Tender For General-Thavalappara Lis-Thavalappara Lis -Renovation Of Electrical Installation At Thavalappara Lis-General Electrical Work
Tender Value
8.25 Lakhs
Estimated cost
Bid Submission
04 Jul 2026
2 days left
EMD
20642
Bank guarantee accepted
Document Fee
1825
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Thrissur → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for General-Thavalappara Lis-Thavalappara Lis -Renovation Of Electrical Installation At Thavalappara Lis-General Electrical Work
BOQ
| Sl. No. | Item Description |
| 1 | Electrification |
| 2 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 3 | 90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 4 | 90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture |
| 5 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 6 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 7 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 8 | OD357243/2025-2026:Supply and fixing of LED bulb 5/7 w |
| 9 | OD210/2026-2027:Supply and fixing cast aluminium stove enameled bulkhead fitting with deep drawn anodized aluminium body, epoxy powder coated, heat resistant prismatic glass cover suitable for 7 W LED to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the originalwiring and making good the surface as required including 7 W LED lamp. |
| 10 | 90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 11 | 90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps |
| 12 | 1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 13 | 1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 14 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 15 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 16 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 17 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 18 | 1.21.5:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.50 mm |
| 19 | 90.14.28.2:S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor |
| 20 | 90.14.28.9:S & F Motor starters of the following ratingsFully automatic star delta starter for 50HP motor |
| 21 | 90.14.24.1:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors. |
| 22 | 90.14.24.8:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors. |
| 23 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)8 way, Double door |
| 24 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 25 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 26 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 27 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 28 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 29 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 30 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 31 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 32 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 33 | 90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 34 | OD44466/2026-2027:Supply and fixing of Spreader/ terminal adapter kit with shroud in the existingmicroprocessor based 4 pole MCCB of rating 160 to 250 A(8 pieces) |
| 35 | 90.14.11.3:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 250A to 400A with CBCT. |
| 36 | 90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A. |
| 37 | 90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 38 | 90.14.11.9:MCCB AccessoriesSupply and fixing auxiliary switch (1 NO + 1 NC) in the existing MCCB of rating up to 630 A. |
| 39 | OD357259/2025-2026:Supply and providing LED indicators for all voltage ranges - Blue Colour |
| 40 | OD357238/2025-2026:Supply and providing LED indicators for all voltage ranges - Red, Green, Black,Yellow or Orange Colour |
| 41 | OD357257/2025-2026:Supply,fixing and installation of Three Phase Ammeter accuracy class 1-digitaltype |
| 42 | OD357255/2025-2026:Supply,fixing and installation of Three Phase Voltmeter accuracy class 1-Digitaltype |
| 43 | OD44422/2026-2027:S & F CURRENT TRANSFORMER -CURRENT TRANSFORMER - 100/5 A, 5 VA, accuracy class 1, Tape woundMetering CT |
| 44 | OD357265/2025-2026:CURRENT TRANSFORMER - 150/5 A, 5 VA, accuracy class 1, Tape woundMetering CT |
| 45 | OD357248/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps for interconnecting the control devices/ equipment including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required - 1.50 sq mm single runwith required sockets. |
| 46 | OD33277/2026-2027:Supplying and fixing .5 amps to 4 amps rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 47 | OD357263/2025-2026:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.250 Amp TP&N |
| 48 | 2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N |
| 49 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 50 | OD357239/2025-2026:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 25 sq mm 6 run |
| 51 | OD33391/2026-2027:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 25 sq mm 3 run |
| 52 | 1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm |
| 53 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 54 | 1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 55 | 90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm |
| 56 | 90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 57 | 9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm) |
| 58 | 9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 59 | OD357252/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands ofsuitable length and other dimensions noted along with each size ofglands for thefollowing sizes of cables as required.(25 sq - 95sq mm with 20 mm wide x 1.20mm thick clip) |
| 60 | OD44443/2026-2027:Supplying and providing earth clamps made out of copper strips of the followingsizes including cutting and bending the flat exactly to the shape of thegland,drilling necessary holes for nut & bolt, tinning the points of contacts and givingconnections to the main earthing system as required.(20 x 3 mm for earthingglands of size 120 sq mm to 185 sq mm) |
| 61 | 90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size |
| 62 | 90.12.24.3:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.6 Sq mm |
| 63 | 90.12.24.2:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.4 sq mm |
| 64 | 90.12.24.6:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.25 sq mm |
| 65 | OD357246/2025-2026:Supply and providing 25 mm green flexible hose and giving connection etc. |
| 66 | OD357237/2025-2026:Supply and fitting 25 mm brass heavy duty half turn ball valve. |
| 67 | OD44451/2026-2027:Fabrication, Supply, conveyance and erecting 32mm/nearest size PVC pipe 10kg/cm2 in recess with suitable specials such as coupler, union, bend, BRASS hose collor, BRASS FTA, Hose clip (SS)etc. and fixing on framework at suction/delivery side of Vacuum pump set using shellac, rubber packing, solvent, bolt, nut and washer etc. complete. |
| 68 | OD357249/2025-2026:Supplying and clamping the following sizes of corrugated pvc flexible conduit withnecessary compression gland with locking ring and check nut at terminationpointed using suitable size GI/painted MS saddles spacing not exceeding 60 cmson surface including making good the damages.20 mm dia . |
| 69 | OD357241/2025-2026:Supplying and clamping the following sizes of corrugated pvc flexible conduit withnecessary compression gland with locking ring and check nut at terminationpointed using suitable size GI/painted MS saddles spacing not exceeding 60 cmson surface including making good the damages.25 mm dia . |
| 70 | OD44462/2026-2027:Supplying and clamping the following sizes of corrugated pvc flexible conduit withnecessary compression gland with locking ring and check nut at terminationpointed using suitable size GI/painted MS saddles spacing not exceeding 60 cmson surface including making good the damages.50 mm dia |
| 71 | OD33380/2026-2027:Supplying and clamping the following sizes of corrugated pvc flexible conduit withnecessary compression gland with locking ring and check nut at terminationpointed using suitable size GI/painted MS saddles spacing not exceeding 60 cmson surface including making good the damages.40 mm dia . |
| 72 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 73 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 74 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 75 | 90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 76 | 90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 77 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 78 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 79 | 5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 80 | 5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 81 | 90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip |
| 82 | OD44473/2026-2027:Supply and installation of dust and vermin proof wall mounting , sintex make meter box of size 1000X690X215 mm GSMB 10069 ( IP65 ) or equivalent suitable for fixing KSEB meter,fuse units,CT etc hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment knock out for cable entry and exit IP65 with neutral CT as required including fixing it and making good the damages etc. as required. |
| 83 | OD18479/2026-2027:Supply and installation of dust and vermin proof wall mounting , sintex make meter box of size700X480X210 mm GSMB 7450 ( IP65 ) or equivalent suitable for fixing KSEB meter,fuseunits,CT etc hinged door construction for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry and exit IP65 withneutral CT as required including fixing it and making good the damages etc. as required.providing vision panel for the meter compartment knock out for cable entry and exit IP65 withneutral CT as required including fixing it and making good the damages etc. as required. |
| 84 | OD357264/2025-2026:Supply , Conveyance and fitting 125/160 A, 2 Way neutral links in the existing Meter box. |
| 85 | OD357262/2025-2026:Supply , Conveyance and fitting 200/250 A, HRC Fuse Base with suitable HRC Fuse |
| 86 | 90.3.18.4:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.50 mm dia with clamps made from 25 x 3 mm MS flat |
| 87 | OD18998/2026-2027:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required. |
| 88 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 89 | 14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 90 | OD357251/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuouslocation for clear vision. |
| 91 | OD44484/2026-2027:Supply and fixing Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour on panel board. |
| 92 | OD44485/2026-2027:Supply and providing 2mm thick Elastomeric fire retardant insulating sheet as per IS 15652/2006 to withstand 3.3 KV dielectric strength near panel/substation. |
| 93 | OD44486/2026-2027:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red withprimer coat of red oxide and written with white paint FIRE mounted on MS angleframe work/ wall bracket filled with fine sand, painting the bracket/ floor standincluding making good the damages, colour washing etc. as required. |
| 94 | OD44487/2026-2027: LT grade rubber gloves |
| 95 | OD44488/2026-2027:Supply and providing ABC 5 Kg Type type Fire Extinguisher with hose and clamps including fixing it to wall as required. |
| 96 | OD44489/2026-2027:Supply and providing 250 mm 2 in one screw driver Taparia make or equivalent - |
| 97 | OD44490/2026-2027:Supply and providing 130 mm Neon line tester Taparia make or equivalent. - |
| 98 | OD18541/2026-2027:Supply of fuse puller up to 630 Amp |
| 99 | OD44515/2026-2027:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required in Panel board/DB's- 2.50 cm, 4 cm or 5 cm height. |
| 100 | OD44516/2026-2027:S/F Cable alley, 100 x 40 mm aluminium anodised legend plates on panel board |
| 101 | OD44517/2026-2027:S/F Bus bar chamber, 100 x 40 mm aluminium anodised legend plates on panel board |
| 102 | OD357260/2025-2026:Supply and fixing single phasing preventer SM 301 GIC/ L&T or equivalent and giving connections as required |
| 103 | OD44596/2026-2027:supply, Installation, testing and Commissioning of 3 HP Monoblock Vacuum pump set KIRLOSKAR KV30 THREE PHASE 3HP (2.2KW) 11/4 X 11/4 MONOBLOCK or equivalent |
| 104 | OD44600/2026-2027:Charges for rewinding the burnt rotor/stator - separate motor in to stator and rotor, dismantling the damaged rotor/stator winding from the rotor/stator slots, cleaning the slots neatly, insulating the slots with correct class of insulating paper, winding the rotor/stator with good quality correct gauge of super enamelled copper winding wires, closing the rotor/stator slots with fibre wedges, putting proper inter layer insulation, connecting the coil end connection, providing new stator/rotor lead wire, steel binding the overhang with proper insulation at both ends, heating the coils and varnishing with good quality insulation varnish, keep it for drying, reassembling and test running. |
| 105 | OD33494/2026-2027:Leading the burnt motor power greater than 30 HP and up to 59 HP ( already dismantled) from pump house to the nearest road side, loading into the vehicle, including charges for loading and unloading etc. |
| 106 | OD33495/2026-2027:Leading the rewound motor 31 to 60 HP from workshop to pump house includingloading into the vehicle , unloading and conveying to the base plate etc. |
| 107 | OD33498/2026-2027: Refitting 31-60 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load |
| 108 | OD357254/2025-2026:Dismantle old panel board, angle iron frame work, cables, pipe etc. from site and convey the same into departmental store. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jun 23, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 04, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysJul 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender