Name of Work:- RECONDUCTORING 11KV LINE FROM NEEROTH BOARDER AB TO KOOTTALIDA GROUND AB UNDER ELECTRICAL SECTION KOOTTALIDA
Sl. No.
Item Description
1
Dismantling (without damage) one km 11kV line (three conductors) including dismantling cross arm, insulators, disc, disconnecting jumper connection, rolling the conductor and stacking the materials.
2
Stringing of one km 3 PH 11kV line with XLPE Insulated ACSR Raccoon or equivalant (3 conductors) after fitting insulators, binding conductors to pin insulators using suitable tie and anchoring with wedge type anchoring clamps including cutting and removing tree branches wherever necessary excluding cut point works.
3
Transporting LT ABC by hired vehicle to a distance up to 5 km and carring up to 2 drum including loading and un loading using crane
4
Additional rate for refitting/redoing one Disc set while renewing any type of 11kV cut pole.
5
Renewing one 1.8m Channel cross arm on the 11kV Pole including dismantling and conveyance.
6
Providing bridging at Cut points for 3 PH 11kV line with XLPE Insulated ACSR Raccoon or equivalent (1 conductors) using IPC and respective conductors
7
Providing one Earth using GI earth pipe of size 38.1mm dia, 2.5m length including digging separate pit (0.45x0.45x2.5m) at a minimum distance of 1.5m away from the pole/structure and maintaining standard distance between different earth pipes in ordinary soil & backfilling.
8
Doing one cable end termination on HT ABC of sizes Up to 3x150+1x120 sqmm and connecting to existing MVT or other terminals,using the cable end termination kit supplied departmentally including charges for cable jointer etc. complete as per the direction of the departmental officers.
9
Providing one Coil Earth using No.8 GI-earth wire (50mm dia, 115 turns) including digging separate pit (0.45x0.45x1.5m) at standard distance away from the pole/structure in ordinary soil & backfilling.
10
Fitting one set (3No.) 11kV LA and giving connections excluding earthing.
11
Fiting One No MVT on existing cross arm excluding termination work (for One phase) of any rating for 11 kV AB Cable
12
Renewal of existing damaged/broken old 11kV Stay to the existing stay rod.
13
Fitting and providing one HT Stay for 11kV pole, including digging and back filling pit in ordinary soil. Please Enable Macros to View BoQ information