| 1 | Creation of 250 KVA sub-station at Arbal Banihal with HT/LT network. |
| 2 | 250 kVA (11/0.433-0.250KV;50Hz), Copper WoundDistribution Transformer of latest Energy EfficiencyLevel-2 (New), IS1180 Part-I; 2014 as per latest upto dateamendment with externally fitted MCCB with cable box and 4x4 Mtrs. suitable cable of ratings |
| 3 | Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymerhousing, Stn. Type |
| 4 | 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical |
| 5 | 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 6 | 300 mm² (1ckt.) 1.1 kv Grade, PVC insulated stranded conductor FRLS type |
| 7 | 9 Mtr. Long Pole( ST-410 SP33) for sub station |
| 8 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and80kV Negative, creepage distance 320mm |
| 9 | GI Channel/Angle/Flat of sizes including clamps |
| 10 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 11 | 11 KV polymeric composite Pin insulator, 12kv, 5 kn, lightening impulse 75 KV Positive and 80 KV Negative, creepage distance 320mm |
| 12 | Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete. |
| 13 | Wedge connctors/PG Clamps |
| 14 | Danger plates with clamps for substation |
| 15 | GI Barbed wire for Anti Climbing for sub station |
| 16 | 3-phase 4 wire Trivector meter with CT |
| 17 | Painting of all ST poles icluding 9 mtr of substation including cross arm, clamps with 1 coat of Red Oxide (Asian/Nerolac make) |
| 18 | Painting of all ST poles icluding 9 mtr of substation including cross arm, clamps with 2 coat of Aluminium Paint (Asian/Nerolac make) |
| 19 | LT Distribution Box for 250 kVA DTR with MCCB forincomer & Switch Fuse Units for Outgoing Circuits |
| 20 | Wire mesh boundary fencing around the Xmer Structure |
| 21 | Sundry Item like aluminium lugs, jumpers, binding tape. |
| 22 | 9 Mtr. Long Pole( ST-410 SP33) for HT network |
| 23 | GI V cross-arm with top Bracket including clamp |
| 24 | GI Channel X-arm including clamps and braces |
| 25 | 30 mm² ACSR Conductor |
| 26 | 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm |
| 27 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 28 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 29 | 8 Mtr. Long Pole(ST-410 SP15) for LT network |
| 30 | ACSR Rabbit |
| 31 | Shackle Insulator |
| 32 | M Clamp |
| 33 | Galvanized Nuts and Bolts for Substation/HT/LT |
| 34 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 35 | Danger Plates |
| 36 | Anti-Climbing Device with Clamps |
| 37 | Cement bottoming 1:2:4 mix as per REC standards.45cum /pole FOR ALL ST Poles including 9mtr ST Poles of substation Please Enable Macros to View BoQ information |