| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board including connection etc as required:- |
| 2 | Short Point :- |
| 3 | Medium Point :- |
| 4 | Long Point :- |
| 5 | Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2 x 1.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modular switch board , earthing the 3rd pin etc. as required. |
| 6 | Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2 x 2.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modular switch board, earthing the 3rd pin etc. as required. |
| 7 | Wiring for circuit/ Sub-main with following sizes PVC insulated copper conductor cable (FR) in PVC casing and capping etc.as required. |
| 8 | 2 x 1.5 sq mm:- |
| 9 | 2 x 2.5 sq mm:- |
| 10 | 2 x 4 sq.mm:- |
| 11 | 4 x 6 sq mm:- |
| 12 | 4 x 10 sq mm:- |
| 13 | Supplying and fixing of the following sizes GI (in recess) and plastic (on surface) modular switch boards etc. as required. |
| 14 | 6 module plastic switch board:- |
| 15 | 8 module plastic switch board:- |
| 16 | 12 module plastic switch board:- |
| 17 | Supplying and fixing of the following sizes modular type cover plates for GI/plastic modular switch boards etc. as required. |
| 18 | 6 module :- |
| 19 | 8 module :- |
| 20 | 12 module :- |
| 21 | Supplying and fixing of the following modular accessories including necessary connection etc. as required. |
| 22 | 6/10 amps one way SP switch (1M) :- |
| 23 | 16/20 amps one way SP switch (1M) :- |
| 24 | 3 pin 6/10 amps socket outlet (2M):- |
| 25 | 3/6 pin 16/20 amps socket outlet (2M):- |
| 26 | 5 step fan regulator (2M):- |
| 27 | Wiring for Circuit/Sub-main wiring with the following sizes of PVC insulated copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/ surface including connection etc. as required. |
| 28 | 1 x 1.5 sq.mm |
| 29 | 1 x 2.5 sq.mm |
| 30 | Providing earthing system with maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminal size 32mmx 6mm including accessories with masonry enclosure of CI cover plate size 12\\"x 12\\" having locking arrangement including CC works etc as required:- |
| 31 | Supply and fixing of 32mm x 6 mm GI strip on walls/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals. |
| 32 | Proving and fixing / Drawing 4.06 mm dia (8 SWG) Copper wire on surface or in existing G.I / PVC / Polythene pipe for loop earthing as required. |
| 33 | Providng and laying 15mm dia(medium gauge) G.I. pipe for drawing of 4.06mm (8SWG) dia G.I./ Copper wire for earth connection from earth electrodes etc as required. |
| 34 | Supplying and Fixing of the following sizes PVC Conduit (medium gauge) on surface with all accessories etc as required. |
| 35 | 19/20 mm dia |
| 36 | Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required:- |
| 37 | 100 amps 415 volts four strip Copper busbar chamber 4 ways of size (455mmx330mmx120mm):- |
| 38 | Supplying and installation of fuse unit kitkat/HRC/HBC of the following ratings in existing main switch/panel board including necessary connection etc as required:- |
| 39 | 100 amps kitkat porcelain fuse unit with base(rewireable):- |
| 40 | Supplying and installation of change over switch of following ratings in existing enclosure/panel including necessary connection etc. as required :- |
| 41 | 63 amps MCB-FP change over switch (without enclosure):- |
| 42 | Supplying and installation of powder coated steel sheet enclosure (MCB DB) suitable for 240/415 volts MCB/ Isolator/ RCCB (SP/ SPN /DP/TP/TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required. |
| 43 | (2+4) / 6 way SPN MCB DB (single door):- |
| 44 | (2+10)/12 way SPN MCB DB (single door):- |
| 45 | 6 way horizontal TPN MCB DB (Double door):- |
| 46 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required:- |
| 47 | 6 to 32 amps SP MCB:- |
| 48 | 40 amps DP MCB:- |
| 49 | 40/50/63 amps TPN MCB:- |
| 50 | Supplying &installation of isolators of following ratings in the existing MCB DB including connection etc. as required.[TSR (IE)2021 Page 44 SL.No.1217(a)] |
| 51 | 80/100 amps FP isolator:- |
| 52 | Supplying & installation of Surge Protection Device (SPD) of following ratings in the existing Panels/MCB DBs including necessay connections etc as required:- |
| 53 | Surge Protection Device (SPD, withdrawable) (Type-2) with Imax 70 KA (3P+N) :- |
| 54 | Catridge for Surge Protection Device (SPD) (Type-2) with Imax 70 KA (1P+N/3P+N) :- |
| 55 | Supplying and fixing of following surface/recess mounting LED luminaries complete with powder coated die cast housing and high efficiency diffuser including necessary connection etc. as required:(with 50000 burning hours and minimum lumen output of 100 lm/watt):- |
| 56 | Surface mounted box type batten suitable for single 18/20 watt integrated LED tube lamp(without lamp):- |
| 57 | Recessed round/Square shaped 12 watt LED downlight with integral driver and high quality polycarbonate diffuser:- |
| 58 | Recessed round/Square shaped 18 watt LED downlight with integral driver and high quality polycarbonate diffuser:- |
| 59 | Supplying and fixing of following LED Tubes, retrofit bulbs/lamps for LED luminaries including necessary connection etc. as requuired: [TSR(IE) 2021 page no 39 Sl No. 1103(a)] |
| 60 | 18/20 watt LED tube with integral driver and polycarbonate diffuser (50000 burning hours and minimum lumen output of 100 lm/watt):- |
| 61 | Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resistant tempered glass/diffuser including necessary connection etc. as required (50000 burning hours and minimum lumen output of 100 lm/watt):- |
| 62 | 40 watt LED post top light fixture with integral driver and high quality polycarbonate diffuser (IP 65):- |
| 63 | Supplying & fixing of decorative type wall mounting fancy bracket model no DWL-CHR-MB14048T1E27 of JAQUAR make/ phillips Platina with suitable lamp i/c necessary connection etc as reqd |
| 64 | Supplying of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades including wiring the down rod with 2 x 1.5 sqmm PVC insulated Copper conductor cable (FR) (ISI marked, BEE 1 star/minimum service value 4.0m3/min/W) |
| 65 | Supplying and fixing of MS frame made of (25 x 25 x 5)mm MS angle with necessary support by (40 x 6)mm MS flat and 10 mm thick boiled plywood on top, grouted on wall with 4 nos leg(25 x 25 x 5mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required. |
| 66 | Supply, Installation testing and commissioning of following ratings true online double conversion UPS with IGBT based rectifier and in-build Isolation Transformer , 50/60 Hz(Auto Sensing) frequency , unity PF voltage regulation +/- 1% Pure Sine wave form, total harmonic distortion <5% with fulol load noise level 50 dB at 1 meter , LED indication for normal mode /battery mode/bypass mode/system fault, audible alarm for main failure low battery , overload , fault and bypass mode complete with necessary battery bank MS rack for mounting battery bank , battery Interlink cables and all other necessary accessories including connection etc. as required. |
| 67 | 3 KVA -3 KW , 72V DC , 1 ph In/1 Ph Output , PF=1.0 Online UPS with 6 nos of 12V 100Ah battery bank etc. as required. |
| 68 | 3 KVA -3 KW , 96V DC , 1 ph In/1 Ph Output , PF=1.0 Online UPS with 8 nos of 12V 100 Ah battery bank etc. as required. |
| 69 | Supplying and fixing of following copper terminal ends:- |
| 70 | 2.5 sq mm |
| 71 | 4 sq mm |
| 72 | 6 sq mm |
| 73 | 10 sq mm Please Enable Macros to View BoQ information |