Name of Work:- Electrical renovation of all toilet block of all buildings [All floor] of Murshidabad Medical College and Hospital (Electrical Work).
Sl. No.
Item Description
1
Supply & Fixing of Heavy Duty Exhaust fans complete with all accessories having the following Model (Full metal body) 9\\" ( 225mm ) Speed 1370 RPM ( Make -EPC/Crompton/USHA )
2
Supply & Fixing of Heavy Duty Exhaust fans complete with all accessories having the following Model (Full metal body) 12\\" ( 300mm ) Speed 1420 RPM ( Make -EPC/Crompton/USHA )
3
Supply & Fixing of Heavy Duty Exhaust fans complete with all accessories having the following Model (Full metal body) 18\\" ( 450mm ) Speed 920 RPM ( Make -EPC/Crompton/USHA )
4
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
5
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) [PWD GS: Pge No: E-14, 1(a-i)]
6
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modulartype switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish.[only PVC Rigid Conduit on ceiling and remaining portion concealed][PWD/GS Page: E-25 Item: 4(c)] Average run 9 mtr
7
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long)
8
30 cm Exhaust fan (12\\") [PWD/GS Page: D-14 Item: 33]
9
60 cm Exhaust fan (24\\") [PWD/GS Page: D-14 Item: 33]
10
Supply & Fixing Single LED T8 T/L fittings( Philips TMC 502 P 1xT-LED 22W ) incl. 1x MAS LED tube 1200mm 18W865 T8 I--2100lm) suspended fromfrom ceiling/beam with L-clamp