| 1 | Material and labour for disconnecting the electric connection and dismantling the existing old LT panel board of any size and keeping aside in safe custody / deposoting to MES store yard including its accessories as schedule of credit to contractor or as directed by Engneer-in-Charge.Note:-(i) work should only be carried out in presence of JE E/M. |
| 2 | Supply and Fixing LT Bus bar chamber Outdoor/floor mounted suitable for 415V 3 phase 4 wire 50 Hz AC Supply system busbar capacity 200A as specified. The panel should be powder coated paint for better environmental protection, made of CRCA sheet steel 3.15 mm having RYB indicating lamp and multifunctional meter for Ampere and voltage rating including making of foundation of the panel, lugs and gland of suitable size, fixing and connection included complete all as specified and as directed.Note:-(i) work should only be carried out in presence of JE E/M. |
| 3 | Material and labour for disconnecting all XLPE cables from panel and carry out preventive Repair/Repacement of unserviceable existing wiring of LT Panel/APFC Panel, cleaning of bus bar with CRC spray and wiring with new copper wiring 2.5/4 sqmm with copper/aluminium lugs, replacing burnt epoxy insulator bar and insulating the bus bar with tape conforming with colour code and reconnecting all cables, complete all as specified and as directed.Note:-(i) work should only be carried out in presence of JE E/M. (ii). The items which will be replaced will be measured and paid separately as \\"Supply Only\\" item of this schedule. |
| 4 | Supply only the following items:- ( to be incorporated under item No : 3.00 above). |
| 5 | 2.5 sqmm single core sheathed copper cable |
| 6 | 4 sqmm single core sheathed copper cable |
| 7 | 6 sqmm single core sheathed copper cable |
| 8 | Copper lugs of suitable size |
| 9 | DMC resin/Red polyamide type Epoxy insulator bus bar connector/supporter of suitable size/dimension |
| 10 | LT Panel Locking set |
| 11 | EPDM Rubber gasket for door sealing. |
| 12 | PU Foam insulation sealent can for sealing cable entry |
| 13 | PVC Grommet of suitable size at cable entry |
| 14 | LT Panel Handle set |
| 15 | Supply and fix in repair for 3 Phase ammeter digital type 3.5 digit displayt 0-500A range squre shape with CT Coil fixed to existing LT Panels, complete all as specified and as directed. |
| 16 | Supply and fix in repair for 3 Phase Voltmeter digital type 3.5 digit displayt 0-500V range squre shape with PT Coil fixed to existing LT Panels, complete all as specified and as directed. |
| 17 | Material and labour for painting of LT Panels of frontal size less than one squre meter by prepration of old painted surfaces, cleaning refixing panel board door with hinges, nut bolts etc. removing of existing rust grease oil spot etc, priming with aluminium red-oxide and then applying 1st grade of synthetic enamelled spray paint (two coat) of approved make, brand and colours (includes cost of paint) & foundation and painting names of the distribution location, complete all as specified and as directed. |
| 18 | All as per item No. 7.00 mentioned here-in-above but frontal size more than one squre meter. |
| 19 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 6 Sqmm 2 core as per IS 7098 (Part I) in trenches/on wall/poles laid in ducts/inside protection pipe of the following cross sectional area including cable glands,lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) including taking out old U/S cable all as directed by the Engr-in-Charge.Note:- (i) Excavation, Earth work, brick protection and sand cushioning shall be measured and paid separately under respective item. (ii) Cable route indicator of metal of height 600 mm above GL duly written \\"LT CABLE\\" on every 50 mtr to be fixed with PCC, 150 mm below the GL , Cost of route indicator and PCC for fixing indicators to be deemed in this item rate. |
| 20 | All as per item No 9.00 mentioned here-in-above but 10 Sqmm 4 Core. |
| 21 | All as per item No 9.00 mentioned here-in-above but 16 Sqmm 4 Core complete all as specified and directed. |
| 22 | All as per item No 9.00 mentioned here-in-above but 70 Sqmm 3½ Core complete all as specified and directed. |
| 23 | All as per item No 9.00 mentioned here-in-above but 95 Sqmm 3½ Core complete all as specified and directed. |
| 24 | All as per item No 9.00 mentioned here-in-above but 120 Sqmm 3½ Core complete all as specified and directed. |
| 25 | Excavation in trenches not exc 1.50 meter wide and not exceeding 1.50 metre in depth for taking out/laying of under ground cable, pole or stay and getting out in soft/loose soil, complete all as specified and as directed. |
| 26 | Returnig , filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in soft / loose soil, complete all as specified and as directed. |
| 27 | Removing excavated materials (soils) not exceeding 50.00 metre and depositing where directed at a level not exeeding 1.50 meter above the starting point in soil, complete all as specified and as directed. |
| 28 | Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling, complete all as specified and directed .Note :- Punned thickness 18 cm shall only be considered for payment. |
| 29 | Supply and lay in trenches brick, common burnt in clay, building brick, sub class 'B' designation 75 for cable protection, complere all as specified and directed by the Engr-in-Charge. |
| 30 | Supply and fixing in replacement 50 mm bore for GI protection pipe \\"light grade\\" galvanized with including all fittings laid in trenches or fixed on pole, complete all as specified and as directed by the Engr-in-Charge. |
| 31 | Boring of holes under road, pavement, hard standing mannually or by trenchless technology using ultra sounding technique and necessary machine or mannually etc. as per site requirment, complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 32 | Boring of holes under road, pavement, hard standing mannually or by trenchless technology using ultra sounding technique and necessary machine or mannually etc. as per site requirment, complete all as specified and as directed. Please Enable Macros to View BoQ information |