| 1 | Identifying and rectifying the defects pertaining to internal electrification of any type and nature such as taking down defective switch/socket/ceiling rose/holders/fittings / fixtures any type, rectification of faulty electric circuits, tightening of loose connections, replacment of old u/s wiring/conduits/casing caping & connections etc. complete all as specified and directed. |
| 2 | Identifying and rectifying the defects pertaining to internal electrification of any type and nature such as taking down defective MCBs / MCB DBs/TPN/ TPN DBs any type, rectification of faulty electric circuits, tightening of loose connections, replacment of old u/s wiring/conduits/casing caping & connections etc. complete all as specified and directed. |
| 3 | NOTE FOR ITEM NO 1 to 2 :-(a) All T & P/Stationeries and labour team required comprising of 01 supervisor and minimum 04 Nos of trained electricians will be provided by the contractor daily as directed by Engineer in charge. (b) Representative of the contractor will be present in complaint cell of E/M & responsible for receiving & attending the complaints from 08:30 Hrs to 16:30 Hrs the time of lodging the complaint. In absence of rep of Contractor penal recovery as decided by GE shall be imposed & on contractor.(c) Cost of minor stores/parts such as screws,clamps,insulation tapes,nuts/bolts, nail of required size etc shall be deemed included in the above quoted item. However, major items such as switches, sockets, bell push, fan regulator etc shall be measured and paid separately under appropriate items of Schedule 'A'.(d) Complaints where complete replacement of circuit/point wiring required shall be measured under relevent item.(e) If contractor fails to rectify the complaint with in 24 hours after receiving, Rs 1000/- per complaint per day will be penalised.(f) Contractor will provide tools & dress to the electfician and helper working in the contract. (h) A complaint register will be maintained by the contractor bearing details of every coomplaint attended shall be entered by the contractor daily including details like building No, Location etc, and the register shall be signed by contrcator, JE and Engineer in Charge. The register will be submitted alongwith RAR/ Final bill for technical check.(j) All the items under Supply only items of BoQ shall be obtained from contractor under proper receipt voucher. |
| 4 | S & F in repair, switch piano flush type 5 Amps single pole one way complete all as specified and directed. |
| 5 | S & F in repair, switch piano flush type 15 Amps single pole one way complete all as specified and directed. |
| 6 | S & F in repair, socket out let multipurpose suitable for 2/3 pin 5 amp flush type complete all as specified and directed. |
| 7 | S & F in repair, socket out let multipurpose suitable for 3/5 pin 15 amp flush type complete all as specified and directed. |
| 8 | S & F in repair, switch socket combination 2 in 1, 3 pin, 5 Amp flush type complete all as specified and directed. |
| 9 | S & F in repair, switch socket combination 2 in 1 5 pin 15 Amps flush type complete all as specified and directed. |
| 10 | S & F in repair, Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body surface type 65mm x 50mm 2 to 3 terminal complete all as specified and directed. |
| 11 | S & F in repair, stepped type electronic fan regulator flush type on the existing phenolic laminated sheet (230 Volts, 50 Hz AC Supply) complete all as specified and directed. |
| 12 | S & F in repair, Batten/angle type holder insulated body with back plate complete all as specified and directed. |
| 13 | S & F in repair, bell push piano type 5 Amps complete all as specified and directed. |
| 14 | S & F in repair, electric bell buzzer ding dong 230 volt AC complete all as specified and directed. |
| 15 | S & F in repair, white / warm / cool white LED Light fitting 1x18 watt complete with all accessories 230V 50 Hz complete as specified and directed. |
| 16 | S & F in repair, LED mirror Light (white/warm/cool white )10 Watt 230V frequency 50/60 Hz integral sleek extruded polycarbonate LED channel with white acrylic cover, Power Factor not less then 0.9 as complete all as specified and directed. |
| 17 | S & F in repair, white/warm/cool white powder coated CRCA housing with LEDs 36W, 230 V, 50 Hz recess mounting LED 2 feet x 2 feet luminaries, Swamless front frame with flat white hight transmission acrylic cover complete with all accessories including connecting up with twin core twisted flexible copper conductor cable with suitable complete all as specified and directed. |
| 18 | S & F in repair, PVC gang box 4 way/8 Way to accommodate 5/15 Amps Switch and Socket complete all as specified and directed. |
| 19 | S & F in repair of Bakalite sheet size 9x11 , 8x5 & 5x5 complete all as specified and directed. |
| 20 | M&L LED light fitting 1x9W bulk head luminaries IP 65 complete with all accessories including LED lamp , connecting up with twin core twisted flexible copper conductor cable with suitable size of 230V 50 Hz complete all as specified and directed. |
| 21 | S & F in repair, decorative wall mounted luminaire,Stylish ,smartway in colour white / warm / cool including 9-12 Watt Stylish LED lamp and shape of lamp circular/rectangular/cylenderical etc complete all as specified and directed. |
| 22 | S & F in repair, LED sleek white / warm / cool white surface round ceiling mounted decorative down light fitting with PC cover suitable for 1x15/18 watt complete all as specified and directed. |
| 23 | S & F in repair, of Decorative stylish adjustable Wall spot or focus light (Metal body) of 1 x 15 watt 230 Volt in white/warm / cool white all as specified and directed. |
| 24 | S & F in repair, LED bulb white / warm / cool white 9/10/12 watt complete all as specified and directed. |
| 25 | S & F in repair, modular switch piano flush type, 6 amps, 230V AC,single pole, one way, complete all as specified and directed. |
| 26 | S & F in repair, modular switch piano flush type, 16 amps, 230V AC,single pole, one way, complete all as specified and directed. |
| 27 | S & F in repair,, modular socket out let with shutter multipurpose suitable for 2 pin and 3 pin 6 amp flush type, complete all as specified and directed. |
| 28 | S & F in repair, modular socket out let with shutter multipurpose suitable for 6 pin 16 amp, flush type completen all as directed by Engr-in-charge complete all as specified and directed. |
| 29 | S & F in repair, white / Brown / Wood Colour Modular Plate with modular base 3 module complete all as specified and directed. |
| 30 | S & F in repair, white / Brown / Wood Colour Modular Plate with modular base 6 module complete all as specified and directed. |
| 31 | S & F in repair, white / Brown / Wood Colour Modular Plate with modular base 8 module complete all as specified and directed. |
| 32 | S & F in repair, white / Brown / Wood Colour Modular Plate with modular base 12 module complete all as specified and directed. |
| 33 | S & F in repair, modular bell alongwith swith,6Amp, 220 V, single pole complete all as specified and directed. |
| 34 | S & F in repair,Electronic modular step fan regulator ,Two module, electronic,step type and connection complete all as specified and directed. |
| 35 | S & F in repair, MCB SPN 40/63 Amps 10 KA 230 volts \\"C\\" series complete all as specified and directed. |
| 36 | S & F in repair, MCB single pole 6 to 32 Amps 10 KA 230 volts \\"C\\" series complete all as specified and directed |
| 37 | S & F in repair, MCB single pole 40/63 Amps 10 KA 230 volts \\"C\\" series complete all as specified and directed |
| 38 | S & F in repair, MCCB 4 pole 125 Amps 25 KA 230 volts \\"C\\" series complete all as specified and directed. |
| 39 | S & F in repair, MCB TPN 63 Amps 10 KA 230 volts \\"C\\" series complete all as specified and directed. |
| 40 | Taking down carefully unserviceable aluminium point wiring (light, fan, socket bell or power) complete, (fittings such as switches, ceiling rose lamp holder, regulators, sockets, pendants) stacking at site and keeping in safe custody for taking credit, complete all as specified and directed. |
| 41 | M&L for point wiring with PVC insulated sheathed 1100 volt grade FRLS cable with multi stranded copper conductor of size 1.5 Sq mm (Nominal area) drawn through and in existing PVC conduit of any size ,fixing acessories inculding sunken anodised pressed terminal box not less than 1.2 mm thick covered with 3 mm thick bakelite laminated sheet cover of suitable size with suitable size screws for mounting switches, sockets, regulators with and including 1.5 sqmm FRLS multi stranded copper conductor drawing as continuous earth wire connected to main earth and earth dolly complete all as specified and directed for the following;- |
| 42 | One light point controlled by one switch 5 Amp. |
| 43 | One ceiling fan/exhaust fan point controlled by one switch 5Amp |
| 44 | One socket out let 5Amp controlled by one switch on same board. |
| 45 | One socket out let 5 Amp controlled by one switch on independent board. |
| 46 | One bell point 5 Amp controlled by one bell push on independent board. |
| 47 | M & L for Point wiring with PVC insulated, PVC unsheathed cable, single core, stranded, copper conductor cable 1.5 Sqmm size, 1100V grade, drawn into with and including PVC casing capping not less than 20mm wide, ISI marked, with 1.5 Sqmm unsheathed, stranded copper cable for continuous earth wire and including pressed steel concealed terminal boxes of reqd size made out of 1.2 mm thick sheet covered with 2.8 mm thick plastic laminated bakalite (hylam) ISI marked sheet suitable for switches/sockets/regulators complete all as specified and directed for the following :- |
| 48 | One light/fan point /bell point controlled by one switch |
| 49 | One socket out let 5Amp controlled by one switch on same board. |
| 50 | One point for socket outlet 5 amp on independent board |
| 51 | All as above Ser item No 42 but point wiring for one 3 pin 15 Amp socket outlet point controlled by one switch using 2.5 sqmm copper conductor cable with continuous earth wire of 2.5 sqmm copper conductor on independent board complete all as specified and directed. |
| 52 | S & F in repair, sheet metal enclosure distribution board SPN 12 way,IP-43, 230 V, 50 Hz double door with neutral, Earthing bar and din rail complete all as specified and directed. |
| 53 | S & F in repair, TPN 04 way,IP-43, 230 V, 50 Hz double door with neutral, Earthing bar and din rail complete all as specified and directed. |
| 54 | S&F sheet metal enclosure double door for distribution board factory made for MCB DB load link VTPN 4 way ,IP-43 ,including suitable size of MCCB 125 Amp as incomer, 125 Amp, 4 pole. (when MCB's are to be used) with suitable size of busbar complete,fixed flush in wall including chases wall for fixing DB and making good the distributed wall surfaces to match with existing specification including taking down all complete all as specified and directed. |
| 55 | M&L for sub main wiring with two single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 04 Sq mm drawing through and including concealed rigid non metallic PVC conduit medium grade ISI marked 20 mm dia including one single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 04 sq mm as earth continuity conductor connected to commen earth and earth dolly complete all as specified and directed.Note: Two runs of 4Sqmm FRLS PVC insulated unsheathed 1100 volts grade cable and One run of PVC conduit shall constitute as 1 RM for the measurement purpose. |
| 56 | Disconnecting & Taking down unserviceable ceiling fan 1400/1200 mm sweep 230 V, AC supply, single phase from position for winding and refixing for the same after winding, necessary connection complete all as specified and directed. Note winding and including repairs measured separately. |
| 57 | All as per item No 47 here-in-before but exhaust fan of size 450/380/300 /250 mm sweep |
| 58 | All as per item No 47 here-in-before but wall mounted fan size 450/400 mm sweep |
| 59 | M&L for collecting unserviceable ceiling fans 1200mm sweep 230 V, AC supply, single phase from E/M store yard of GE Nagrota , Dismantling the ceiling fan and taking out complete burnt winding from fan motor and rewinding the same with super enameled copper winding wire of existing gauge & size including thoroughly cleaning all the components of fan, oiling , greesing & painting with one coat of syntetic enemel paint after scrbbing and perparing the old painted surface of the fan with and including replacement of rusted /unserviceable nuts, bolts, canopy, split pin rubber reel , machine screws, shaft etc (rate included in the quoted items) including replacement of defective / unserviceable parts / spares as required reassembling the fan and testing complete deposinging the complete repaired fan to E/M store yard of GE Nagrota including transportation complete all as specified and derected. |
| 60 | All as per item No 50 here-in-before but ceiling fan of size 1400 mm sweep |
| 61 | M&L for collecting unserviceable exhaust fan 450mm sweep 230 V, AC supply, single phase from E/M store yard of GE Nagrota , Dismantling the exhaust fan and taking out complete burnt winding from exhaust fan motor and rewinding the same with super enameled copper winding wire of existing gauge & size including thoroughly cleaning all the components of fan, oiling & greesing painting with one coat of syntetic enemel paint after scrbbing and perparing the old painted surface replacement of rubber pads and depositing the exhaust fan to E/M store yard GE Nagrota including transportation and testing etc complete all as specified and derected. |
| 62 | All as per item No 52 here-in-before but exhaust fan of size 250 mm sweep |
| 63 | All as per item No 52 here-in-before but exhaust fan of size 300 mm sweep |
| 64 | M&L for collecting unserviceable PVC exhaust fan 250mm sweep 230 V, AC supply, single phase from E/M store yard of GE Nagrota , Dismantling the exhaust fan and taking out complete burnt winding from PVC exhaust fan motor and rewinding the same with super enameled copper winding wire of existing gauge & size including thoroughly cleaning all the components of fan,oiling & greesing and depositing the exhaust fan to E/M store yard GE Nagrota including transportation and testing etc complete all as specified and derected. |
| 65 | M&L for collecting unserviceable wall mounted fan 450/400mm, sweep 230 V, AC supply, single phase from E/M store yard of GE Nagrota , Dismantling the wall mounted fan and taking out complete burnt winding from wall mounted fan motor and rewinding the same with super enameled copper winding wire of existing gauge & size including thoroughly cleaning all the components of fan, oiling & greesing painting with one coat of syntetic enemel paint after scrbbing and perparing the old painted surface replacement of rubber pads and depositing the wall mounted fan to E/M store yard GE Nagrota including transportation and testing etc complete all as specified and derected. |
| 66 | Taking down carefully from position , ceiling fan 230 volts single phase 50 Hz 1400 mm sweep from the position & removing/ cleaning of dust properly, oiling and greasing of bearing including necessary repairs and refixing and connecting up with all requisite accessories complete all as specified and directed. Note ; necessary accessaries paid seperately here in after. |
| 67 | All as per item No 57 here-in-before but ceiling fan of size 1200 mm sweep |
| 68 | Taking down carefully exhaust fan 230 volts single phase 50 Hz 450 mm sweep from the position & removing/ cleaning of dust properly, oiling and greasing of bearing including necessary repairs and refixing and connecting up with all requisite accessories complete all as specified and directed. Note ; necessary accessaries paid seperately here in after |
| 69 | All as per item No 59 here-in-before but exhaust fan of size 250/300 mm sweep |
| 70 | Taking down carefully wall mounted fan 230 volts single phase 50 Hz 450 mm sweep from the position & removing/ cleaning of dust properly, oiling and greasing of bearing including necessary repairs and refixing and connecting up with all requisite accessories complete all as specified and directed. Note ; necessary accessaries paid seperately here in after. |
| 71 | S & F in repair of gun metal bush of required size suitable for ceiling fans and exhaut fans complete all as specified and directed. |
| 72 | S & F in repair of hanger for ceiling fan 1200mm/ 1400 mm sweep with nuts, bolts, washers complete all as specified and directed. |
| 73 | S & F in repair of aluminium blades for ceiling fan 1200 mm sweep complete all as specified and directed |
| 74 | S & F in repair of aluminium blades for ceiling fan 1400 mm sweep complete all as specified and directed |
| 75 | S & F in repair of bearing suitable for ceiling fan of any size complete all as specified and directed. |
| 76 | S & F in repair of bearing suitable for Exhaust fan/Air circulator/wall mounted fan of any size complete all as specified and derected. |
| 77 | M&L scrubbing and preparing the old painted surfaces of ceiling fan of size 1200/1400mm sweep complete including blade painting the same with white duco paint and writing the MES Nos of the fans, 25mm with black synthetic enamel paint and including oiling greasing complete all as specified and derected. |
| 78 | M&L scrubbing and preparing the old painted surfaces of exhaust fan of size 300/450mm sweep complete including blade painting the same with white duco paint and writing the MES Nos of the fans, 25mm with black synthetic enamel paint and including oiling greasing of any make complete all as specefied and directed. |
| 79 | S & F in repair canopy top and bottom for ceiling fans complete all as specified and derected. |
| 80 | S & F in repairs flexible twin core 23/0.0076 with copper conductor including connecting fan complete all as specified and derected. |
| 81 | S & F in repair 300mm (2 Feet long) long fan down rod with clamp heavy duty as required complete all as specified and directed. |
| 82 | S & F in repair, exhaust fan frame made out of MS sheet of any make and size of exhaust fan with suitable size of nut bolt and washers complete all as specified and directed |
| 83 | Material and labour for replacement of Unserviceable Louvers with new louvers of exhaust fan 450mm sweep complete all as specified and directed. |
| 84 | Material and labour for replacement of Unserviceable Louvers with new louvers of exhaust fan 300/380 mm sweep complete all as specified and directed. |
| 85 | S&F in repairs oil filled condenser of 2.5 MFD capacity after removing existing unserviceable condenser from any situation complete all as specified and directed. |
| 86 | All as per item No 76 here-in-before but condenser 4 MFD capacity |
| 87 | S & F in repair, stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc as required complete all as specified and directed. |
| 88 | S & F in repair,blade suitable for wall mounted fan 400/450 mm sweep fan complete all as specified and directed |
| 89 | S & F in repair, in replacement for shackle assembly for ceiling fan complete all as specified and directed |
| 90 | S & F in repair, ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed. |
| 91 | S & F in repair, exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers complete all as specified and directed. |
| 92 | S & F in repair, exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250/300m incl cutting of hole of suitable size and making good after installation of exhaust fan at site complete all as specified and directed. |
| 93 | S & F in repair, electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. complete all as specified and directed.Note: It should work on Pressure pump also |
| 94 | Taking down the water heater storage type of any make of any capacity. dismantling the water heater carefully from its position fixed on walls, reassembling the water heater after replacement of defective parts and reinstalling the water heaters to their original locations or as directed, commissioning and testing the water heater complete all as specified and directed.Note: Any material/part found unserviceable during servicing shall be replaced by the contractor and measured and paid separately under respective items. |
| 95 | S&F in repair of unsv PVC connection of any make with (ISI Mark) having10mm dia, 45 cm long with steel reinforcement suitable for hot water geyser outlet supply with 02 Nos of Unions/ cup shaped cover with washers complete all as specified and directed. |
| 96 | S&F in repair of unsv PVC connection of any make with (ISI Mark) having 10mm dia, 45 cm long suitable for cold water geyser inlet with 02 Nos of Unions/ cup shaped PVC cover with washers complete all as specified and directed. |
| 97 | S&F in repair of unserviceable inlet /outlet assembly of any make of geyser having six/seven/eight /nine hole suitable for water heater of capacity 25/50 litre complete all as specified and directed. |
| 98 | S&F in repair of unserviceable inlet /outlet assembly of any make of geyser having six/seven/eight /nine hole suitable for water heater of capacity 10 litre complete all as specified and directed. |
| 99 | S&F in repair of unsv rubber gasket suitable for six/seven/eight/ nine hole assembly of suitable size of water heater of capacity 50/25/10 ltr complete all as specified and directed. |
| 100 | S&F in repair of unsv 4'' long and 1/2'' dia Chrome plated bolt with suitable washers complete all as specified and directed. |
| 101 | S&F in repair of unsv split bottom cover (two pieces) suitable for water heater of any capacity duly painted, complete all as specified and directed. |
| 102 | S&F in repair of unsv neon indicating lamp, rectangular /round as required at site, complete all as specified and directed. |
| 103 | S&F in repair of unsv heating element 1.5 KW, single phase, 230 volt with triangular base suitable for 25/50 Ltr water heater complete all as specified and directed. |
| 104 | S&F in repair of unsv heating element 2.0 KW, single phase, 230 volt with triangular base suitable for 25/50 Ltr water heater complete all as specified and directed. |
| 105 | S&F in repair of unsv heating element 1.5 KW, single phase, 230 volt with round base suitable for 25/50 Ltr water heater complete all as specified and directed. |
| 106 | S&F in repair of unsv heating element 1.5 KW, single phase, 230 volt with round base suitable for 10 Ltr water heater complete all as specified and directed. |
| 107 | S&F in repair of long thermostat switch range upto 80”C suitable for 25/50 ltrs cap water heater complete all as specified and directed. |
| 108 | S&F in repair of unserviceable plug top 3 pin 15 Amps complete all as specified and directed. |
| 109 | S&F in repair of unserviceable safety nut for geyser of capacity 25/50 ltrs complete all as specified and directed. |
| 110 | S & F in repair of unserviceable Switch socket combination 3 pin 16A, flush type complete all as specified and directed. |
| 111 | S & F in repair of unserviceable sheet metal enclosure with socket plug top and MCB single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 Amp complete all as specified and directed. |
| 112 | M&L in replacement of sub main wiring with two single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 6 Sq mm drawing through and including concealed rigid non metallic PVC conduit medium grade ISI marked minimum 20 mm dia including one single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 6 sq mm as earth continuity conductor connected to commen earth and earth dolly complete including taking down existing UNSV complete all as specified and directed. |
| 113 | S&F submain wiring alongwith earth with the 2x 10.0 sq mm +1 x 10.0 sq mm earth(with phase,Neutral,Earth wire) wire size of FR is PVC insulated copper conductor ,single core cable in surface/recessed complete all as specified and directed. |
| 114 | S & F in repair Wireless Door Bell Kits chime for office with LED light 150 Meter operating range suitable ringtone 5 Level volume ,1 Reciever and 1 push button IP-44 Waterproof complete all as specified and directed. |
| 115 | Dismantling the solar panel (made of flat collector plates) of any description, material and labour for cleaning the glass by washing with using soft detergent, cleaning & de-scaling the inside surface of copper fins / tubes with suitable size of drill rod, wire brush & with circulating concentrated de-scaling solution(ORISCALE BLASTER) mixed with water in suitable proportion circulating through pump till the complete deposits/scale is removed and approved by the Engineer-in-Charge, brazing the leaking copper tubes, fixing the copper tube & fins properly in their respective positions, reassembling the solar system after servicing / maintenance including replacement of flanges made out of gun metal, nuts, bolts & washers, gaskets etc., fixing & installation of the solar flat collector plate in position and its testing to the entire satisfaction of Engineer-in-Charge complete all as specified and directed. |
| 116 | Opening of existing aluminium cladding from tank ,cleaning and stacking the same for reuse ,taking out glass wool and repairing the stainless steel tank and repairing the leakage by means of TIG welding as approved ,refilling of glass wool ,aluminium cladding by using old aluminium sheet complete all as specified and directed. Note:- Existing glass wool and aluminium sheet shall be reused, new glass wool and aluminium sheet if required shall be not measured and paid for separately complete all as specified and directed. |
| 117 | Disconnecting and taking out old existing unserviceable water heating element of any description and in any position and supply, fixing new water heating element hexagonal/ Rectangular/circle type of capacity 5 KW with suitable thermostat as per existing site including all necessary fittings complete all as specified and directed. |
| 118 | Disconnecting and taking out old existing unserviceable water heating element of any description and in any position and supply, fixing new water heating element hexagonal/ Rectangular/circle type of capacity 3 KW with suitable thermostat as per existing site including all necessary fittings complete all as specified and directed. Please Enable Macros to View BoQ information |