FRLS to be laid through HDPE pipe suitable for 300sqmm cable including cost of HDPE pipe |
| 4 | Supply,installation,testing and commissioning of 11 kV Indoor Heat Shrinkable Cable Termination Kits 300 sqmm 3-core |
| 5 | Supply,installation,testing and commissioning of 11 kV outdoor Heat Shrinkable Cable Termination Kits 300 sqmm 3-core |
| 6 | Supply,installation,testing, and commissioning of 11 kV Isolator, double break,3-pole, 630Amp, horizontal mounting Type, with Earth Switch |
| 7 | Supply and errection of 9 Mtr. Long Pole ( ST-410 SP33) |
| 8 | Providing and painting of ST Poles with One coat of Red Oxide and two coates of Aluminium Paint to give even shade (reputed brand) |
| 9 | Providing and fixing of Galvanised iron of sorts |
| 10 | Providing and laying of Cement bottoming of 9 mtrs long ST Poles in mix of 1:2:4 using 20mm crushed stone aggregate including shuttering, form work etc as per REC standards 0.48cum/pole. |
| 11 | Providing and fixing of Earthing of ST poles and isolators Complete by by GI pipe 40mm 3 mtr long through GI strip 25x3mm, as per REC standards. |
| 12 | Proviidng,Laying,stringing ,tensioning and binding of 100sqmm ACSR conductor as per REC construction standard (with latest amendments if any |
| 13 | Providing and fixing of Clamps of Sorts |
| 14 | Providing and fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 15 | Providing and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 16 | Providing and fixing of Anti climbing devices. |
| 17 | Providing and fixing of Danger plate. |
| 18 | Providing and fixing of PG Clamps for 100mm sq Conductor |
| 19 | Adjusting existing Cables for making way for new Cable and removing of debris and foilage in the existing trench and adjusting existing panels in the Receiving Station to pave way for new panel |
| 20 | Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements. |
| 21 | NOTE: ALL WORKS SHALL BE CARRIED OUT STRICTLY AS PER REC STANDARDS WITH LATEST AMENDMENTS THERE OF. Please Enable Macros to View BoQ information |