| 1 | Excavation in trenches not exceeding 1.5 m width and not exceeding 1.5 m in depth and getting out in soft / loose soil for taking up / laying cable / pipe etc complete all as specified and directed. |
| 2 | Returning, filling including spreding, leveling watering & well ramming in laying not exc. 25cm for soft/loose soil, complete all as specified and directed. |
| 3 | Removal of excavated material at a distance not exc 50 mtr and dipositing where directed at a level not exc. 1.5 mtr above the starting point for soft / loose soil, complete all as specified and directed. |
| 4 | Supply and laying in trenches in road cross / floors tube galvanished iron light grade with all fittings for protection of cable of following dia/bore of pipe :- |
| 5 | (a) 40 mm bore |
| 6 | (b) 50 mm bore |
| 7 | Supply and lay in replacement and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with standerd aluminum conductor, 1100 Volts grade, of size 50 Sqmm 3.5 Core, complete all as specified and directed. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. |
| 8 | Supply and lay in replacement and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminum conductor, 1100 Volts grade, of size 35 Sqmm 3.5 Core, complete all as specified and directed. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. |
| 9 | Supply and laying in replacement XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 25 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing , complete all as specified and directed. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. |
| 10 | Supply and laying in replacement XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 16 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete all as specified and directed. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. |
| 11 | S&F Rigid non-metallic PVC conduit 20 mm dia exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. from PVC junction box to street light bracket for protection of cable fixing clamp on PCC poles drilled the hole and insert a PVC gutti and screwed suitable size screw and fix the clamp, complete all as specified and directed. |
| 12 | M&L for cable protection pipe double wall corrugated (DWC) high density polythne pipes (HDPE) of dia 75 mm with ISI marked (with CML No) with and including all fittings and jointing material for electric cable and laid in trenches as specified in IS 16098-2013 Part-2 complete all as specified and directed. |
| 13 | Supply, fixing and testing after jointing Cable Jointing Kit for 11 KV grade cable for indoor type end termination heat shrinkable joint complete with jointing material and accessories suitable for XLPE armoured aluminum cable of size 95 sqmm 3 core complete all as specified and directed. |
| 14 | Supply, fixing and testing after jointing Cable Jointing Kit for 11 KV grade cable for outdoor type end termination heat shrinkable joint complete with jointing material and accessories suitable for XLPE armoured aluminum cable of size 95 sqmm 3 core complete all as specified and directed. |
| 15 | Supply, fixing and testing after jointing cable jointing kit for 11 KV grade cable for straigh through heat shrinkable joint complete with jointing material and accessories suitable for XLPE armoured aluminum cable of size 95 sqmm 3 core complete all as specified and directed. |
| 16 | Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50 m below normal ground level, connected to galvanised iron earth strip 32x6mm up to test point with suitable GI nuts/bolts and brazed properly up to main board including earth pit in cement concrete 1:2:4 type B-1, precast RCC cover in 1:2:4 reinforced with expanded metal, with suitable handle, excavation and earth work in any type of soil and including medium grade GI watering pipe 25mm bore with funnel wire mesh and medium grade GI earth wire protection pipe 50 mm bore up to main board complete as shown in electrical plate no 3 of MES schedule Part-I 1991, connected to earthing testing point including taking out existing unsv earthing complete all as specified and testing on completion complete all as specified and directed. |
| 17 | Supply and fixing LED light fitting 1x30 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size, complete all as specified and directed. |
| 18 | Supply and fix MCB’s single pole with neutral, 6 to 32 Amps, 250 volts with ‘B’ curve,10 KA fixed in existing PVC box including connecting complete all as specified and directed. |
| 19 | Supply and fix MCB TPN, 40 to 100 Amps, 250 volts with ‘B, curve,10 KA fixed in existing PVC box including connecting complete all as specified and directed. |
| 20 | Supply and fix in replacement 200-210 Watt LED flood light with pressure die- cast aluminium housing, complete with all accessories, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purposelighting W Turo Floodlight luminaires with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66 Protection fixed in existing clamp and connecting with existing cable, including nuts, bolts and washer etc complete all as specified and directed.Make :Havells (Ordering Code - LHFPCZBFP46J200) or equivalent make as mentioned in Appx 'B' to PS. |
| 21 | Supply and fix in repair LED street light fitting of 60 W sealed optic luminaire with housing made of die cast aluminium with smooth finish powder coated for better environmental protection complete all as specified below:- (i) The fixture shall be designed so as to ave lumen maintenance of at least 70% at the end of 70000 hours. (ii) The luminaire should be operable with auto adjustable 120-240 volt supply using the same driver. Ambient temperature at LED should not be more that 70 degree centigrade. (iii) Power factor of the electronic driver should be at least 0.90 abd efficiency of the luminaire to be more than 85%. (iv) The fixture should be dark sky complaint. The fixture should use aluminium, MCPCB printed circuit boards for better thermal management. (v) The luminaire should throw the perfect amount of uniform lught with exactly the desired intensity, and best pole spacing , along with better light control. (vi) The luminaire shall employ indivdual optical lens for the each of the LED's to ensure better uniformity of light distribution. (vii) The fixute should be vibration resistance, if the fixture is also to be used in vibration prone areas like flyovers/bridges. (viii) Heat dissipation should be managed through a built in external heat sink. (ix) Colour rendering index of minimum 65 with color temprature of 4000K. |
| 22 | Supply and fix in repair LED street light fitting of 35 W/40W light sealed optic luminaire with housing made of die cast aluminium with smooth finish powder coated for better environmental protection complete all as specified below:- (i) The fixture shall be designed so as to ave lumen maintenance of at least 70% at the end of 70000 hours. (ii) The luminaire should be operable with auto adjustable 120-240 volt supply using the same driver. Ambient temperature at LED should not be more that 70 degree centigrade. (iii) Power factor of the electronic driver should be at least 0.90 abd efficiency of the luminaire to be more than 85%. (iv) The fixture should be dark sky complaint. The fixture should use aluminium, MCPCB printed circuit boards for better thermal management. (v) The luminaire should throw the perfect amount of uniform lught with exactly the desired intensity, and best pole spacing , along with better light control. (vi) The luminaire shall employ indivdual optical lens for the each of the LED's to ensure better uniformity of light distribution. (vii) The fixute should be vibration resistance, if the fixture is also to be used in vibration prone areas like flyovers/bridges. (viii) Heat dissipation should be managed through a built in external heat sink. (ix) Colour rendering index of minimum 65 with color temprature of 4000K. |
| 23 | Supply and erect in true vertical position Prestressed concrete pole, 9.0 metres long. of size 102mm x 152mm at top and 102 mm x 289mm at bottom class 10 complete all as specified and directed.Note: (i) PCC foundation & coping shall be measured & paid separately.(ii) Excavation earth work and PCC will be measured and paid for seperately under respective item of schedule \\"A\\". |
| 24 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation, filling and mass concrete in foundation of poles complete all as specified and directed. |
| 25 | M&L for plain cement concrete 1:3:6 type C-2 (using 20mm graded crushed stone aggregate) as in foundation, filling and mass concrete in foundation of stay assembly complete all as specified and directed. |
| 26 | M&L for cement concrete 1:2:4 type B-1(using 20mm graded crushed stone aggregate) as in benching, coping, including weathering slightly rounded or chamfered angles complete all as specified and directed. |
| 27 | Disconnecting the existing Unserviceable MCCB of 63 A Capacity, taking out from the panel board and supply and fix new MCCB four pole of 63 Amps, 25 KA breaking capacity as per site requrement, exiting capacity suitable for 415 Volt, 50 Hz, 4 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete all as specified and directed. |
| 28 | Disconnecting the existing Unserviceable MCCB of 100 A Capacity, taking out from the panel board and supply and fix new MCCB four pole of 100 Amps, 25 KA breaking capacity as per site requrement, exiting capacity suitable for 415 Volt, 50 Hz, 4 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete all as specified and directed. |
| 29 | Disconnecting the existing Unserviceable MCCB of 125 A Capacity , taking out from the panel board and supply and fix new MCCB four pole of 125 Amps, 25 KA breaking capacity as per site requrement,exiting capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete all as specified and directed. |
| 30 | Disconnecting the existing Unserviceable MCCB of 200 Capacity , taking out from the panel board and supply and fix new MCCB four pole of 200 Amps, 35 KA breaking capacity as per site requrement,exiting capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete all as specified and directed. |
| 31 | Material and Labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and directed.Note :- Due to dea sore area angle iron msut use the Hot Dipp and stainless steel nut bolts |
| 32 | S&F Rigid non-metallic PVC conduit 20mm dia exclusive of boxes (junction / terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. from PVC Junction Box to street light bracket for protection of cable fixing clamp on PCC poles drilled the hole and insert a PVC gutti and screwed suitable size screw and fix the clamp, complete all as specified and directed. |
| 33 | Surcafe excavation not exceeding 10 cm deep and averaging 5 cm deep and getting out grass, debries to make the surface free from grass and stones and debries at Pump House, STP plant,Sub statin etc complete all as specified and directed. |
| 34 | Servicing of transformer upto 400 KVA/200 KVA at carrying out insulation resistant test(HT-LT,HT-E & LT-E), BDV of Oil (top & bottom sample), Filtration & topping up of oil, test, quaterly resistance check of earth pits, arresting of leakage by proper tightening of terminals& joints,replacement of loose or burnt out gasket & proper sealing of valves etc complete all as specified and directed.Note: (i)The cost involved for oil filtration & topping with new mineral oil will be measured & paid separately.(ii) The contractor should produce all testing certificates immediately after testing. Moreover testing should be carried out by authorized OEM only (iii) The contracted labour manning the substation should immediately inform any oil leakage,change in colour of silica gel,level down of oil in conservator etc Please Enable Macros to View BoQ information |
| 35 | Servicing of transformer upto 400 KVA/200 KVA at carrying out insulation resistant test(HT-LT,HT-E & LT-E), BDV of Oil (top & bottom sample), Filtration & topping up of oil, test, quaterly resistance check of earth pits, arresting of leakage by proper tightening of terminals& joints,replacement of loose or burnt out gasket & proper sealing of valves etc complete all as specified and directed.Note: (i)The cost involved for oil filtration & topping with new mineral oil will be measured & paid separately.(ii) The contractor should produce all testing certificates immediately after testing. Moreover testing should be carried out by authorized OEM only (iii) The contracted labour manning the substation should immediately inform any oil leakage,change in colour of silica gel,level down of oil in conservator etc Please Enable Macros to View BoQ information |