| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER (AF) BANGALORE NAME OF WORK : REPAIR/MAINT TO LT PANEL EXTERNAL ELEC SUPPLY AND DISTRIBUTION NETWORK SYSTEM INCL CABLES, PANEL AND CONNECTED WORKS AT POCKET II AND REP TO SOLAR WATER HEATING SYSTEM IN VARIOUS BLDGS AT CHAFB. CA NO: GE(AF)/B/ OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Dismantling & taking out LT burnt cable ends of any size from LT panel/LT feeder pillar box/trenches any type/size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks/PCC cover and sand returning filling the excavated soil complete all as specified and directed |
| 3 | Dismantling & taking out defective LT PVC/XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cables complete all as specified and directed for the following sizes:- |
| 4 | 25 sqmm to 70 sqmm ,3.5 core |
| 5 | 95 sqmm to 240 sqmm , 3.5 core |
| 6 | M&L for painting of steel tubular poles any length with one coat of aluminium paint and also marking ZEBRA pattern with alternate yellow and black colour to steel tubular poles 1.5m from the bottom of pole including numbering of poles using synthetic enamel paint complete all as specified and directed |
| 7 | M&L for painting of RCC/PCC poles any length with one coat of white cement based paint ans also marking ZEBRA pattern with alternate yellow and black colour to RCC/PCC poles 1.5m from the bottom of pole including numbering of poles using synthetic enamel paint complete all as specified and directed |
| 8 | M&L for painting of old surfaces of any description of steel / grill / sub-station MS gate etc, over 10 cm in width or girth with one coat of synthetic enamel paint complete all as specified and directed. |
| 9 | M&L for painting of old surfaces of any description of steel / grill / sub-station over 10 cm in width or girth with one coat of aluminium paint complete all as specified and directed |
| 10 | Excavation in trenches not exc 1.5 m wide and n.exc 1.5 m in depth, getting out for electric cable complete in any type of soil complete all as specified and directed |
| 11 | Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above starting point complete all as specified and directed |
| 12 | Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed |
| 13 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and directed. |
| 14 | M&L for sand filling (pulverized stone dust) for sand cushioning incl spreading & levelling for protection of cable complete all as specified and directed |
| 15 | M&L for boring of holes under road pavment/hard standing by manual boring including making good to the distrubed surfaces complete all as specified and directed |
| 16 | S&F for GI tubing light grade as in cable protection, laid in trenches/under road crossing/fixed on pole/wall/under floor with suitable iron clamps of required size incl taking down of old/unsv pipe complete for following sizes :- |
| 17 | 40 mm bore |
| 18 | 50 mm bore |
| 19 | 80 mm bore |
| 20 | M&L for repair/cleaning/servicing of existing/old feeder Pillar box / LT panel board of any size/type incl cleaning/dusting with compressed air, tightening of all electric connections to bus bar & switchgears, re-fixing of door with proper fixing & locking arrangement, replacement of wornout lugs, nut, bolts, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire and lugs, proper connection to main earth lead, glands to be provided/replaced as required at cable entries, fixing of door front & back side with proper locking arrangement, repair to PCC work as required at site and spray painting with powder coated paint with light grey paint in outer/inner side of panel after cleaning and preparing surface incl sign writing complete all as specified and directed |
| 21 | S&F (in replacement) following items in the existing LT panels / Feeder Pillar box / Distribution Board of any size / type (indoor or outdoor) installed at any location and connection with using aluminum lugs incl making necessary alteration in panel/door as required for proper fixing & connection incl taking down old/unsv one complete all as specified and directed :- |
| 22 | MCCB 4 pole 63 amps rating, 16/25 KA breaking capacity, 415 Volt |
| 23 | MCCB 100 amps rating, 16/25 KA breaking capacity |
| 24 | MCCB 125 amps rating, 16/25 KA breaking capacity |
| 25 | MCCB 160 amps rating, 36 KA breaking capacity |
| 26 | MCCB 200 amps rating, 36 KA breaking capacity |
| 27 | MCCB 250 amps rating, 36 KA breaking capacity |
| 28 | MCCB 350 amps rating, 36 KA breaking capacity |
| 29 | MCCB 400 amps rating, 50 KA breaking capacity |
| 30 | MCB TPN 63 amps, 415 Volt, 'C' curve |
| 31 | MCB TPN 100 amps, 415 Volt, 'C' curve |
| 32 | Digital Multifunctional Panel meter for measuring Voltage (0-500 V), Current, PF etc including necessary PT & CT's with connected acccessories |
| 33 | Digital type Volt meter (0 to 500 volts) three phase of size 96mm x 96mm or as per existing size in the LT Panel |
| 34 | Digital type Amp meter (0 to 500 amps) digital type, three phase of size 96mm x 96mm with suitable CTs or as per existing size in the LT Panel |
| 35 | Phase Indicator lamp, LED type, RYB with holder |
| 36 | Push button switch with NO/NC contacts 415 V, 6 A , with add on Aux Contacts and connected acccessories |
| 37 | Rotatory selector switch 3/4 way 10 A for Panel meter |
| 38 | S&F in replacement of MCCB sheet metal enclosure, factory fabricated, solid neutral link suitable for fixing of MCCB of 63/100/125 amps rating, enclosure to be fixed on wall with necessary clamping/fixing/grouting arrangement as required at site incl connection of required size of existing incoming/outgoing cables with suitable lugs complete for following type of MCCBs :-Note - MCCB shall be measured and paid seperately |
| 39 | For 3 pole MCCB |
| 40 | For 4 pole MCCB |
| 41 | M&L for spray Painting of LT Panel complete of any size/capacity after preparation of surface and applying two coats of synthetic enamel (smoke grey) paint and old steel surface, including sign writing and replacing the old/unsv danger notice plate complete all as specified and directed.(Note : New danger notice plate shall be measured and paid seperately) |
| 42 | S&F Danger notice plate, made out of 1.6mm thick MS sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for LT 20 x 15 cm size, fixed as in repairs, complete all as specified and directed. |
| 43 | S&F Outdoor type Bus bar chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including provision of 400 amp, 6 way Aluminium busbar, incl excavation,grouting/PCC/earth work etc as required for fixing of chamber and connecting incoming and out going cables complete with glands and lugs and testing incl taking down old/unsv chamber complete all as specified and directed. |
| 44 | S&F Outdoor type bus bar chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including provision of 800 amp, 6 way Aluminium busbar, incl excavation,grouting/PCC/earth work etc as required for fixing of chamber and connecting incoming and out going cables complete with glands and lugs and testing incl taking down old/unsv chamber complete all as specified and directed. |
| 45 | S&F and testing of LT busbar chamber board, made out of 3 mm thick CRCA sheet of size not less than 600x450x200mm duly painted with two coats of synthetic enamelled paint over one coat of red oxide primer wall mounted/semi-grouted in wall with locking arrangement, double door type, compartmentalised and provision for tapping incoming & outgoing electric connections with suitable size of lugs, glands, one MCCB will be mounted on proper din rales and comprising of the followings:-(i) Aluminium busbar chamber TPN of 300 amps rating (set of 4 strips)(ii) Phase indication lamp-set of 3(iii) MCCB 4 pole 415 Volts, 50 Hz, 100 amps rating, 25 KA breaking capacity - 01 NoNote :- Cost of busbar, indication lamp & MCCB shall deemed to be included in the quoted rate |
| 46 | Supply and laying or fixing or passing through pipe, 1100V grade, heavy duty cable with XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed incl taking down old/unsv cable complete all as specified & directed for following sizes:-Note :- Excavation & earth work, sand cushioning, PCC cover protection & GI pipe where required shall be measured & paid seperately |
| 47 | 10 sqmm 2 core |
| 48 | 10 sqmm 4 core |
| 49 | 16 sqmm 4 core |
| 50 | 25 sqmm 4 core |
| 51 | 35 sqmm 3.5 core |
| 52 | 50 sq mm 3.5 core |
| 53 | 70 sq mm 3.5 core |
| 54 | 95 sq mm 3.5 core |
| 55 | 120 sq mm 3.5 core |
| 56 | 240 sq mm 3.5 core |
| 57 | Disconnection of all incoming and outgoing cable connections, dismantling of exisiting LT Panel carefully with all accessories / parts and taking outside from the extg location/room and shifting at new location / place upto 1 KM distance with the help of all T&P, crane, trailor etc arrangement as required at site complete all as specified & directed. |
| 58 | M&L for installation and testing of shifted LT Panel (shifted under sl item No 56.00 here-in-before) of any size at new location after assemblying all connected accessoried / parts and incoming and outgoing cables, control wires, earthing connections etc using glands as required at site complete all as specified & directed. |
| 59 | M&L for Plain cement concrete type D-2, 1:4:8 using 40 mm graded crushed stone aggregate as in foundation, sub floors/sub-bases, and paving etc complete all as specified & directed. |
| 60 | M&L Plain Cement Concrete 1:2:4 type B-1 (using 20 mm graded granite stone aggregate) as in foundations/platform/pole coping for steel/PCC pole, filling and mass concrete, finished surface even and smooth complete all as specified and as directed. |
| 61 | M&L for Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel using GI nut, bolts & washer complete all as specified & directed. |
| 62 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip of size 32 x 6 mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in elecrtical plate No 3 of SSR pt I, connected to LT Panel/DB/earthing test point including PCC chamber, RCC cover 50mm thick with 8 mm dia bars, protection pipe, funnel etc including excavation, earth work, disposal of surplus soil and earth strip protection pipe of GI 40 mm bore light grade upto 7.5 metre including testing on completion all as specified and as directed.Note: (i) The unit rate includes 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includesGI main earthing lead/strip of size 32x6 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained (iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester shall be provided by the contractor. |
| 63 | M&L for Testing of earthing resistance of existing earthing using calibrated 3/4 wire digital Earth resistance tester and recording the earth resistance value in register obtaining the signature of user and MES excecutive after varification all as specified and directed.(Note : Contractor has to provide digital earth resistance tester and should be available all the time during the contract period) |
| 64 | S&F Steel tubular swaged poles, 9.0 metres long complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 and marking ZEBRA pattern with alternate yellow and black colour to steel tubular poles 1.5m from the bottom of pole and one coat of aluminium painting for the remaining portion of pole including numbering of poles complete all as specified and directed (Note :- Item required for excavation earth work, pole foundation, coping, plinth protection etc shall be measured and paid separately under relevant item of schedule) |
| 65 | Dismantling and taking out existing/old/damaged PCC pole any type/size after disconnection all existing incoming/outgoing existing cable connections complete all as specified & directed |
| 66 | Dismantling and taking out existing/old/damaged steel pole any type/size after disconnection all existing incoming/outgoing existing cable connections complete all as specified & directed |
| 67 | M&L for servicing of Solar water heater with electric back up system after disconnecting the existing water supply/ electrical connections from any height of the building, transporting the heating/storage tank to authorised service station and back as required including stripping out the hot water vessel by taking out the outer cover, insulating materials etc. and continuous brazing of the inner container for arresting leakages including replacement of defective / worn out spare parts and re-assembling the system and re-installed at the same location, connecting up water/ electrical connections and testing for satisfactory performance complete all as specified and as directed of the following capacity complete all as specified & directed. Note :- Servicing of Flat plate collector shall be measured and paid separately under respective items of this Schedule |
| 68 | 100 litres capacity |
| 69 | 200/300 litres capacity |
| 70 | 500 litres capacity |
| 71 | 1000 litres capacity |
| 72 | M&L for servicing of Solar flat plate collector box after disconnecting the existing water supply from any height of the building, dismantling the box, cleaning and servicing the Copper/aluminium Plates/ sheets/ angles and solar glass panel including replacement of defective/ worn out components and re-assembling the box connecting up water connections and testing for satisfactory performance complete all as specified and as directed of following capacity :-Note :- Replacement of Solar glass panel if required shall be measured and paid separately under respective items of this Schedule |
| 73 | 100 litres capacity |
| 74 | 200 litres capacity |
| 75 | 300 litres capacity |
| 76 | 500 litres capacity |
| 77 | 1000 litres capacity |
| 78 | M&L for taking down, dismantling and shifting of existing solar water heating system of any capacity/type alongwith all parts / accessories from existing location to new/ desired location as per user/site requirement and installing, commissioning and testing complete for proper functioning of the solar water heater in all respect all as specified and as directed.Note :- (i) All T&P arrangement shall be arranged by the contractor. The cost of the same shall be deemed to be included in the quoted rate. (ii) Spare parts/items if required to be replaced shall be measured and paid seperately |
| 79 | M&L PCC 1:3:6 type C1 using 20mm graded stone aggregate for mass concrete complete all as specified and as directed. |
| 80 | S&F in replacement Heating element with rubber gasket threaded/ push type 230V, 3 KW rating complete all as specified and as directed. |
| 81 | S&F iin replacement thermostat suitable for solar water heater upto 300 litres capacity and range 0 to 80 degree centigrade complete all as specified and as directed. |
| 82 | S&F in replacement 25mm thick bonded mineral wool preformed \\"SNAP ON\\" pipe sections of density 144 kg/ cum conforming to IS 9842, lagged all around to hot water pipe line of 20mm bore suitable for existing make complete all as specified and as directed. |
| 83 | S&F in replacement 5mm thick, toughened plain glass panels suitable for solar water heater plate collector box, suitable for existing make complete all as specified and as directed. |
| 84 | S&F in replacement solar collector panel Flat plate collector based of toughned tempered glass of 4mm thick and cladding with aluminium sheet 26 SWG complete with copper rising tube, copper heater tubes, copper sheet and absorber for solar water heater complete all as specified and directed |
| 85 | S&F in replacement GI water tubes, 15 mm bore, medium grade, galvanised, with all fittings, fixed complete to walls and ceiling or laid in floors as in short lengths complete all as specified and as directed of the following sizes :- |
| 86 | 15 mm bore |
| 87 | 20 mm bore |
| 88 | 25 mm bore |
| 89 | S&F in replacement Gun metal gate valves, with iron wheel head, screwed both ends for 25 mm bore GI pipe complete all as specified and directed. |
| 90 | S&F in replacement stop valve 20 mm dia cast copper alloy screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipe or for unions and fixed complete all as specified and directed. |
| 91 | S&F in replacement closing tap cast copper alloy chromium plated screwed for iron pipe of size 15 mm dia complete all as specified and directed. |
| 92 | M&L for Cutting screwing existing steel tubing 15mm for alteration or additionals or lengthening screw on pipe to form connector complete all as specified and directed for the following sizes :- |
| 93 | 15 mm bore |
| 94 | 20 mm bore |
| 95 | 25 mm bore |
| 96 | S&F MS framed work such as grills, gratings etc with ends of bars shouldered or riveted of forged into spiles, framed guard bars, barred iron doors, ladders, framed balusters , walking way, railing, framework of watertanks and similar work conforming to FE-290, Gde-165 including dismantling of existing wrought iron or mild steel work of any description complete all as specified and directed |
| 97 | S&F in replacement MCB Single pole and neutral, 32 Amps, 240 volts, 10 KA rupturing capacity, 'C' curve type complete all as specified and directed. |
| 98 | S&F in replacement Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of 250 ltr capacity complete all as specified and directed. |
| 99 | S&F in replacement Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of 500 ltr capacity complete all as specified and directed. |
| 100 | M&L for Earthing Complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common saft filling in alternate layers and electrode connection by using earth lead GI wire 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and other end of the earth wire connected to main switch board protected by galvanised iron light grade pipe 15mm bore in wall/floor/and GI Pipe 20mm bore light grade for watering with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover including necessary excavation and earth work in any type of soil, returning slurry approved soil and disposed of surplus soil to a distance not exceeding 50 Mtr away all as shown in electrical plate No 3 of SSR 2009( Part-I) complete all as specified and directed.Note :- (i) Rate quoted include the cost of earth lead and GI protection pipe upto 7.5 mtr length. (ii) On completion of Earthing Contractor should check Earthing Results and submit the Test Report to Engr-in-charge. If desired results are not obtained then Earthing shall be redone by the contractor at his own cost. |
| 101 | S&F in replacement hot water pipe duly insulated with glass wool and aluminium cladding of dia 25 mm bore complete all as specified and directed |
| 102 | S&F in replacement hot water pipe duly insulated with glass wool and aluminium cladding of dia 15 mm bore complete all as specified and directed |
| 103 | S&F in replacement hot water storage tank of capacity 100 Ltrs per day with inner shell fabricated from stainless steel 1mm thick in cylindrical shape and outer cover fabricated from aluminium sheet 1mm thick (having insulation of rock wool) mineral wool 100mm thick & cladding with aluminium 26 SWG complete all as specified and directed. |
| 104 | S&F in replacement hot water storage tank of capacity 200 Ltrs per day with inner shell fabricated from stainless steel 1mm thick in cylindrical shape and outer cover fabricated from aluminium sheet 1mm thick (having insulation of rock wool) mineral wool 100mm thick & cladding with aluminium 26 SWG complete all as specified and directed. |
| 105 | S&F in replacement Temperature & Pressure Release Valve for Pressurized System, Spring Type incl connection complete all as specified and directed Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |