| 1 | (A) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(C) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted typewith Class-'F' insulation, conforming to IS-325.(D) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plasteredwith anti vibration pads. |
| 2 | 2280 lpm at 70 m Head |
| 3 | (A) Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required:(Diesel Driven Pump)(B) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(C) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulatedwith 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event offault with audio indications, painted with post office red colour etc. as required.(D) M.S fabricated, common base plate, coupling, couplingguard, foundation bolts etc. as required.(E)Suitable cement concrete foundation duly plasteredand with anti vibration pads. |
| 4 | 2280 lpm at 70 m Head |
| 5 | (A) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(B)Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
| 6 | 180 lpm @70m head |
| 7 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : |
| 8 | Incomings630A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps Outgoings (Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 setsJockey Pump100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 setsDiesel Engine ControlControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication. Battery charger suitable for 12V/24 V DC with boost and trickle selector switch,0-30 V DC volt meter and 0-20 a DC mmeter.All standard relays and accessories for automatic operation of diesel engine.SYSTEM CONTROLLERDesigning. Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 9 | Providing & fixing of pressure switch in M.S. pipe lineincluding connection etc. as required. |
| 10 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
| 11 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 12 | 80 mm dia |
| 13 | 100 mm dia |
| 14 | 150 mm dia |
| 15 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motoralarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : |
| 16 | 100 mm dia |
| 17 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 18 | 150 mm dia |
| 19 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 20 | 250 mm dia |
| 21 | 200 mm dia |
| 22 | 150 mm dia |
| 23 | 100 mm dia |
| 24 | 80 mm dia |
| 25 | 65 mm dia |
| 26 | 40 mm dia |
| 27 | 32 mm dia |
| 28 | 25 mm dia |
| 29 | Supplying and fixing single headed internal hydrant valve with instantaneous Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 30 | Single Headed Stainless Steel |
| 31 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 32 | Stainless Steel (Grade 304) |
| 33 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 34 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling asrequired : |
| 35 | Stainless Steel (Grade 304) |
| 36 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 37 | 80 mm dia |
| 38 | 100 mm dia |
| 39 | 150 mm dia |
| 40 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories |
| 41 | Pendent Sprinkler |
| 42 | Horizontal Side wall sprinkler |
| 43 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete asrequired: |
| 44 | 1500mm |
| 45 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required |
| 46 | 150 mm dia |
| 47 | Cable and wiring |
| 48 | Supplying & laying of 2x1.5 sqmm fire alarm (FS) armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 49 | (A)Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(E)Suitable cement concrete foundation duly plasteredand with anti vibration pads. |
| 50 | 450 lpm at 35 m Head |
| 51 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required vsize to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 52 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required. |
| 53 | 4-way 150 mm dia MS pipe |
| 54 | Providing, laying, testing & commissioning of 'B' class heavy duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 55 | 150 mm |
| 56 | Supplying, installation, testing and commissioning of intelligent analog addressable photothermal detector complete with mounting base, complete as required. |
| 57 | Supplying and laying the XLPE insulated and sheathed FS armoured cables of 1.1 K.V. Cu conductor including supplying and making end termination with brass compression gland FRLS. |
| 58 | 120 sq.mm x 3 core armoured cable (Polycab) |
| 59 | 25 sq.mm x 3 core armoured cable (Polycab) |
| 60 | Providing and fixing Fire hose cabinet glazed door shutter and frame with hold fasts (frame fabricated from 40 x 40 x 5mm and shutter from 35x35x5mm M.S. angle) 1800 mm high x 1200 mm wide with locking arrangement, 4mm thick glass with 1.6 mm M.S. flats including all accessories, painting with one coat of steel primer and two coats of postal red enamel paint. The words “hose cabinet” to be painted on the box. |
| 61 | Providing and Fixing Power Type Stored pressure fire extinguisher 9 KG |
| 62 | Providing and Fixing CO2 Type Stored Pressure Fire Extinguisher 4.5 KG squeeze grip/wheel MS body |
| 63 | Providing and Fixing Flamelog ABC DCP Type Map-50 Wheeled Fire Extinguisher 50 Kg |
| 64 | Providing and fixing Water Mist Type Stored Pressure Fire Extinguisher 9 Ltr. |
| 65 | Providing and fixing fire man axe as required with test certificate of 20000 volts. |
| 66 | Providing and fixing 10 zone Annunciation panel for the Sprinkler System on A.C. supply with stand by battery complete in all respects. |
| 67 | Providing and fixing weather proof standard hose cabinet (750mm x 600 mm x 250 mm) out door type suitable for accommodating yard hydrants made of 1.5mm thick M.S. sheet having central opening glazed door including necessary locking arrangements, painting one coat of primer and two coats of postal red enamel paint and housing 2 Nos. canvas hose pipe and branch pipe as required. (The cabinet shall be floor mounted on suitable raised platform). The shutters are to be lockable type. The words “Fire Hose Cabinet” to be painted on the box. |
| 68 | Providing and fixing M.S. structure work fabricated from standard sections E.g. MS squarebars, flots, rounds, angles, channels including cutting to size drilling, welding, fixing & welding to insert plates in RCC structure members as directed by site incharge, including cutting and making good the walls, floors & RCC roof (for pipe supports, clamps, M.S. ladders & manholes for tank covers etc) including painting will two or more coats of enamel joint of approved colour over a coat of approved steel primer as for drawings & direction of the site In charge. |
| 69 | Core / hole cutting for passing 110mm dia pipe in R.C.C. slab, beam and roofs 100 mm to 150mm deep/thick for passing pipe etc. and repairing the hole after insertion of drain pipe etc. with suitable chemical with mixing of cement etc, including finishing complete so as to make it leak proof all complete as per direction of EIC. 100 mm dia |
| 70 | Supplying and installation of Fire pressure vessel of 450mm dia and 1m high fabricated from 8-10mm thick M.S. plate suitable for 10kg/sqcm. working pressure with accessories, painted with two coats of Postal red enamel outside over a coat of primer and epoxy paint inside for automatic operation of pump. (One for fire Main Wet Riser System and Second for Sprinklers System.) Please Enable Macros to View BoQ information |