| 1 | DSR Item No.5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 2 | DSR Item No.5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets opf G.I. nut bolt & spring washer spaced at 50mm) |
| 3 | DSR Item 11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required |
| 4 | 3½ x 300 sq. mm (70mm) |
| 5 | Foundation for DG Set |
| 6 | DSR 2.6 (Civil) Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. (9.24+ 0.70) =9.94) (0.70 for angle iron grouting work for caging) |
| 7 | All kinds of soil |
| 8 | DSR 2.27 (Civil) Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete |
| 9 | DSR item No. 4.1 (Civil) Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-All work up to plinth level. |
| 10 | 1:5:10 (1 cement: 5 fine sand derived from natural sources: 10 graded stone aggregate 40 mm nominal size derived from natural sources). |
| 11 | DSR 5.22 (Civil) Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 12 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 13 | DSR Item No. 5.9 (Civil) Centering and shuttering including strutting, propping etc. and removal of form for : |
| 14 | Foundations, footings, basis of columns, etc. for mass concrete. |
| 15 | DSR 13.2.1 (Civil) 12 mm cement plaster of mix: 13.1.1 1:4 (1 cement: 4 fine sand). |
| 16 | DSR 5.1.3 (Civil) Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level i) 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size de rived from natural sources).(3.24 +0.70 = 3.94)(0.70 for angle iron grouting work for caging) |
| 17 | DSR 12.1.1 (Civil) Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 18 | 1.00 mm thick with zinc coating not less than 275 gm/m² |
| 19 | DSR 10.25.2 (Civil) Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
| 20 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works(400+210+80 =690) (Angle iron + Angle iron +MS flat) |
| 21 | DSR 15.16 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 22 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 23 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 24 | DSR 29.1 Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc.AS PER COMPLETE ITEM NO.14 OF DNIT. |
| 25 | 250KVA |
| 26 | Supply and Laying of following XLPE insulated and PVC sheathed, armoured, aluminium conductor cable of 1.1KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing DWC/RCC/HUME pipe as required at site. The job include the cost of making connections with suitable size of Al. Lugs/thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. The cable should be of Polycab / Havells / Finolex / RR Kabel / KEI / RPG / Universal/Grandlay make only. |
| 27 | Size 300 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 28 | Size 70 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 29 | Supplying and fixing exhaust gas piping of suitable dia. for 250 KVA DG Set welded black MS, B class pipe conforming to IS:3589 c0ut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50 mm thick (density 120 kg/m3), wrapped in wire mesh & cladding with 0.8 mm aluminium sheet etc. as required as per specifications for the 250 KVA DG set. (The item shall be measured on linear basis per each run of exhaust piping from outlet of silencer to end of exhaust piping). |
| 30 | Supplying and erection of MCCB BDB of following ways surface/ recess mounting, vertical type, MCCB 415 V, BDB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCBs 4 pole with MCBs and incomer as required to complete the job. The job includes cost of all labour and other petty material required to complete the job to the entire satisfaction of Engineer in charge of the work. The make should be of Lauritz Knudsen/ Hager/ ABB/ Legrand only. |
| 31 | 6 way (4 + 12), Double door |
| 32 | Fabricating, supplying & fixing of loose wire box of size 850 mm x150 mm x170 mm fabricated out of 16 SWG CRCA sheet steel complete with all accessories front open able cover making holes for conduit painting etc as required. The job includes 63 Amp backlite connector heavy duty for expansion of the circuit / wires for power, neutral, earth etc. as required as per site & this also includes all labour, petty material required to complete the job to the entire satisfaction of EIC of work. |
| 33 | Fabrication, Supplying, Installation, Testing and Commissioning of outdoor type double door Electric Control Panel of cubical construction conforming to IEC 61439 (Part I & Part II), floor mounted type, fabricated out of 2 mm thick CRCA sheet, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated of approved shade, having suitable capacity TPN Aluminum bus bars, DMC/ SMC bus bar supports, base frame of MS channel 100mm x 50mm x 6mm size, having switchgears and accessories , internal wiring with 2.5 sq.mm PVC insulated single core cable, common copper earth bar of size 25 x 5 mm over the entire width of panel and 2 nos. earth studs, cable entry from the top & bottom, cable gland plates, numbering, labeling etc. complete in all respect, suitable for operation on 415 V, 3 phase, 50 Hz. AC supply with protection class IP 54 as required. The job includes the cost of MCCB, accessories, interconnection with solid connection, carriage and installation of cubical panel at site to the entire satisfaction of Engineer in charge. The outdoor type double door Electric Control Panel should have provision of following switchgear and accessories:- (Note:- (Note: All MCCBs shall be with ROM, Spreader terminals) |
| 34 | LT panel |
| 35 | Detail of switch |
| 36 | Space for 400 Amp MCCB 4 pole-1 No. |
| 37 | Space for 125 Amp MCCB 3 pole-2 Nos. |
| 38 | Space for 63/100 Amp 3 pole -3 Nos. |
| 39 | Space for 63/100 Amp 3 pole -1 No. spare. |
| 40 | Metering |
| 41 | S/E of 1 no. intelligent multifunction digital meter to read V, A, KVA, KWH, THD, PF, Hz oh with 3 Nos. cast resin cast CT’s of 800/5 Amp Class I.O. Accuracy and 15 VA burden |
| 42 | S/E of 1 No. Phase indication lamp with 2 Amp backup MCB breaker ON/OFF indication light with MCB, test terminal block set circuits as per standard practice. |
| 43 | DSR 2.2 |
| 44 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 45 | 100 A,30KA,FPMCCB |
| 46 | 125 A,36KA,FPMCCB |
| 47 | 400 A,50KA,FPMCCB |
| 48 | DSR 2.10 |
| 49 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 50 | Single pole |
| 51 | Providing and fixing expanded metal mesh duly painted of size 20x60 mm and strands 3.25 mm wide 1.6 mm thick weighing 3.64 kg per sqm for encasing of rolled steel sections in beams, columns and grillages, excluding cost of hangers & this also includes all labour, petty material required to complete the job to the entire satisfaction of EIC of work. |
| 52 | Supply & erection of MS enclosure for 63 to 200 amp MCCB. The job includes all labour, petty material required to complete the job to the entire satisfaction of EIC of work. |
| 53 | Supply & erection of MS enclosure for 300 to 600 amp MCCB on existing angle iron structure. The cost of wooden board of suitable size & thickness for erection of MCCB enclosure is alos included in job. The job includes all labour, petty material required to complete the job to the entire satisfaction of EIC of work. |
| 54 | Supply and Laying of following XLPE insulated and PVC sheathed, armoured, aluminium conductor cable of 1.1KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing DWC/RCC/HUME pipe as required at site. The job include the cost of making connections with suitable size of Al. Lugs/thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. The cable should be of Polycab / Havells / Finolex / RR Kabel / KEI / RPG / Universal/Grandlay make only. |
| 55 | 35 Sq. mm. 3.5 Core |
| 56 | Labour charges for horizontal boring 1 Mtr. Below ground level including cost of 2 Nos. Pit digging and refilling complete in all respects upto entire satisfaction of the EIC of the work. |
| 57 | Shuffling of power & light /fan/computer points in each niche & switch board in various branches/ offices at various levels & separate neutral & earth wire of each circuit. The job including connection with 1.5 sq mm copper wire in switch board/ BDB as required. The job includes all labour and petty material required to complete the job to the entire satisfaction of the E.I.C. of the work. |
| 58 | Supply & erection of PVC double sheathed 8 core 2.5 mm copper conductor unarmed cable to be laid in existing pipe. The cable should be of Polycab / Havells / Finolex / RR Kabel / KEI / RPG / Universal/Grandlay make only. The job includes cost of all labour, T&P etc. to complete the job to the entire satisfaction of the EIC. |
| 59 | DSR 15.15 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 60 | 120 mm dia (OD-120 mm & ID-103 mm nominal) Please Enable Macros to View BoQ information |