| 1 | Dragging, loading, carriage and unloading of following store materials with proper stacking from ESC Daliganj to JE dumps store and from JE dump store to work site within municipal area. |
| 2 | ACSR Panther/Dog conductor |
| 3 | 33KV LA |
| 4 | 33KV CT 400/200/1 A or 200/100/1A |
| 5 | 33KV Bus Isolator |
| 6 | Control pannel I/C for 33KV Single feeder |
| 7 | 33 KV VCB 1250 A, 750MVA with steel structure |
| 8 | 24Volt Battery with charger |
| 9 | Transformer 05 MVA (Old & Used) |
| 10 | Transformer 10 MVA (Old & Used) |
| 11 | 33 KV 11 KV XLPE cable 3x300 mm2 |
| 12 | Cable jointing kit outdoor 11 KV 3*300 sqmm |
| 13 | Cable jointing kit Indoor 11 KV 3*300 sqmm |
| 14 | 11 KV VCB (O/G) 200/100/5A 350 MVA |
| 15 | 11 KV VCB 600/300/5A 350 MVA |
| 16 | 11 KV Bus Cupler |
| 17 | 11 KV 3x185 mm. XLPE Cable |
| 18 | Cable jointing kit O/D 11 KV 3*185 sqmm |
| 19 | Cable jointing kit I/D 11 KV 3*185 sqmm |
| 20 | 11 Mtr. STP |
| 21 | 11 Mtr. PCC |
| 22 | 33 KV Fuse Set |
| 23 | 33 KV Post Insulator |
| 24 | 33 KV Line Isolator |
| 25 | MS Angle 75x75x6, 2.6M 2 Nos Total [email protected] Kg./M With Wastage |
| 26 | MS Angle 65x65x6 |
| 27 | Rail 105 LB |
| 28 | MS Round of 32 mm dia for laying of main earthmat in switch yard & for panel earthing bridge [email protected] Kg./M |
| 29 | MS Channel 125x65mm 3.5m Long 4 Nos Pieces [email protected]. Mtr. With wastage. |
| 30 | Single Core Cable 1x630 sqmm. |
| 31 | Top Channel |
| 32 | Dropper Channel |
| 33 | T-Off Channel |
| 34 | 11 KV Pin Insulator |
| 35 | 11 KV Pin |
| 36 | 11 KV Stay Set |
| 37 | 33 KV Stay Set |
| 38 | 33 KV V Type Cross Arm 100x50x6mm M.S Channel |
| 39 | 33 KV Disc fitting |
| 40 | 33 KV Pin With Nut |
| 41 | 33 KV Pin Insulator |
| 42 | 33 KV Stay Set |
| 43 | Earthing Complete |
| 44 | 33 KV LINE ERECTION WORK |
| 45 | Earthing of substation switchyard complete by round bar 32 mm diaexavation of earth for laying of earth mat 750mm deep and proper leveling after laying of earthmat complete as per specification and connection of all swithyard equipment by GI Flat 50x6mm (The contractor shall arrange all the material except MS Round bar 32mm) |
| 46 | Cutting, Fabrication and driving of earth electrode of size 32x3000mm |
| 47 | Cutting Shaping, laying and welding of riser strip size 50x6mm G.I Strip of size 50x6mm in between earth mat and equipments/structure/ body of T/F for earthing (Two nos riser for each structure equipment individually GI strip shall be provided contractor). |
| 48 | Earthing of indoor equipment by making of 2 nos. Quard of round bar 32mm dia as per norms. |
| 49 | Fabrication & erection of cable stand made of two nos MS channel 100x50x3mtr long jointed to each other by means of 05 nos MS strip 50x6 mm of size 150 mm long each by welding at equal distance interval as per norms and grouting in block of 300x300x700 completely providing two nos cable clamp also. (All materials will be provided by contractor except MS Channel). |
| 50 | Outdoor Delta Type Earthing |
| 51 | Painting of all existing and new structures equipment |
| 52 | New/Extension of 33 KV Bus Bar Gantary complete with structure |
| 53 | Construction fo power T/F plinth suitable for 33/11 KV 5 MVA power T/F of size 4x3x1.3 having 0.4 mtrheight above ground level. The work includes excavation of foundation base concreting in cc ratio 1:6 M as 12 1st class brick work in ratio 1:4 with coarse sand foundation cc in ratio 1:4:8 using M.S bar of 12 mm dia for reinforcement the work includes laying of 2 nos rail pieces 4 mtr long as per drawing/practice the plinth shall be finished in all respect. (Only rail piece and M.S angle provided by the department) |
| 54 | Construction of masonty type plinth for 33 KV VCB of size 1.6x1.6x1 M Brick, sand, cement and stone grit including grouting of 4 nos foundation bolts for erection of 33 KV VCB |
| 55 | Isolator Structure-Fabrication of Isolator structure minimum 3.5 mtr overall height and 2.5 mtr above ground level as per RESSPO drawing, with help of M.S channel 125x65 mm two pieces of M.S channel joined to each other by M.S flat 50x6 mm, diagonally at the interval of 0.5 mtr and top & bottom of the structure. Grouting of Isolator structure in CC (cement, coarse sand and stone grit of 20 mm gauge) including supply of necessary T&P and painting OS structure complete. (only M.S channel and angle provided by the deptt) |
| 56 | Lightning Arrestor/ CT structure: Fabrication of lightning arrestor/CT structure as per RESSPO drawing with the help of 2 nos M.S channel 125x65 mm minimum 3.5 mtr long grouting 1 mtr deep from ground level in cc in ratio 1:4:8. complete in all respect. |
| 57 | Fuse set structure: Fabrication of Fuse set structure as per RESSPO drawing with the help of 2 nos M.S channel 125x65 mm minimum 3.5 mtr long grouting 1 mtr deep from ground level in cc in ratio 1:4:8. complete in all respect. |
| 58 | Erection of structures, grouting, plinthing of ALL structures equipment. |
| 59 | Mounting of accessories/equipment on fabricated structure complete work with making proper alignment and tightening the work includes fabrication work if required for equipment. proper operation of equipment. |
| 60 | 33 KV VCB |
| 61 | CT 200/100/1-A |
| 62 | 33 KV Lighting Arrestors |
| 63 | Bus/Line Isolator |
| 64 | Fabrication & Erection of Neutral stand structure with foundation |
| 65 | Erection and commissioning of 5 MVA T/F mounting of radiator conservator tank exposure vent. Etc. Filling of T/F oil in radiator conservator tank with complete work as per RESPO Norms. |
| 66 | Jumpering complete T/F bay with ACSR panther cond. And required clamp with nut & bolts from 33 KV existing bus bar & 33 KV cable to T/F (With copper L Piece) complete work. (01 No. T/F Bay) |
| 67 | Laying of double circuit 11 KV 3x300 sqmm XLPE cable in normal soil by digging of suitable size of trench as per site condition cable should be covered by bricks and sand. |
| 68 | Hoisting, Jumpering, clamping of 11 KV 3x300 sqmm XLPE cable on cable stand, panel with proper taping with the help of empire tape. PVC tape and connectors. |
| 69 | Construction of control cable trench of size 150mm wide 300 mm deep with brick work along with provision trench cover M.S angle at both the edge of the trench. |
| 70 | Construction and fixing of trench cover 0.5 M wide 0.75 mm thick with cement, coarse sand & stone grit in ratio 1:2:4 for covering of cable trench 150mm wide with provision of M.S angle and MS Bar as per RESPO Norms. |
| 71 | Supply & Laying of copper control cable of following sizes its proper dressing, ferruling and connection with the system. |
| 72 | Copper Control Cable 2x2.5sqmm |
| 73 | Copper Control Cable 4x2.5sqmm |
| 74 | Pipe boring type earthing minimum 80 Ft. Deep from ground level or upto water level with B Class G.I. Pipe 2\\" Dia. Connection of equipment with earthing by GI Strip 50x6mm included in the job as per specifiacation/norms for power transformer, VCB, CT/LA and other. (All materials will be provided by Contractor.) |
| 75 | Dragging of following panels (Control and feeder pannel) from unloading place upto control room and placement erection and grouting, commissioning & testing of the same as per RESPO Norms. |
| 76 | 33 KV T/F Control Panel |
| 77 | 11 KV Incoming VCB 600/300/5A |
| 78 | 11 KV Outgoing VCB 200/100/5A |
| 79 | 11 KV VCB Bus Coupler, 350 MVA |
| 80 | Erection of 24 V Batteries set with charger including stand (Stand shall be provided by Contractor) & initial charging complete set. |
| 81 | Grouting, Plinthing and painting of new erected 11M long ST Poles of single pole support, double pole cable exposures. |
| 82 | Fabrication, erection, double pole for 33 KV Cable exposure on ST. Pole 11 Mtr. Long with fixing of necessary clamp channel, angle 33 KV Pin & Pin insulator making single ckt 3 Phase 3 Wire bus bar for separate cable with single core cable including electrode earthing, danger board, barbed wire complete in all repect as per RESPO Norm. |
| 83 | Fabrication, erection, Single pole for PCC Pole 11 Mtr. Long with fixing of necessary clamp channel, angle 33 KV Pin & Pin insulator, danger board, barbed wire complete in all repect as per RESPO Norm. |
| 84 | Grouting of pole in depth of 1/6 the length of pole in ratioa 1:4:8 in cement sand and brick balast as per RESPO Norms. |
| 85 | Construction of pole plinth 300mmx450mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESPO Norms. |
| 86 | Painting of new erected ST Pole with two coat of red oxide paint, PO red paint at top of pole 2 M & Balance by two coats of best quality aluminium paint ISI of burger/nerolac/asian mark as per norms. |
| 87 | Hoisting of 33/11 KV 3x185/300 sqmm XLPE cable on double pole with MS Pipe/GI pipe of size 5/6\\" dia 3 M long including its jumpering complete with clamps, nuts and bolts (All material arranged by contractor) |
| 88 | Laying of double circuit 11 KV 3x185 sqmm XLPE cable in normal soil by digging of suitable size of trench as per site condition cable should be covered by bricks and sand. |
| 89 | Laying of double circuit 11 KV 3x185 sqmm XLPE cable in constructed cable trench with proper ferruling, cable trench should filled by fine sand. |
| 90 | Hoisting , jumpering, clamping of 11 KV 3x185 sqmm XLPE cable on 11 KV Pannel with proper taping with the help of empire tape, PVC tape and connectors. |
| 91 | Extention of switchyard |
| 92 | High Pressure testing |
| 93 | Constrution of firewall, RCC framed with fire bricks in between T/F (4.5x0.345x4.00) Mtr. |
| 94 | Interlinking tiles wide complete work including material and labour with providing grovel in (20 mm stone ballast in switchyard area.) |
| 95 | Complete work of fixing of interlockingtils in switchyard area. (All the materials shall be provided by contractor) |
| 96 | Provideinggravels (20 mm Stone Ballast) in switchyard upto 15 cm hight from the graund level. |
| 97 | Supply of copper bus bar. |
| 98 | Repairing of old damge Power Transfomer Plinth. |
| 99 | Dismantling of 5 MVA old T/F from plinth & kept aside in switchyard |
| 100 | Grouting & Nuzzling of 11 KV stay set complete including fixing of necessary clamps. Accessories required including its grouting by civil material (Sand, Brick blast & cement). All material except stay wire shall be supplied by the contractor. |
| 101 | Grouting & Nuzzling of 33 KV stay set complete including fixing of necessary clamps. Accessories required including its grouting by civil material (Sand, Brick blast & cement). All material except stay wire shall be supplied by the contractor. |
| 102 | Ordinary earthing by 11 KV MS earth Rod 2500mm long as per RESPO Schedule. All material except earthing wire shall be supplied by the contractor. |
| 103 | Laying Stringing & sagging of 3 Phase 3 wire 33/11 KV New Line on ACSR Wesal/Racoon/Dog conductor as per RESPO Specification and direction on E/I. All material exept ACSR wesal/Racoon/Dog conductor shall be supplied by the contractor. |
| 104 | Laying Stringing & sagging of 3 Phase 3 wire 33/11 KV New Line on ACSR Panther conductor as per RESPO Specification and direction on E/I. All material exept ACSR wesal/Racoon/Dog conductor shall be supplied by the contractor. |
| 105 | Looping and chopping of tree branches for clearince root of erection new line. |
| 106 | INTERLINKING 33KV BANI TO BHATGAON SUBSTATION UNDER B.P. 2026-27 (AMAUSI ZONE) |
| 107 | Laying of 33 KV XLPE Cable for INTERLINKING 33KV BANI TO BHATGAON SUBSTATIONDragging, loading, carriage and unloading of following store materials with proper stacking from ESC Daliganj to JE dumps store and from JE dump store to work site within municipal area. |
| 108 | 33 KV XLPE cable 3x300 mm2 |
| 109 | Cable jointing kit ST. TH. 33KV 3*300 sqmm |
| 110 | Cable jointing kit outdoor 33KV 3*300 sqmm |
| 111 | ACSR Panger conductor |
| 112 | 33KV LA |
| 113 | 33KV CT 400/200/1 A or 200/100/1A |
| 114 | 33KV Bus Isolator |
| 115 | Control pannel I/C for 33KV Single feeder |
| 116 | 33 KV VCB 1250 A, 750MVA with steel structure |
| 117 | 2x2.5mm2 control pannel |
| 118 | 4x2.5mm2 control pannel |
| 119 | 24Volt Battery with charger |
| 120 | Single core cable 1*400 sqmm |
| 121 | Aluminium Lug 630Sqmnn |
| 122 | Earthing Complete |
| 123 | 33 KV LINE ERECTION WORK |
| 124 | Fabrication & erection of 33 KV cable exposure type double pole with the provission of separate bus bar for each cable with fixing of necesory clamps and other acessories like danger board, numberplate, barbed wire, 6 no. pin insulators with pins,2 no. channels 125x65 mm (1600mm each),1 no.MS channel 125x65mm(3200mm in length) and 2 no.MS angle 65x65x6 mm (each 3200mm in length) for supporting the hoisting of cable & poles.itsjumpering by single core PVC aluminium cable with proper size of lug. (all material arranged by contractor except steel,pole, PVCaluminium cable & insulator) including hosting of 33KV cable on these D/P.as per RESPO norms. |
| 125 | Providing & Fixing of Cable route marker at 200mtr interval & at cable junction point (S/TH) along the under ground line |
| 126 | Laying of 33 KV XLPE cable by HDD Method |
| 127 | Laying of 33 KV XLPE cable by HDD Method in HDPE PIPE 140MM DIA |
| 128 | Construction of masonry type plinth for 33KV VCB of size 1.6x1.6x1M brick, sand, cement & stone grit including grouting of 04Nos foundation bolts for erection of 33KV VCB |
| 129 | Fabriction of Isolator structure minimum 3.5Mtr overall hight & 2.5Mtr above ground level as per Respo drawing with the help of MS Channel 125*65MM two pieces of MS channel joined ot each other by M.S Flat 50x6nnm duagibakky at the interval of 0.5ntr and top & botton of the structure, Grounting of Isolator structure in CC (cement, coarse sand and stone grit of 20mm gauge) including supply of necessary T&P and painting os structure complete, (only M.S. Channel and angle provided by the deptt.) |
| 130 | Lightening Arrestor/CT structure :- Fabrication of lightening arrestor/CT Structure as per Resspo drawing with the help of 2 Nos. M.S. Channel 125*65 mm mimimum 3.5mtr long grouting 1mtr deep from ground level in cc in ratio 1:4:8, complete in all respect. |
| 131 | Erection of structures, grouting, plinthing of All structure equipment. |
| 132 | Mounting of accessories/equipment on fabrication structure complete work with making proper alignment and tightening the work includes fabrication work if required for proper operation of equipment. |
| 133 | 33KV VCB |
| 134 | 33KV CT 400/200/1 A or 200/100/1A |
| 135 | 33KV Lightening Arrestors |
| 136 | Bus/Line Isolator |
| 137 | Fixing of Control pannel I/C for 33KV Single feeder, complete wiring of pannel as per drawing |
| 138 | Laying of 2x2.5mm2 cabke from different equipments to control pannel. |
| 139 | Laying of 4x2.5mm2 cabke from different equipments to control pannel. |
| 140 | Earthing of different equipments/pannel as per norms |
| 141 | Providing & fixing of G.I. Strip 50*6MM for earthing of different equipments using Arc welding including cutting/bending etc. |
| 142 | High pressure Testing of 33 KV cables/line/ as per norms |
| 143 | Complete electrical testing of 33KV VCB, CT & Control pannel including configuration of overcurrent & earth fault. |
| 144 | Return back balance material & Cable Drum from site to LESA store daliganj. Please Enable Macros to View BoQ information |