| 1 | Electrical Internal(Part A)SOLAR LIGHTING SYSTEM:-Supply installation testing and commissioning of 10 KVA off grid Solar System, 10 KVA, 120 Volt PCU - 1 No, 10 numbers 150 AH 12 Volt Battery, 30 number of 325 watt 24 volt Poly crystalline Solar Panel, Structure as required, wirring with 10 sqmm wire, MC4 connector, ACDB, DCDB complete in all respect as per direction of Engineer-in-charge, PCU Specification - 10 KVA 120V, Pure Sine Wave Design, Inbuilt in rMPPT charge controller (30 Percent more efficient).USB based communication, 30 days data logs Inbuilt AC & DC energy meter. Comply with IEC 61683 and IEC 60068-2-(1,2,14,30) standards. Robust design-20 yrs product life, 2 yrs of warranty. Reverse AC Voltage Protection. User friendly & accessible LCD Display with all AC and DC Parameters. Configurable by Display Switches and Digital LCD (20X4). ( Make of PCU - UTL Alfa + or equivalent), Battery specification - 150 Ah, 12 Volt Solar inverter tubular Battery(Make - Amaron/ Luminous/ Exide) Solar Panel Specification -325 watt 24 volt Polycrystalline Solar Panel BIS Certified Performance - Open-Circuit voltage (Voc): 45.53 Volt, optimum operating current (Imp): 8.68 Amps, short-circuit current (Isc): 9.22 Amps, Module efficiency: 16.85% Warranty: 12 years on product and 25 years performance warranty, Structure Specification - 40 x 40 x 6 GI angel, Wirring Specification - 10 sqmm Cu wire, MC4 Connector shall be used for connection. ACDB & DCBD as per the requirement shall be installed. |
| 2 | Supply & fixing of lightning finial 25mm dia x 300mm long copper. |
| 3 | Supplying and laying 25 mm x 6 mm CU earth strip ISI marked on surface or in recess for connection etc as required. |
| 4 | Supply and fixing of earthing with copper plate 600 mm x 600 mm x 3.15 mm thick ISI marked including accessories and providing masonary with cover plate having locking arrangement and watering pipe etc (But with out charcoal and salt) as required |
| 5 | Extra for using salt and charcoal for G.I. or copper plate earth as required |
| 6 | Supply and laying 8 SWG copper wire ISI marked at 0.5 meter below ground level for conductor earth electorde including soldering etc. as required |
| 7 | Recessed wiring to light point/Fan point/ Exhaust fan point/Call bell point with 1.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked with 20 mm dia non-metallic PVC flexible conduit with 6Amp, 250V Modular switch ISI marked and ceiling rose ISI marked mounted on metal box having front Modular cover of suitable size, metal box with 1.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire including all accessories and connection.(Make of wire-L&T/Anchor/Havells/V-Guard/Great White/HPL or any other approved make) Group-B L.P- F.P- C.B.P- |
| 8 | Group-C L.P- F.P- C.B.P- |
| 9 | Recessed wiring to submain in the following sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked conforming to IS-694/1990 in the following mm dia non-metallic heavy duty flexible conduit 1.6 mm thick along with the following sq.mm FR PVC insulated single core multistrand copper conductor as earth wire as required.(Make of wire-Finolex/L&T/Anchor/Havells/V-Guard//HPL or any other approved make)2 X 1.5 sq.mm +1 X 1.5 sq.mm in 20 mm dia |
| 10 | 2 X 2.5 sq.mm +1 X 1.5 sq.mm in 20 mm dia |
| 11 | 2 X 4 sq.mm +1 X 1.5 sq.mm in 20 mm dia |
| 12 | 2/3 way MCB enclosure Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 Sutable for Surface and Flush mounting Available in CRCA sheet steel RAL9003 powder coated With provision to mount MCB/Isolator/RCCB/RCBO and other modular devices |
| 13 | 4way single door |
| 14 | Supply and fixing of following rating 240 V/415 V \\"C\\" series MCB suitable for lighting and other loads of the following poles in the exiting MCB DB ISI marked complete with connections testing and commissioning etc. (Make-HPL/ Havells/ Legrand /L&T/C&S or any other approved make)SP MCB 6-32A C-series |
| 15 | Supply and fixing of twin core unarmoured PVC insulated 10 sqmm Al wire with GI wire support |
| 16 | Supply and laying of 3 core 10 sqmm sheathed Copper cable in exiting conduit |
| 17 | 63Amp Iron clad double pole main switch with M.S board.of size 250x300x60mm deep in recesss includig wall cutting and making good the same with wiring complete in all respect |
| 18 | Supply and fixing of 8 way 100 Amp Bus Bar Chamber Please Enable Macros to View BoQ information |