Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 2 | 20 mm |
| 3 | 25 mm |
| 4 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal, 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 5 | Short point (up to 3 mtr.) |
| 6 | Medium point (up to 6 mtr.) |
| 7 | Long point (up to 10 mtr.) |
| 8 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 9 | On board |
| 10 | Short point (up to 3 mtr.) |
| 11 | Medium point (up to 6 mtr.) |
| 12 | Long point (up to 10 mtr..) |
| 13 | S&F of following sizes of polypropelene corrugated flexible conduit including gland on both side of flexible conduit as required. |
| 14 | 20 mm OD |
| 15 | 25 mm OD |
| 16 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size , 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. Note:- To ensure strong bond, apply adhesive to the conduit surface before fixing Conduit accessories. |
| 17 | Short point (up to 3 mtr.) |
| 18 | Medium point (up to 6 mtr.) |
| 19 | Long point (up to 10 mtr.) |
| 20 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galvanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 21 | On board |
| 22 | Short point (up to 3 mtr.) |
| 23 | Medium point (up to 6 mtr.) |
| 24 | Long point (up to 10 mtr..) |
| 25 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked ( IS:14927 P - II ) uPVC trunking & it's accessories, Hot Dipped Galvanized Modular box 1.2 mm thick with earth terminal/ Surface mounted UPVC molded modular box, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose/holder /3 way Connector, screws, making connections, testing etc. as required. |
| 26 | Short point (up to 3 mtr.) |
| 27 | Medium point (up to 6 mtr.) |
| 28 | Long point (up to 10 mtr.) |
| 29 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked ( IS:14927 P - II ) uPVC trunking & it's accessories, Hot Dipped Galvanized Modular box 1.2 mm thick with earth terminal/Surface mounted UPVC molded modular box, modular 6 A switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required |
| 30 | On board |
| 31 | Short point (up to 3 mtr.) |
| 32 | Medium point (up to 6 mtr.) |
| 33 | Long point (up to 10 mtr..) |
| 34 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 35 | 25 mm x 12 mm |
| 36 | 32 mm x 12 mm |
| 37 | 50 mm x 50 mm |
| 38 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 39 | 1 x 1.5 sq.mm |
| 40 | 2 x 1.5 sq.mm |
| 41 | 3x 1.5 sq.mm |
| 42 | 1 x 2.5 sq.mm |
| 43 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 44 | 1 x 4.0 sq.mm |
| 45 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 46 | 1 x 6.0 sq.mm |
| 47 | Supply & laying service connection with ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. |
| 48 | 2.5sq.mm |
| 49 | 4.0 sq.mm |
| 50 | Supply and Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 51 | 1.5 Sq.mm 3 core flat / Round |
| 52 | 2.5 Sq.mm 3 core flat / Round |
| 53 | 4.0 Sq.mm 3 core flat / Round |
| 54 | P & F 1.2 mm thick Hot dipped galvanized boxes with brass earthing terminal of following sizes (nominal size) in recessed/surface as required. |
| 55 | 100mm x 100mm x 60mm |
| 56 | 150mm x 75mm x 60mm |
| 57 | 175mm x 100mm x 60mm |
| 58 | 150mm x 150mm x 60mm |
| 59 | 225mm x 100mm x 60mm |
| 60 | 200mm x 150mm x 60mm |
| 61 | 200mm x 125mm x 75mm |
| 62 | 200mm x 250mm x 75mm |
| 63 | 250mm x 300mm x 75mm |
| 64 | 250mm x 100mm x 60mm |
| 65 | P & F paper phenolic resin bonded laminates confirming to IS : 2036 - 1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc plated nut and bolts as required. 3.0 mm thick |
| 66 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 67 | Single pole MCB (With B / C curve tripping characteristics) |
| 68 | 6 A to 32 A rating |
| 69 | 40 A rating |
| 70 | Double pole MCB (With B / C curve tripping characteristics) |
| 71 | 6 A to 32 A rating |
| 72 | 40 A rating |
| 73 | Four pole MCB (With B / C curve tripping characteristics) |
| 74 | 6 A to 32 A rating |
| 75 | 40 A rating |
| 76 | Triple pole MCB (With B / C curve tripping characteristics) |
| 77 | 6 A to 32 A rating |
| 78 | 40 A rating |
| 79 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required.Suitable for Two / Three / Four module for MCB |
| 80 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 81 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 82 | Providing & Fixing of 6 amp. Combined flush type non modular socket and switch set made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 83 | Providing & Fixing of 16 amp. Combined flush type non modular socket and switch set with indicator and fuse set, made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 84 | Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push surface type CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 85 | Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A switch surface type, CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 86 | Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push flush type CM/L no. printed and made out from industrial grade Polycarbonate materialincluding cutting hole in tile and making connection testing etc. as required. |
| 87 | Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A switch flush type CM/L no. printed , made out from industrial grade Polycarbonate material, including cutting hole in tile and making connection testing etc. as required. |
| 88 | Providing & Fixing of non modular 6A hanging bell push/one way switch made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 89 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 90 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 91 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 92 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 93 | Providing & Fixing of ISI marked (IS:1293) 6 amp unbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal including making connection testing etc. as required. |
| 94 | Providing & Fixing of ISI marked (IS:1293) 16 amp unbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal including making connection testing etc. as required. |
| 95 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 96 | Providing & Fixing of ISI marked (IS:302) gong bell with CM/L no. printed including making connection testing etc. as required. |
| 97 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 98 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 99 | 6 A one way switch |
| 100 | 6 A two way switch |
| 101 | 6 A bell push |
| 102 | 10 A one way switch |
| 103 | 16 A one way switch 1M |
| 104 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 105 | 6 A 3 pin shuttered socket |
| 106 | 6/16 A shuttered socket |
| 107 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required.5 step fan regulator 2 Module |
| 108 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. Modular MCB 6 A to 32 A SP |
| 109 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 110 | 1/2 Module |
| 111 | 3 Module |
| 112 | 4 Module |
| 113 | 5 Module |
| 114 | 6 Module |
| 115 | 8 Module |
| 116 | 10 Module |
| 117 | 12 Module |
| 118 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 119 | 1-2 Module |
| 120 | 3 Module |
| 121 | 4-5 Module |
| 122 | 6-8 Module |
| 123 | 10-12 Module |
| 124 | Providing & Fixing of Wiring Accessories OEM fabricated following size virgin material UPVC modular boxes on surface suitable for modular accessories as required. |
| 125 | 1-2 Module |
| 126 | 3 Module |
| 127 | 4/5 Module |
| 128 | 6 / 8 module |
| 129 | 10 / 12 module |
| 130 | Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 131 | 1/2 Module |
| 132 | 3 Module |
| 133 | 4 Module |
| 134 | 5 Module |
| 135 | 6 Module |
| 136 | 8 Module |
| 137 | 10 Module |
| 138 | 12 Module |
| 139 | Providing and fixing of power plug point with non modular accessories with Galvanized box of 1.2 mm thick with earth terminal with suitable size 3.0 mm thick phenolic laminated sheet (IS : 2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outlet making connection , testing , etc. as required. |
| 140 | Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. |
| 141 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. 4 pole MCCB With Thermal Magnetic release |
| 142 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 143 | 125 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 144 | 160 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 145 | 200 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 146 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 147 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 148 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. 10.0 Sq. mm |
| 149 | 2 core |
| 150 | 4 core |
| 151 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 152 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 153 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. 10 SWG G.I. ( Hot Dipped ) Wire |
| 154 | Making of hole in wall (brick/stone) of required and placing NP-2 RCC pipe ring of required size for housing exhaust fan and making good the same, with cement plaster required of following size. Up to 457 mm size |
| 155 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 156 | Providing & Fixing of of M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed with cement concrete mortar with required support as required. |
| 157 | P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required. |
| 158 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. 230 mm sweep, Minimum air delivery 750 Cum / hour |
| 159 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required. 300 mm sweep(900 RPM) |
| 160 | Providing & Fixing of ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. |
| 161 | 150 mm sweep Minimum Air Delivery 150 Cum / hour |
| 162 | 200 mm sweep Minimum Air Delivery 450 Cum / hour |
| 163 | Providing & Fixing of 450 mm Sweep Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Sintered Iron bush oil impregnated, with metal front and back 120 or more ribs guard; Three no. Aluminium blades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required. Wall mounting type with Adjustable Vertical Angle |
| 164 | Providing & Fixing of extra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe including cutting, threading, drilling, fixing quarter pin etc as required. |
| 165 | Numbering of ceiling fans/ fixtures with approved enamel paint etc as required. |
| 166 | P & F of Gravity Louver shutter of superior quality made out of frame of 18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel paint including cost of nuts, bolts, etc as required. Up to 380 mm size |
| 167 | Providing & Fixing of Vertical (BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap action adjustable thermostat , Dual indicating lamps Injected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top , including making inlet, outlet Flexible alloy connection, testing etc. as required. 15 Ltr. |
| 168 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. 1170mm(+/-10%) LED batten with min. lumen output 2200 lm , 20W |
| 169 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 170 | Recessed Mounting |
| 171 | Minimum lumen output 1950 lm , 18W |
| 172 | Surface Mounting (with extruded alumn. Housing ) |
| 173 | Minimum lumen output 1950 lm , 18W |
| 174 | SITC of energy efficient /energy saving IP 20 LED direct retrofit Bulb in existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf 0.95 , CRI >70, minimum life time of minimum 25000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. 9 Watt |
| 175 | Providing & Fixing of IK07 IP65 protected Top/Bottom mounted LED Post top Luminarie top & bottom made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with powder quoted reflector. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED Driving output current <750mA as required. Minimum lumen output 3200 lm Post top Luminarie |
| 176 | SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal. The motor body of single phase pump shall be of SS and rest of all shall be of cast iron. Shaft of three phase pump shall be of SS 410 grade. All casting parts should be cathod electro deposition (CED) coated. Motor winding shall be 100% copper wire material. Dynamically balanced rotating parts to ensure min. vibration etc. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect. 150 mm diameter Submersible pump shall have following HP Rating, phase, Head range, Discharge range respectively. 5.0 HP, 3-Ø, (72 - 161)Mtr, (230-48) LPM |
| 177 | Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 ) with socket,elbow,tee, flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect. ( If Pipe Laid Underground Excavation and refilling cost will be paid extra) 50 mm dia. |
| 178 | SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect. For single phase Submersible / Monoblock pump |
| 179 | 0.5 HP to 1.5 HP (DOL starter) |
| 180 | 2.0 HP to 3.0 HP (DOL starter) |
| 181 | Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. (New model ceiling fan) |
| 182 | 900/1200 mm sweep (New model ceiling fan) |
| 183 | 1400 mm sweep (New model ceiling fan) |
| 184 | Charges for oiling, overhauling of ceiling fan, table fan, pedestal fan irrespect to the size of fan including removing,refixing of fan from site and testing etc. as required. |
| 185 | Fans w/o Removing & Refixing |
| 186 | Fans with Removing & Refixing at Suitable Location |
| 187 | Providing and Replacement of ball bearing of ceiling/ exhaust fan and refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material shall be retained by the contractor. |
| 188 | Provinding & Replacement of M.S. Shaft of ceiling fan. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 189 | P & Replacement of cover/ bearing seat of ceiling/ exhaust fan. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 190 | P & F Aluminium Blades (a set of 3 blades) duly painted and well finished 900/ 1200 mm. The material of the fan blade shall be of designation 31500B with condition HX6 aluminium alloy sheet confirming to IS 737/2008 |
| 191 | P & F Aluminium Blades (a set of 3 blades) duly painted/ powder coated. ( 1400/ 1500 mm) The material of the fan blade shall be of designation 31500B with condition HX6 aluminium alloy sheet confirming to IS 737/2008 |
| 192 | Providing and Replacement of Gun metal bush of ceiling/exhaust/cooler fan/ as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 193 | P & F 3 Speed rotary switch for Desert Cooler complete with testing etc as required. |
| 194 | P & Replacement of M.S. Shaft of fan motor for Desert Cooler/ exhaust fan. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 195 | P & replacement of supporting legs(4 no.) of vertical pump of desert cooler as required for Desert Cooler/ exhaust fan. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 196 | P & F of stud with nuts and washer for Desert Cooler/ exhaust fan.All the scrap material should be retained by the contractor. |
| 197 | Servicing and overhauling of 20\\" sweep desert cooler including oiling, greasing, painting of tank from inside with rubber paint after properly desmantling each assembly and refixing the same as required. |
| 198 | Painting of desert cooler with two coats of rubber paint inside of water tank and two coat of synthetic enamelled paint on both side of cooler body, fan body, grills etc.after cleaning with sand paper, complete in all respect as required. |
| 199 | Replacement of cooler pads (heavy) set of 3 no. of size 25\\" x 27\\" |
| 200 | P & F Brass float valve of weighing approx. 250 gm, 8\\" long rod,PVC ball of 4\\" dia. For desert coler as required. |
| 201 | P & F adjustable M.S.grill 20/22 gauge of size approx. 24\\" x 26\\" including painting etc. as required. |
| 202 | P & F aluminiun blade for 20'' desert cooler fan as required. |
| 203 | P & F outer/inner threaded PVC nipple 1/2\\" dia and 2\\" long |
| 204 | P & Replacement of pvc pipe of 1/2\\" size for vertical pump of desert cooler as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 205 | P & replacement of shaft for vertical pump of desert cooler as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 206 | P & replacement of 4 nos. supporting legs of 20'' fan motor with rubber pads of desert cooler as required.Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 207 | P & replacement of high quality pvc distribution ' T 'and 3 no. elbow for cooler |
| 208 | P & F ISI marked waterproof plywood 6.0 mm thick including cutting, hardwares etc. as required. |
| 209 | Labour Charges for fixing of desert cooler in windows including handling of cooler upto desired location, making electrical/water connection s,testing etc. as required. |
| 210 | Ground floor |
| 211 | First floor |
| 212 | P & F of ISI marked vertical pump suitable for 20\\" desert cooler including making connection testing etc. as required. ISI marked vertical pump |
| 213 | P & F of submercible pump set suitable for 18/24 \\"Desert coolers. |
| 214 | P & F cooler fan motor suitable for 20\\" desert cooler including making connection testing etc. as required. |
| 215 | with copper winding Motor ISI Marked |
| 216 | with Aluminium winding Motor ISI Marked |
| 217 | Rewinding of Heavy duty Exhaust fan motor including all necessary material,The motor is to be wound taking no. of coils,turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. 300/ 380 mm sweep |
| 218 | Rewinding of single phase motor of 1400 RPM including all necessary material and of the same characteristics as original with required size of super enamelled wire 'E' class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 219 | 0.25 H.P. To 0.50 H.P. |
| 220 | 0.75 H.P. To 1.0 H.P. |
| 221 | Rewinding of motor of desert cooler fan with super enamelled copper wire, 'E ' class insulation material including removing,refixing,testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 222 | Providing and replacement of heating element of blower type heat convector as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 223 | Providing and replacement of heating element rod of radiation type heat convector as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 224 | Providing and replacement of Chrome plated reflector of radiation type heat convector as required.Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 225 | single rod |
| 226 | double rod |
| 227 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capallary and strainer/ filter. |
| 228 | 1.0 TR Window/ Split A.C. |
| 229 | 1.5 TR Window/ Split A.C. |
| 230 | Replacement of defective compressor by company repaired compressor as per OEM recommendations of following gadgets including testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 231 | 1.0 TR A.C. |
| 232 | 1.5 TR A.C. |
| 233 | P & Replacement of condensing/ cooling coil of copper fins for following capacity A.C./ Water cooler/ Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 234 | 1.0 TR A.C. |
| 235 | 1.5 TR A.C. |
| 236 | Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner |
| 237 | P & Replacement of thermostat of A.C./ Water cooler/fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 238 | P & Replacement of selector switch of 1.0/1.5/2.0 TR A.C Fan as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 239 | P & Replacement of starting relay of A.C/water cooler/fridge compressor as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 240 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 241 | Starting capacitor |
| 242 | 20-30 micro farad |
| 243 | 40-60 micro farad |
| 244 | Running capacitor |
| 245 | 2.5/3.15 micro farad |
| 246 | 4.0 micro farad |
| 247 | Rewinding of single phase/3phase submersible motor including all necessary material and of the same characteristics as original with required size of super enamelled wire 'E' class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 248 | 0.5 H.P. To 1.0 H.P. |
| 249 | 2.0 H.P. |
| 250 | Above 3.0 HP to 5.0 HP |
| 251 | From7. 5 HP to 10.0 HP |
| 252 | Repairing of submersible pump of with replacement of broken impellers ,diffuser,bush/bearing set , oil seal complete with testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 253 | Above 3.0 HP to 5.0 HP |
| 254 | From7. 5 HP to 10.0 HP |
| 255 | Dismentling of split air conditioner of any capacity/any type including existing indoor unit & outdoor unit , refrigerant piping , connecting cables , drain pipe etc. including shifting of dismentaled material to store complete as required |
| 256 | Providing & Laying XLPE insulated & P.V.C. sheathed Un-Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing commissioning etc. as required of following size. |
| 257 | 6.0 Sq. mm |
| 258 | 2 core |
| 259 | 4 core |
| 260 | 10.0 Sq. mm |
| 261 | 2 core |
| 262 | 4 core |
| 263 | 16.0 Sq. mm |
| 264 | 2 core |
| 265 | 4 core |
| 266 | 25.0 Sq. mm |
| 267 | 2 core |
| 268 | 3.5 core |
| 269 | 35.0 Sq. mm |
| 270 | 2 core |
| 271 | 3.5 core |
| 272 | 50.0 Sq. mm |
| 273 | 3.5 core |
| 274 | 70.0 Sq. mm |
| 275 | 3.5 core |
| 276 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 277 | 6.0 Sq. mm |
| 278 | 2 core |
| 279 | 4 core |
| 280 | 10.0 Sq. mm |
| 281 | 2 core |
| 282 | 4 core |
| 283 | 16.0 Sq. mm |
| 284 | 2 core |
| 285 | 4 core |
| 286 | 25.0 Sq. mm |
| 287 | 2 core |
| 288 | 3.5 core |
| 289 | 35.0 Sq. mm |
| 290 | 2 core |
| 291 | 3.5 core |
| 292 | 50.0 Sq. mm |
| 293 | 2 core |
| 294 | 3.5 core |
| 295 | 70.0 Sq. mm |
| 296 | 1 core |
| 297 | 2 core |
| 298 | 3.5 core |
| 299 | 95.0 Sq. mm |
| 300 | 3.5 core |
| 301 | Providing Manpower through Contracting agency for Supervision / Execution / Operation of various Electromechanical Installations. (one shift of 8 working Hrs per day for 26 Working Days in a month) on basis of minimum wages + VDA order Dt. 28.03.2025 Ministry of Labour and Employement Govt. of India |
| 302 | Wireman, Electrician, Welder, Lineman, AC Mechanic, Fireman, , Supervisor, ELV technician or equivalent professional with ITI or Equivalent course and Experience of 2 years in relevant field ) |
| 303 | Technical Helper Having basic Knowledge of E&M Services Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail