| 1 | Wiring for light point / ceiling fan point /wall fan point including 6 amp 3 pin socket/call bell point / exhaust fan point with 1.5 sq mm FRLS /HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable size GI box and earthing the point with 1.5 sq mm,1.1 kV, FRLS/HFFR PVC insulated copper conductor single core cable etc as required.Preferred Make ( Wire,1.1 kV ):-Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approvedby Engineer-in ChargePreferred Make (Switch,Socket,Blank plate etc):-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in ChargePreferred Make ( MMS Pipe):-Prestoplast/Precision/AKG/ Anchor/Equivalent approved by Engineer-in Charge |
| 2 | Upto 6 metres.( Group A ) |
| 3 | upto 9 meters.( Group B ) |
| 4 | Rewiring for light point / ceiling fan point /wall fan point including 6 amp 3 pin socket/call bell point / exhaust fan point with 1.5 sq mm FRLS /HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable size GI box and earthing the point with 1.5 sq mm,1.1 kV, FRLS/HFFR PVC insulated copper conductor single core cable etc as required.Preferred Make ( Wire,1.1 kV ):-Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approvedby Engineer-in ChargePreferred Make (Switch,Socket,Blank plate etc):-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in ChargePreferred Make ( MMS Pipe):-Prestoplast/Precision/AKG/ Anchor/Equivalent approved by Engineer-in Charge |
| 5 | Upto 6 metres.( Group A ) |
| 6 | upto 9 meters.( Group B ) |
| 7 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required .Preferred Make ( Wire,1.1 kV):- Finolex/RR Kabel/Polycab/Havells/KEIPreferred Make ( MMS Pipe):- Presto plast/Precision/AKG/ Anchor/Equivalent approved by Engineer-in Charge |
| 8 | 2 X 1.5 sq mm + 1 X 1.5 sq mm for earth wire |
| 9 | 2 X 2.5 sq mm + 1 X 2.5 sq mm for earth wire |
| 10 | 2 X 4 sq mm + 1 X 4 sq mm for earth wire |
| 11 | 2 X 6 sq mm + 1 X 6 sq mm for earth wire |
| 12 | 2 X 10 sq mm + 1 X 6 sq mm for earth wire |
| 13 | 2 X 16 sq mm + 1 X 6 sq mm for earth wire |
| 14 | 4 X 2.5 sq mm + 2 X 2.5 sq mm for earth wire |
| 15 | 4 X 4 sq mm + 2 X 4 sq mm for earth wire |
| 16 | 4 X 6 sq mm + 2 X 6 sq mm for earth wire |
| 17 | 4 X 10 sq mm + 2 X 6 sq mm for earth wire |
| 18 | 4 X 16 sq mm + 2 X 6 sq mm for earth wire |
| 19 | 4 X 25 sq mm + 2 X 6 sq mm for earth wire |
| 20 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required.Preferred Make (MMS Pipe):-Presto plast/Precision/AKG/Anchor/Equivalent approved by Engineer-in Charge |
| 21 | 20 mm |
| 22 | 25 mm |
| 23 | 40 mm |
| 24 | Supplying and drawing following sizes of FRLS/ PVC insulated 1.1 kV grade copper conductorsingle core cable in the existing surface /recessed steel / PVC conduit as required.Preferred Make (Wire):- Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approved by Engineer-in Charge |
| 25 | 2 X 1.5 sq mm +1 X 1.5 sq mm for E.C.C |
| 26 | 2 X 2.5 sq mm +1 X 2.5 sq mm for E.C.C |
| 27 | 2 X 4 sq mm +1 X 4.0 sq mm for E.C.C |
| 28 | 2 X 6 sq mm +1 X 6.0 sq mm for E.C.C |
| 29 | Supplying and fixing metal box of following sizes on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.ISI Approved. |
| 30 | 75 mm X 75 mm X 60 mm deep |
| 31 | 100 mm X 100 mm X 60 mm deep |
| 32 | 150 mm X 150 mm X 60 mm deep |
| 33 | Supplying and fixing following sizes / modules ,GI box along with modular base & cover plate for modular switches in recess etc as required.Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge. |
| 34 | 1 or 2 Module (75 mm X 75 mm ) |
| 35 | 3 Module (100 mm X 75 mm ) |
| 36 | 4 Module (125 mm X 75 mm ) |
| 37 | 6 Module (200 mm X 77 mm ) |
| 38 | 8 Module (125 mm X 125 mm ) |
| 39 | 12 Module (200 mm X 150 mm ) |
| 40 | Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge. |
| 41 | 5 /6 Amps Switch |
| 42 | 15 /16 Amps Switch |
| 43 | 3 pin 5 /6 Amps Socket Outlet |
| 44 | 6 pin 15 / 16 Amps Socket Outlet |
| 45 | Supplying and fixing Two Module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.Preferred Make:-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge |
| 46 | Supplying & Fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 25 Amps modular socket outlet and 25 Amps modular SP MCB, \\"C\\" curve including connections,painting etc.as required.Preferred Make:-Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/Equivalent approved by Engineer-in Charge |
| 47 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. Preferred Make:-Anchor/Havells/Orient Equivalent approved by Engineer-in Charge |
| 48 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required Preferred Make:- Crabtree/Hager Insysta/Legrand Myline range/MK/Equivalent approved by Engineer-in Charge. |
| 49 | Supplying and fixing 3 pin, 5 amp ceiling rose including 3 inch x 3 inch PVC box/ wooden block with connection etc as required.Preferred Make:-Anchor/SSK/Equivalent approved by Engineer-in Charge. |
| 50 | Installation , testing and commissioning of pre- wired, fluorescent fitting /compact fluorescent fitting/LED fittings of all types complete with all accessories and tube etc. directly on false ceiling / wall including connection with 3 X1.5 sq mm FRLS PVC insulated copper conductor single core cable and earthing etc as required. |
| 51 | Installation, testing and commissioning of pre-wired,fluorescent fitting /compact fluorescent fitting of all types,complete with all accessories and tube/lamp etc., including supplying and fixing balland socket arrangement,2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connections with1.5 sq. mm FRLS/HFFR PVC insulated,copper conductor, single core cable and earthing etc. as required. |
| 52 | Supplying and fixing of extra conduit down rod of 20 cm Length (heavy gauge) GI pipe 15 mm dia wiring with 3 X 1.5 sq mm single core FRLS PVC cu cable including cutting, threading and painting etc as required.(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored.) |
| 53 | Supplying & Fixing of Four pole terminal for extention of existing electrical cable as where required of following rating, Preferred Make:-L&T/Hager/Havells/Legrand/Kirloskar/MK Equivalent approved by Engineer-in Charge |
| 54 | Up to 40 Amp |
| 55 | Above 40 Amp to 100 Amp |
| 56 | Above 100 Amp to 250 Amp |
| 57 | Removing and refixing of ceiling fan/exhaust fan/wall fan/ pedestal fan (Repairing fan) by checking the wire insulation,connection and applying new grease to the bearing, oil seal cleaning & oiling, replacement of bushes and shafts, nuts & bolts,safety pin, insulator etc as required. |
| 58 | Installation , testing and commissioning of wall fan/ ceiling fan including wiring the down rods of standard length (upto 30 cm ) with 3 X1.5 sq mm FRLS/HFFR PVC insulated copper conductor single core cable etc as required. |
| 59 | Installation of exhaust fan in the existing opening including of all hardwares & making good the damage connection, testing, commissioning etc. complete as required. |
| 60 | Upto 450 mm Sweep |
| 61 | Extra for fixing the louvers / shutters complete with frame for a exhaust fan of all sizes. |
| 62 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Wall Surface as required incl. S+F of 1 X 10 SWG rust free GI wire for E.C.C making holes and manding good the damages to original finish incl painting.( Cable Dept supply) |
| 63 | Upto 35 sq mm (rust free clamped with 1 mm thick rust free saddle) |
| 64 | Above 35 sq mm and upto 95 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 65 | Above 95 sq mm and upto 185 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 66 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Cable Tray along with S+F of 10 SWG GI wire as earth wire as required. |
| 67 | Upto 35 sq. mm (clamped with 1mm thick saddle @ 3 sets per metre.) |
| 68 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25 X 3mm MS flat clamp @ 3 sets per metre.) |
| 69 | Above 95 sq mm and upto 185 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 70 | Laying of cable as below after Cutting Floor/Pavement/Wall and making holes incl embedding the cable at an average depth as below and mending good the damages to original finish incl S+F of 1 X 10 SWG wire for ECC (Cable Dept Supply) |
| 71 | From 2.5 sq mm to 35 sq mm at an average depth of 75 mm in floor/ pavement/wall etc. |
| 72 | Above 35 sq mm to 95 sq mm at an average depth of 100 mm in floor/ pavement/wall etc. |
| 73 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size Direct in Ground including excavation, sand cushioning, protective covering @ 8 bricks per metre on each cable and refilling the trench etc. as required. |
| 74 | Upto 35 sq. mm |
| 75 | Above 35 sq. mm and upto 95 sq. mm |
| 76 | Above 95 sq mm and upto 185 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 77 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing Masonry Open Duct incl mending good the damages to original finish. (Cable Dept Supply). This includes S+F 10 SWG GI earth wire for cables. |
| 78 | Upto 35 sq mm . |
| 79 | Above 35 sq. mm and upto 95 sq. mm |
| 80 | Above 95 sq mm and upto 185 sq mm (rust free clamped with 25 X 3 mm rust free MS flat clamp) |
| 81 | Supplying and making End Termination with brass compression gland and lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 kV grade as required.Preferred Make:-ARUN/Dowells/3M /Equivalent approved by Engineer-in Charge |
| 82 | 2 X 6 sq mm (19 mm ) |
| 83 | 2 X 10 sq mm (19 mm ) |
| 84 | 2 X 16 sq mm ( 22 mm ) |
| 85 | 4 X 10 sq mm (25 mm ) |
| 86 | 4 X 16 sq mm (28 mm ) |
| 87 | 3.5 X 25 sq mm (28 mm ) |
| 88 | 3.5 X 35 sq mm (32 mm ) |
| 89 | 3.5 X 50 sq mm (35 mm ) |
| 90 | 3.5 X 70 sq mm (38 mm ) |
| 91 | 3.5 X 95 sq mm (45 mm ) |
| 92 | 3.5 X 120 sq mm (45 mm ) |
| 93 | 3.5 X 150 sq mm (45 mm ) |
| 94 | Earthing with perporated GI Earth Pipe 4.5 mtr long, 40 mm dia including accesssories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc for any type of soil (Morrumed/boldered soil) with charcoal/coke,salt and also pouring of shifted loose soil as required and as instructed by the EIC.Preferred Make (Pipe):- GI Pipe TATA (Medium) /Bansal (Medium)/Jindal (Medium)/Equivalent approved by Engineer-in Charge |
| 95 | Earthing with G.I. Earth Plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc.for any type of soil (Morrumed/boldered soil) with charcoal/ coke and salt as required. |
| 96 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.All Joints should be done after 4\\"over lapping of the strips and by welding only. |
| 97 | Supplying and Fixing Earth Busbar of G.I.Flat 25 mm X 6 mm on wall having clearance of 6 mm from wall incl. providing drilled holes on busbar complete with G.I. blots, nuts, washers, spacing heavy duty insulators etc as required. |
| 98 | Providing and fixing Hot dipped 6 SWG dia GI wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required for GI pipe earthing & others. |
| 99 | Earthing with Copper Earth Plate 600 mm X 600 mm X 3 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and 40 mm dia. GI (medium gauge) watering pipe of 2.7 metre long etc for any type of soil (Morrumed/boldered soil) with charcoal / coke and salt as required.Preferred Make (Pipe):-TATA (Medium) /Bansal (Medium) /Jindal (Medium)/Equivalent approved by Engineer-in Charge |
| 100 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.All Joints should be done by Brazing only after 4\\" overlapping the strips or as decided by the Engineer. |
| 101 | Providing and fixing Earth Bus of 50 mm X 5 mm copper strip on surface on two no heavy duty insulators for connection etc. as required. |
| 102 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required for copper plate earthing. |
| 103 | Supply and Fixing medium gauge Gi pipe (ISI-Medium) protection for cable entry including bending the pipe to the required shape complete as required with laying of wire/cable through pipe.Preferred Make:-Medium size TATA/Bansal/Jindal/Equivalent approved by Engineer-in Charge |
| 104 | 25 mm |
| 105 | 40 mm |
| 106 | Supplying and fixing DP/TPN MCB DB sheet steel Enclosure on surface/recess complete with connection, testing and commissioning etc.as required with out MCB. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 107 | Supplying and Fixing Four Pole (4P) MCCB DB Sheet Steel Enclosure on surface/recess complete with connection,testing and commissioning etc.as required with out MCB/MCCB Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 108 | 100/125 Amps, Four Pole, Enclosure for MCCB |
| 109 | 160 Amps, Four Pole,Enclosure for MCCB |
| 110 | 250 Amps, Four Pole,Enclosure for MCCB |
| 111 | Supplying and fixing 20/32 Amps,240 Volt SPN Industrial type socket outlet (With MCB),with 2 pole andearth,metal enclosed plug top along with 20/32 Amps,\\"C\\" curve,SP,MCB, in sheet steel enclosure,on surface or in recess with chained metal cover for the socket out let and complete with connections,testing and commissioning etc,as required.Preferred Make:- Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 112 | Supplying and fixing 20 Amps,415 Volt TPN Industrial type socket outlet (With MCB),with 4 pole and earth,metal enclosed plug top along with 20 Amps,\\"C\\"curve,TPN,MCB, in sheet steel enclosure,on surface or in recess with chained metal cover for the socket out let and complete with connections,testing and commissioning etc,as required.Preferred Make:-Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 113 | Supplying and fixing 32 Amps,415 Volt TPN Industrial type socket outlet (With MCB),with 4 pole and earth,metal enclosed plug top along with 32 Amps,\\"C\\" curve, TPN,MCB, in sheet steel enclosure,on surface or in recess with chained metal cover for the socket out let and complete with connections,testing and commissioning etc,as required.Preferred Make:-Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 114 | Supplying and fixing 63 Amps,415 Volt TPN Industrial type socket outlet (With MCB),with 4 pole and earth (3P +N+E-FP),metal enclosed plug top alongwith 63 Amps,\\"C\\" curve, TPN,MCB, in sheet steel enclosure,on surface or in recess with chained metal cover for the socket out let and complete with connections,testing and commissioning etc,as required.Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 115 | Supplying and fixing Cable End Box (Loose Wire Box)/junction box for Incomming/Outgoing, suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/recess, complete with connection,testing and commissioning etc.as required. Preferred Make:-Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 116 | For 6 way, Double door SPN MCBDB |
| 117 | Supplying and fixing Cable End Box (Loose Wire Box)/junction box for Incomming/Outgoing, suitable for following triple pole and neutral, horizontal/vertical type sheet steel, MCB distribution board, 240 Volts, on surface/recess, complete with connection,testing and commissioning etc.as required. Preferred Make:-Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 118 | For 4 way, Double door TPN MCBDB |
| 119 | Installation , testing and commissioning of pre- wired, fluorescent fitting /compact fluorescent fitting/LED fittings and all types of MCB,DB and other all types of electrical works by extra manpower set(one skillrd and one unskilled/day) complete the job. |
| 120 | Fixing of LED Batten Tube Light/ Out side LED Light/Surface down LED Light on the existing fixture as per complaints given by Departments. |
| 121 | Supplying and fixing following way, Single Pole and Neutral, (SPN DB)IP- 43, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Preferred Make:-Legrand/Hager/L&T/ABB/Equivalent approved by Engineer-in Charge |
| 122 | 6 Way , Double door |
| 123 | 8 Way , Double door |
| 124 | 12 Way Double door |
| 125 | 16 Way Double door |
| 126 | Supplying and fixing of following ways surface/ recess mounting, Horizontal type, IP-43,415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. Preferred Make:-Legrand/Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge |
| 127 | 4 Way (4 + 12), Double door |
| 128 | 6 Way (4 + 18), Double door |
| 129 | 8 Way (4 + 24), Double door |
| 130 | Supplying and fixing of following ways surface/ recess mounting, Vertical Type,IP-43, 415 V, TPN MCB DB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TP DB is normally used where 3 phase outlets are required.) Preferred Make:-Legrand/L&T/Hager/Siemens/Equivalent approved by Engineer-in Charge |
| 131 | 4 Way (4 + 12), Double door |
| 132 | 8 Way (4 + 24), Double door |
| 133 | 12 Way (4 + 36), Double door |
| 134 | Supplying and fixing double door Vertical TPN MCCB DB Distribution board for MCCB Incomer IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provisionfor earthing attachment Up to 160 Amp & 250 Amp Preferred Make:- Legr Legrand /Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge |
| 135 | 4 Way Double door (160 Amp & 250 Amp ) |
| 136 | 8 Way Double door (160 Amp & 250 Amp ) |
| 137 | 12 Way Double door ( 160 Amp & 250 Amp ) |
| 138 | Supplying and fixing 5 Amps to 32 Amps rating, 240/415 V,10 kA,“C” curve,miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Preferred Make:- Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge |
| 139 | Single Pole |
| 140 | Double Pole |
| 141 | Triple Pole |
| 142 | Triple Pole and Neutral |
| 143 | Supplying and fixing 40 Amps to 63Amps rating, 240/415 V,10 kA,“C”curve, MiniatureCircuit breaker suitable for inductive load of following poles in the existing MCB DB or inenclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABBEquivalent approved by Engineer-in Charge |
| 144 | Single Pole |
| 145 | Double Pole |
| 146 | Triple Pole |
| 147 | Four Pole |
| 148 | Supplying and fixing 80-125 Amps rating, 240/415 V, 10 kA, “C” curve, Miniature Circuit Breaker suitable for inductive load of following poles in the existing MCB DB or in enclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalentapproved by Engineer-in Charge |
| 149 | TriplePole MCB |
| 150 | Four Pole MCB |
| 151 | Supplying and fixing of Molded Case Circuit Breaker (MCCB),415 Volt, of Breaking capacity 30KA/36kA/50KAwith Icu = Ics (for 1 sec),adjustable overload setting (Thermal Magnetic) with two sets copper spreader terminals suitable for inductive load of following poles in the existing MCB/MCCB DB/SMDB or in enclosure complete with connections, testing and commissioning etc. as required.Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABBEquivalent approved by Engineer-in Charge |
| 152 | 100 Amps, FourPole MCCB |
| 153 | 125 Amps, FourPole MCCB |
| 154 | 250 Amps, FourPole MCCB |
| 155 | Supplying and fixing of Molded Case Circuit Breaker, 415Volt, of Breaking capacity 30KA/36kA/50KAwith Icu = Ics (for 1 sec),adjustable overload setting (Thermal Magnetic) with two sets copper spreader terminals suitable for inductive load of following poles in the existing MCB/MCCB DB/SMDB or in enclosure complete with connections, testing and commissioning etc. as required.Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABBEquivalent approved by Engineer-in Charge |
| 156 | 160 Amps, FourPole MCCB |
| 157 | Supplying & Fixing of AC Controller having one no 6-way SPN Double Door DB +Two no Contactor 25A like Hager Preferred Make Cat.no-ESC 225+ one no FM-1/Quartz daily or Time clock 110V,AC Base/Din mounting Link EH 111 Hager Preferred make with one no 6A SP,MCB+ internal wiring with 4sq.mm.copper circuit including connection with existing AC unit,etc. Make -Hager. |
| 158 | Cleaning ,Checking & fixing of Nut-Bolt,Eye pin,Insulator,capacitor etc of the Ceiling fan as per complaints given by Departments,.materials Department supply. |
| 159 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing ,wall colour matching (Light Yellow) including Suitable length of extra ceiling fan down rod heavy guage( Simplex ) etc. complete as required with 3years years on site replacement warranty the ceiling fan.Preferred Make-Havells/Orient/Crompton/Usha or equivalent Approved by EIC |
| 160 | 1200mm BLDC Ceiling Fan without Remote |
| 161 | Supplying & fixing of LED fittings 2 ft X 2 ft, 240 Volt, Lumen ≥ 3600, Efficacy ≥ 120 Lm/Watt, Power Factor ≥ 0.9, CCT ≥ 6500 K, CRI ≥ 80, THD max. 15%, IP 20, 120 degree beam angle, with necessary connection from the existing Light poin and Powder coated die cast /Extruded aluminium/CRCA Sheet Body.All the luminaires should be warranted for 3 years at the site free of cost. Permanent numbering of LED luminaires is mandatory during installation at the site.Preferred Make:- Havells/Philips/Jaquar/Wipro/Lighting Technologies/Equivalent approved by Engineer-in Charge |
| 162 | Supplying & fixing of 4 ft. LED batten with aluminum housing, polycarbonate diffuser, CCT = 6500 k, Lumen= 2000 lm , CRI> = 80, pf>= 0.9 , Efficacy >=110 lumen/watt ,with necessary connection from the existing Light poin and Powder coated die cast /Extruded aluminium/CRCA Sheet Body with 3 years warranty for free replacement Preferred. Make:-Havells/Philips/Jaquar/Wipro/Lighting Technologies/Equivalent approved by Engineer-in Charge |
| 163 | Supplying & fixing of LED Flood Light powder coated pressure die cast aluminium 240 Volt, Lumen ≥ 3600, Efficacy ≥ 120 Lm/Watt, Power Factor ≥ 0.9, CCT ≥ 6500 K, CRI ≥ 80, THD max. 15%, IP 20, 120 degree beam angle, with necessary connection from the existing Light point and powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver.All the luminaires should be warranted for 3 years at the site free of cost. Permanent numbering of LED luminaires is mandatory during installation at the site.Preferred Make:- Havells/Philips/Jaquar/Wipro/Lighting Technologies/Equivalent approved by Engineer-in Charge |
| 164 | 100 W |
| 165 | Dismantling of Light Fitting / Fans / SPN DB/ TPN DB/Main Switch /Main Supply Panel /existing old wiring,cable etc and shifting to site store including mending good damages to original finish. |
| 166 | Light Fitting/Celling Fan/Wall Fan/Exhaust Fan/Industrial plug & Socket DB/Metal Enclosure etc. |
| 167 | TPN DB/SPN DB/Main Switch etc.including accessories & old cable/Wiring |
| 168 | Medium Size main supply Panel etc. including accessories & old cable/Wiring Please Enable Macros to View BoQ information |