| 1 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 2 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 3 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 4 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 6 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 8 | 25 mm |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 10 | 15/16 A switch |
| 11 | 6 pin 15/16 A socket outlet |
| 12 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 13 | 6 Module (200mmX75mm) |
| 14 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 15 | 100 A,30KA,FPMCCB |
| 16 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 17 | 6 way , Double door |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Single pole |
| 20 | Double pole |
| 21 | Triple pole and neutral |
| 22 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 23 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 24 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) |
| 25 | 36 watt |
| 26 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 27 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 28 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 29 | 3½ X 35 sq. mm (32mm) |
| 30 | Supplying of labour for miscellaneous work for dismantling of boards, wiring etc |
| 31 | Skilled labour in Electrical trade |
| 32 | Unskilled labour in Electrical trade |
| 33 | Supplying and fixing of following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 34 | 63A Triple pole |
| 35 | 63A Double pole |
| 36 | 40A Double pole |
| 37 | 40A Single pole |
| 38 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 250 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required. |
| 39 | 12 way (4W X 3), Double door |
| 40 | Supplying and laying of following size of FRLS PVC insulated copper conductor, single core cable in the existing surface PVC conduit or on the existing cable tray as required. |
| 41 | 2 X 10 mm2 FRLS CU cable |
| 42 | Supply, loading, transportation, unloading at site, storage st site, shifting from storage place to site of following size of XLPE Insulated PVC Sheathed, Aluminium Conductor armoured power cable of 1.1 KV grade conforming to IS amended upto date and as per specifications |
| 43 | 3.5C X 35 sq. mm XLPE Al Cable Please Enable Macros to View BoQ information |