| 1 | Supply, Installation, tesing and commissioning of INDOOR TYPE 33KV, HT VCB Panel Board having 2 Nos. Incomers, 1 No. Bus-coupler and 2 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 33KV, 1250Amp, 31.5kA rms-3s, pannel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC. The Board shall consist of following panels : |
| 2 | 33KV INCOMER VCB PANEL : |
| 3 | 33KV, 1250Amp, 31.5KA rms-3s panel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC) |
| 4 | Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 600/300/5+5A, Core 1 : Class 5P10, 15VA and Core 2 : Class 0.5, 15VA |
| 5 | Potential Transformers : 1 set of 3 Nos. Single Phase Fixed Type PTs having ratio 33KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection |
| 6 | Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device |
| 7 | Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy |
| 8 | Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make |
| 9 | Protection & Auxiliary Relays : |
| 10 | 1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%). |
| 11 | 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V). |
| 12 | 1 No. Trip Circuit Supervision Relay |
| 13 | 1 No. High Speed Master Trip Relay |
| 14 | Additional Accessories and Features : |
| 15 | Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies |
| 16 | Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As Per Page No. Make:- ABB/Schneider/Siemens |
| 17 | 33KV OUTGOING VCB PANEL : |
| 18 | Same description as INCOMER PANEL above except following changes : |
| 19 | Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels |
| 20 | Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 400/200/5+5A PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2) |
| 21 | Additional Protection Relays : |
| 22 | 1 No. Numerical Transformer Protection Relay shall have Transformer Differential Protection, Restricted Earth Fault Protection, Over Current + Earth Fault Protection. Relay shall have complete control features. |
| 23 | 2 No. Auxiliary Relays for Transformer OTI, WTI & Buchholz - Alram & Trip Protection |
| 24 | 1 No. Trip Circuit Supervision Relay |
| 25 | 1 No. High Speed Master Trip Relay |
| 26 | Additional Accessories and Features : |
| 27 | 8 Window Annunciator along with Hooter (As per page No. )Make:- ABB/Schneider/Siemens |
| 28 | 33KV BUS-COUPLER VCB PANEL : |
| 29 | Same description as INCOMER PANEL above except following changes : |
| 30 | Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens |
| 31 | Supply, Installation, tesing and commissioning of INDOOR TYPE 11KV, HT VCB 1250Amp 25KA rms-3sec pannel with SCADA Campatibility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 9 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC.. The Board shall consist of following panels : |
| 32 | 11KV INCOMER VCB PANEL : |
| 33 | 11KV, 800Amp, 18.4KA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC) |
| 34 | Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2) |
| 35 | Potential Transformers : 1 set of 3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection |
| 36 | Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device |
| 37 | Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy |
| 38 | Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make |
| 39 | Protection & Auxiliary Relays : |
| 40 | 1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%). |
| 41 | 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V). |
| 42 | 1 No. Trip Circuit Supervision Relay |
| 43 | 1 No. High Speed Master Trip Relay |
| 44 | Additional Accessories and Features : |
| 45 | Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies |
| 46 | Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As per page No. )Make:- ABB/Schneider/Siemens |
| 47 | 11KV OUTGOING VCB PANEL : |
| 48 | Same description as INCOMER PANEL above except following changes : |
| 49 | Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels |
| 50 | Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA. (As per page No. )Make:- ABB/Schneider/Siemens |
| 51 | 11KV BUS-COUPLER VCB PANEL : |
| 52 | Same description as INCOMER PANEL above except following changes : |
| 53 | Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens |
| 54 | Supply, Installation, testing commissioning with loading, unloading etc. 33/11 K.V. Power Transformer 5 MVA outdoor distribution Transformer, Tapping range +5% to -15% in step of 2.5% each step with H.T./L.T. bushing, OTI, WTI, Buchholz, Marshalling box OLTC, AVR & RTCC Panel Having Losses-No load losses : 08KW & Load losses : 50 KW as per Latest Specification of UPPCL (Make: TRANSTRON/MODERN/ELECON or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report) |
| 55 | Supply Installation, and Commissioning of 63 KVA, 11/0.433 KV Transformer including loading, unloading, local carriage with all material, labour, T&P required for proper completion of the work. (Make: TRANSTRON/MODERN/ELECON or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report) |
| 56 | Construction of Power Transformer Plinth of Size 3.50 x 3.50 x 1 Mtr. and the top of Plinth 30 cm R.C.C. Work 1:2:4 with fixing of 02 Nos. Rail l.b. complete in all respect with required all material such as steel bar, brick, coarse sand, cement, labour and T&P etc for proper completion of the work as per specification of M.V.V.N.L. |
| 57 | Construction of Plinth for 63 KVA Transformer of size 2.00 x 1.25 x 1.0 Complete with all material, labour & T&P required for proper completion of work as per specifiaction drawing and direction of E/I. |
| 58 | Supply,Installation, testing & commissioning of 11 KV Indoor APFC pannel 12.65KV, 3960KVAr, 3- phase, 50 C/s housed in indoor type CRCA panel, capacitor bank having two variable steps of 1188 KVAR.and two variable steps 792 KVAR Aluminium busbars, Epoxy insulators, HT HRC fuse, Surge Suppressor etc. with details are follows-(10 11 KV, aluminium wound, Dry type series reactors a) 1188 KVAR, 11KV 0.2% for 1188 KVAR step-6 Nos., b) 0.792KVAr for 1188 KVAr 0.2% for 792 KVAR step-6 Nos., (2) 11 KV, 3- Phase dry type RVT-1 No. (3) 12 KV 3 Phase indoor type metal enclosed vaccum contactor-12 Nos. (4) Indoor type automatic PFcorrector unit-1 No. (5) IP 42, Indoor CRCA cubicle panel for accommodationg capacitors,series reator, Vaccum contactor, surge suppressor etc. -1set. |
| 59 | 9 KV,10 KA, Class lll surse arrestor |
| 60 | Control cables, lungs/thimble, Junction Box etc. |
| 61 | 11 KV 3 core al, XLPE Insulated 3x300 mm sq. Cable |
| 62 | 11 KV XLPE cable (3x300sq.mm) heat shrinkable jointing kit indoor. |
| 63 | 11 KV VCB Switchgear for capacitor bank with complete arangement Adddisnal pannel for connetion with existing 11 KV bus bar. |
| 64 | Casting of civil foundation. |
| 65 | Cable trench for laying of power/control cables. |
| 66 | Earthing for panel by Chemical pipe earthing.Make ABB/Schneider/Siemens/Crompton |
| 67 | Construction of Plinth for 33 KV RMU of size 2.25 x 2.25 x 0.75 Mtr.Complete with all material, labour & T&P required for proper completion of work as per specifiaction drawing and direction of E/I. |
| 68 | Supply & Fixing of 200Amp./ 415volt Heavy Duty bouble break complete with HRC fuse and 200A 4way Al Bus Bar on angle iron frame complete in all respect |
| 69 | Supply & Fixing of 32Amp. 415V. Metal clad TPN requireable type switch fuse unit on angle iron frame complete in all respects. PWD SI No. 315-2018 Cat.B |
| 70 | Providing necessary T&P and furniture for maintenance staff as per Item Given below. |
| 71 | 12 mm thick Rubber mat of size 2x 1 m PWD S.O.R. 2018 Item No. 1136 No. 4 |
| 72 | Brass Earth chain(MR) Nos. 2 |
| 73 | Rubber hand gloves tested on 1100V. Pair 4 |
| 74 | Maximum load/ minimum load tripping board complete with all necessary equipments. No. 1 |
| 75 | Single line diagram with board complete. No. 1 |
| 76 | Notice board. No. 1 |
| 77 | Wall clock No. 1 |
| 78 | First aid boxNo. 1 |
| 79 | Sign. board of S/S with stand. No. 1 |
| 80 | Key board No. 1 |
| 81 | Table with drawer & sunmica Armed chair No. 1 |
| 82 | Armed chair No. 6 |
| 83 | Rack No. 2 |
| 84 | Bench No. 2 |
| 85 | Making fire fighting arrangements in the control room building as per Item Given below. Page No- |
| 86 | Cost of Fire extinguisher 4.5 kg capacity complete with stand No. 4 |
| 87 | Cost of Fire bucket complete No. 6 |
| 88 | Cost of Fire bucket stand for 6 Nos. bucket made of M.S. Angle 45x45x6mm. No. 1 |
| 89 | Supply & Laying of Armoured control cable As per page No. Make Polycab/Gloster/Havells/Universal/KEI/Finolex |
| 90 | 4x2.5 Sqmm |
| 91 | 6x2.5 Sqmm |
| 92 | Supply, Installation, Testing & Commissioning of 24V, 20A Trickle cum Boost Battery Charger suitable for 24V 70AH Battery Bank and also to feed 5A Power to External Load such as Emergency Light etc.70AH, 30V Battery Bank SMF batteries with Mounting Rack & along with connecting Leads and other associated accessories. The Charger shall be suitable to operate Emergency Light Load along with 33kV HT VCB Closing / Opening and also 11kV VCB Closing & Opening. As per page No. |
| 93 | Construction of control cable trench of required size 0.30x0.45 Mtr. M-15 class brick work including plastering etc. and covered with R.C.C. slab (0.50x0.60M) size complete with all material, labour and T&P etc. required for proper completion of work. Detail analysis of Page No- |
| 94 | Supply & Filling of 20mm stone grit in yard 100mm thick complete in all respects. As per page No. |
| 95 | Supply & Laying of Al. conductor 33 KV (E) XLPE cross linked polyethylene) over all served cable with flat galvanised steel strip armouring at a depth of 1.0M below ground level over a cushion of 75mm thick sand bed alround and protect with bricks on sides and top surface 300x3x4 mm red stone the cable run shall be fixed on M.S clamp etc of suitable size and crossing the road cable shall run through 150mm dia hume pipe proper completion of work. Make Polycab/Gloster /Havells/Universal/KEI /Finolex As per page No. |
| 96 | (i) 300Sqmm 3 core |
| 97 | Supply & jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 33KV 3Core Complete in all respects. Make:- Raychem/3M/Densons |
| 98 | Out door 240-300 Sqmm As per DSR 2025 SI No. 23.8.3 |
| 99 | In door 240-300 Sqmm As per DSR 2025 SI No. 23.7.3 |
| 100 | Supply & Laying of following type high conductivity aluminum strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest amendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. Make Polycab/Gloster/Havells /Universal/KEI /Finolex |
| 101 | 70 Sqmm 3 core as per PWD SOR 2018 S.No. 506(d) |
| 102 | 300 Sqmm 3 Core as per page No. |
| 103 | 400 Sqmm 3 core as per page No. |
| 104 | Supply & Jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 11KV 3Core Complete in all respects.Make:- Raychem/3M/Densons |
| 105 | Indoor type 300-400 Sqmm As per DSR 2025 SI no. 23.4.4 |
| 106 | Indoor type 70 Sqmm As per DSR 2025 SI no. 23.4.1 |
| 107 | Outdoor type 300-400 Sqmm As per DSR 2025 SI no. 23.5.4 |
| 108 | Outdoor type 70 Sqmm As per DSR 2025 SI no. 23.5.1 |
| 109 | Supply and Erection of cable stand of size 3.00x0.50m above G.L. duly grouted with cement concrete upto 50 cm. depth for laying cables made of angle iron size (65x65x6mm) having welded M.S. flat of size 50x6mm on top middle, and 45mm above ground level for fixing cable by clamping with M.S. flat of 40x4mm size as per direction of E/I. |
| 110 | Supply & Laying of Al. conductor PVC insulated armoured served. sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side and top. On surface the cable run shall be fixed on M.S clamps of suitable size and crossing the road cable should run through 150mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I wire climpped at several places also armouring of cable shall be properly connected with earth conductor/terminal the job include the cost of all material, labour and T & P required for proper completion of the work. Make Polycab/Gloster/Havells /Universal /KEI /Finolex As per PWD SOR 2018 S.No. 501 h) & (l) |
| 111 | 10sqmm 4 core |
| 112 | 50 Sqmm 3½core |
| 113 | Supply and fixing of palm or pin copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects as per PWD SOR 2018, S.I. No. 504 |
| 114 | 10 Sqmm |
| 115 | 25 Sqmm |
| 116 | 50 Sqmm |
| 117 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of E/I. |
| 118 | 10 Sqmm 4 core As per PWD SOR 2018 SI no. 503 (h) |
| 119 | 50 Sqmm 3½ core As per PWD SOR 2018 SI no. 503 (L) |
| 120 | Supply & fixing of 7mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thick) having 3mm thickness with Single arm bracket (1Mtr length) on RCC foundation including the cost of 4 way connector with bakelite sheet fixed in G I Pole ,foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. UP PWD SOR 2018 SI No-641 Make:- Vallmont/Bajaj/RRISPAT CONSOUL |
| 121 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser/Reflector with 1.0 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 6 Amp SPMCB Complete driver set suitable for 30 to 40 watt. Confirming to IP 65 Protection Including Street light Bracket (60 cm long) with pole cap suitable for Street light Fittings complete in all respect as per direction of E/I.PWD SOR 2018 SI No-1420 CAT-AAA Make:- Philips/Havells/Polycab/Jaquar |
| 122 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D) |
| 123 | Supply and Burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 727 (D) |
| 124 | Making suitable earth of GI pole with 2.5 Mts. long 20mm M.S rod connected with 7/16 SWG G.S. wire duly clamped & binded on pole including the cost of materials, labour and T & P required for proper completion of work as per direction of E/I. |
| 125 | Supply and laying of 32mm x6 mm G.I strip from Earth Electrode directly in the ground as required complete in all respect as per PWD SOR-2018 item no. 717 |
| 126 | Supply and laying of 32mm x6 mm Copper strip Comlete As per PWD SOR 2018 SI. No. 720 |
| 127 | Supply & Fabrication of 8 SWG G.I. Wire mesh Security fencing by providing vertical supports of 50 x 50 x 6mm long including cutting bending at top at a distance of 0.60 Mtr. Including welding, cutting and Bending at bottom at a distance of 0.15 Mtr. Drilling of 04 Nos. Holes of 6mm Dia on Top for Holding the Barbed Wire at a distance of 125 mm hole to hole and 7 Hole in vertical position of 10mm Dia at a distance of 280mm hole to hole for riveting the chain link mesh of size 2\\" x 1\\" and MS Flat 50 x 6mm & 25x3mm and fixing the vertical support in plumb including brick work in repair wall with supply of all material, labour, T&P etc. required for proper completion of the work (Drawing Enclosed) as per MVVNL Specification |
| 128 | Supply & Fixing of 1200 mm Sweep of Ceiling Fans with Fan Motor of A.C. Permanent insulation capacitor rating confirming BEE 5 Star rating and IS: 374/79 and also comply with IS:1709/1984 with Latest ammendment. The rated voltage 220/240 Volts, 50 Hz, I-ph AC the fan assemble should consists of down rod blades, shackle canopies etc. and double ball bearing system. complete in all respect ( Make Havells, Bajaj, Crompton) |
| 129 | Supply & Fixng of 300 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect ( Make Havells, Bajaj, Crompton) |
| 130 | Supply & Fixng of 450 mm Sweep Heavy Duty 950 RPM 230 Volt single Phase Exhaust Fan. Complete in all respect ( Make Havells, Bajaj, Crompton) |
| 131 | Supply & Fixing of 16 SWG M.S Drum with Livers duly painted including making hole in the wall for exhaust fan and finishing properly complete in all respect as per PWD SOR 2018 SI No. 1122 (A) |
| 132 | Supply & Fixing of Shock Treatment Chart (Prescribed Under I.E. Rules) duly framed with glass and supported from back with hard board or soft board with supply of all material, labour, T&P for proper completion of work. Complete in all respect. as per PWD SOR 2018 SI No. 1134 |
| 133 | Supply & Fixing of Recess/ Surface/ Pendent Mounting Round 10 to 15 Watt L.E.D. Down lighter having powder coated Die cast Aluminium Housing with Heat Sink, Diffuser/ Reflector and Driver set complete in all respect as per PWD SOR 2018 S. No. 1402 Cat AAA |
| 134 | Supply & Fixing of L.E.D. Tubelight with Batten suitable for up to 1x22 Watt L.E.D. Tubelight including Tube on surface complete in all respect as per PWD SOR 2018 S.No. 1413 Cat AAA |
| 135 | Supply & Fixing of L.E.D. Street Light Fittings having Die cast Aluminium Body and diffuser/ Reflector with 1.0sqmm 3 core Multistrand copper unarmoured cable suitable length ,1 no. 6 Amp. SPMCB complete Driver Set suitable for 45 to 50 Watt confirming to IP 65 Protection including street light Bracket (60 cm long) with Pole cap suitable for street light fittings complete in all respect as per Direction of E/I. PWD SOR 2018 S.No. 1421 |
| 136 | Making & Fixing of Retro Radium Board frame with 50sqmm Hollow M.S. Pipe & ACP Sheet 3mm & Retro Radium base 3mm thick including all materials, Labour, T&P etc. and Fixing at Site Please Enable Macros to View BoQ information |