| 1 | Supplying , Installation, Testing and commissioning of Vertical Turbine pump set with SS impeller capable to discharge 126 m3/hr.against total head of 50 m, (make Kirloskar/Jyoti/Wilo-Mather&Platt/WPIL) coupled with suitable capacity vertical hollow shaft/solid shaft Squirrel cage induction motor , rating of motor 20% more BHP than that of pump (make Kirloskar /ABB /CGL/ Siemens) operated on 415 +/- 10% volt, 3 phase , 50 C/S A.C supply , IE3 type as per IS:325 and IEC:63400-Ihaving speed 1450 rpm,with heavy duty M.S. column assembly with SS line shaft and each coloumn of 5 feet length including cost of supplying , fitting and fixing of all required accessories such as CIDF sluice valve-1 set, CIDF NR valve-1 set, pressure gauge-1 No, strainer-1 No, M.S. channel base plate etc. all complete including cost of taken out existing old pumpset. |
| 2 | Supplying and Installation of FASD starter suitable for above mentioned VT pumpset make LK/BCH/Schneider. |
| 3 | Supplying and Laying of 25 mm2 , 1.1 kv, 3 core PVC insulated unarmoured copper cable make Polycab/KEI/Gloster, from starter to motor. |
| 4 | Supplying, Installation Testing and commissioning of Horizontal split casing centrifugal pump set with Bronze impeller having discharge 126 m3/hr. against total head of 35 m, (make - Kirloskar/Jyoti/Wilo-Mather&Platt/WPIL), coupled with suitable capacity squirrel cage induction motor, rating of motor 20% more BHP than that of pump(make Kirloskar /ABB /CGL/ Siemens) ,TEFC, IE3 type as per IS:325 and IEC:63400-Ihaving speed 1450 rpm,operated on 415 +/- 10% volt, 3 phase , 50 C/S A.C supply, mounted on a commonM.S. base plate including cost of supplying , fitting and fixing of all required accessories such as CIDF sluice valve-1 set, CIDF NR valve-1 set, pressure gauge-1 No, Foot valve-1No, etc. all complete including cost of taken out existing old pumpset. |
| 5 | Supplying and Installation of FASD starter suitable for above mentioned C/F pumpset make LK/BCH/Schneider. |
| 6 | Supplying and Laying of 16 mm2 , 1.1 kv, 3 core PVC insulated unarmoured copper cable make Polycab/KEI/Gloster, from starter to motor. |
| 7 | Cost towards complete repairing of control panel at Intake well with changing of damaged parts such as :-1.150 Amp TPN MCCB,50 KA -1 No. as incoming feeder.2. 75 Amp TP MCCB, 50 KA-2No as outgoing feeder.3.Star delta timer-2Nos(One for each starter) 4. 32 Amp switch fuse unit -01 No. for internal and external light load.5. (0-500 v) Volt meter-01 No., Ampere meter-01 No.,Three phase indicator lamp,Powder coating paint,Push Button ON/OFF,ON/OFF/TRIP Indicator lamp,Wiring,etc as per required and testing on full load . |
| 8 | Cost towards providing all labour, tools and technicians for taken out and dismantling 40 HP VT P/Set with bowl assembly, 6\\" dia. coloumn pipe and line shaft etc all complete. |
| 9 | Cost towards dismantling and repairing of complete bowl assembly. |
| 10 | Cost towards making supplying and fitting S.S. top shaft as per size and sample. |
| 11 | Cost towards making supplying and fitting of C.I. spider bearing having OD 6.5\\" with rubber bush as per size and sample. |
| 12 | Cost towards lowering of VT P/Set. After complete repairing and assembling works. |
| 13 | Cost towards complete repairing of control panel at clear water pump house with changing of damaged parts such as :-1.125 Amp TPN MCCB,50 KA -1 No. as incoming feeder.2. 63 Amp TP MCCB, 50 KA-2No as outgoing feeder.3.Star delta timer-2Nos(One for each starter) 4. 32 Amp switch fuse unit -01 No. for internal and external light load.5. (0-500 v) Volt meter-01 No., Ampere meter-01 No.,Three phase indicator lamp,Powder coating paint,Push Button ON/OFF,ON/OFF/TRIP Indicator lamp,Wiring,etc as per required and testing on full load . Please Enable Macros to View BoQ information |