| 1 | Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 2 | Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required (single pin set) |
| 3 | Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 4 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.Above 8.0 metre and upto 10.0 metre |
| 5 | Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to bededucted) |
| 6 | Erection of angle iron/ channel iron cross arm on wood/ RCC/ PCC/ steel tubular/ rail pole etc. as required. |
| 7 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:240 sqmm |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.400 sq mm single core x 4 run |
| 10 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 11 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 12 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.1. nut, bolt, spring,washer excavation and re-filling etc. as required. |
| 13 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 14 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 15 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.630 A,50KA,FPMCCB |
| 16 | 250 A,36KA,FPMCCB |
| 17 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled whiteon both sides, and with inscription in single red colour on front side as required. |
| 18 | Surface dressing of the ground including removing vegetation and inequalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. 2.28.1 All kinds of soil |
| 19 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.2.8.1 All kinds of soil |
| 20 | Supplying and filling in plinth with sand under floors, including watering,ramming, consolidating and dressing complete. |
| 21 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:5:10 (1 cement : 5 coarse sand (zoneIII)derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 22 | Centering and shuttering including strutting, propping etc. and removal of form for all heights :Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 23 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 24 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : Suspended floors, roofs, landings, balconies and access platform |
| 25 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. ThermoMechanically Treated bars of grade Fe-500D or more. |
| 26 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 27 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. ThermoMechanically Treated bars of grade Fe-500D or more. |
| 28 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns,pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 29 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 30 | 12 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) |
| 31 | Neat cement punning |
| 32 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 33 | Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. 10.26.1 M.S. tube |
| 34 | Finishing walls with Acrylic Smooth exterior paint of required shade :13.46.1 New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 35 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : 13.62.1 Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 36 | Supplying and fixing of 11 KV 400 A Gang operated switch with all accessories complete as required and as directed by the department. |
| 37 | Supplying and fixing of 11 KV 400 A D.O. fuse set complete as required and as directed by the department. |
| 38 | Supplying, installation testing and commissioning of 750 ~800 kVA, 50 HZ, 11 kV/0.433 kV copper wound, outdoor type, oil-filled transformer With off circuit tap Change, ONAN (Dyn11),5 star rating with all accessories complete and as per the direction of the department including official inspection of 750~800 kVA transformer testing at factory site by departmental officers from NIT Silchar, for ensuring compliance with technical specifications and safety norms prior to commissioning at site.Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-bottom filter valve g) Thermometer pocket with cap; h) Lifting lugs for the complete transformer as well as for core and winding assembly; i) Pressure relief device or explosion vent j) One filter valve on the upper side of the tank ;k) Inspection hole ; l) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); m) Buchholz relay for transformers n) Oil level indicator o). Monogram Plate p) Inspection cover q). Detachable type radiators with top and bottom shutoff valve. r)Oil Conservator with Oil level indicator, minimum level marking and drain plug s) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for alltransformers with the Regulations, Guidelines and Standards as mentioned below Energy Efficiency Level : 1;Fittings :IS 1180 where applicable; make: Crompton Greaves,Schneider or equivalent make |
| 39 | Supply of 11/33 KV HT 3 core Stranded compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting compound, XLPE Insulated, Insulation Screening with truded Semi Conducting compound in combination with Copper Tape (0.3kA for 1 se , cores laid up, inner sheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed cable conforming to IS 7098 / (PART-I 1985 with latest amendment. (Nicco/ Havells/ RPG/CCI/Polycab/Gloster/ Finolex make) A) 240 sq mm 3 Core armoured 11 KV (E) H.T. U.G. cable. |
| 40 | Supply of following size PVC/XLPE insulated and PVC sheathed 1.1 KV G Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium f1100V grade as per IS 7908(Part 1) 1988 armoured U.G. cable as specified and directed by the deptt. ( Havells/ RPG/CCI/Polycab/ Finolex make) 400Sq. mm.Single Core armoured U.G. cable |
| 41 | Supplying and fixing including connections of the Aluminium Lugs for following size of PVC insulated and PVC sheathed/XLPE Aluminium conductor cable of 1.1 KV grade as required.a) 4 X 400 Sqmm single core cable(4 lugs) |
| 42 | Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type (MDO) with guide frame and 4 standard auxiliary contacts in the existing cubical panel board of the following capacity complete with making necessary connection as specified and directed by the deptt. (ABB Emax/L & T / Siemens 3 WL/ Schneider Master pact NW)1250A Breaking capacity @ Ics = 50 KA (MDO) |
| 43 | Supplying with fitting and fixing four pole 415 V front handle operated on load changeover switch with powder painted sheet steel enclosure outdoor type confirming to IP 65 protection fitted on angle iron frame of the following capacity complete with a provission for sufficient space for 400 sq mm single core cable x 16 runs for incoming and 400 sqmm single core cable x 8 runs for outgoing with making necessary connection as approved ,specified and directed by the deptt.The panel board is to be erected in 1 : 3 : 6 PCC foundation including excavation of trench and brick soling etc. complete.(C&S,Havells,Indo Asian,HPL,Socomec,GECO,L&T make) 1250 A |
| 44 | Supplying including installation, commissioning of vermin and dust proof totally enclosed, Phosphatised Powder Painted cubical outdoor, compartmentalize cubical type panel board of suitable size made of 18 SWG sheet with a provision for 1400 amps copper busbar, One 1250 Amps ACB as incomer and 1 no 630 Amps MCCB and Three nos 250 Amps MCCB as outgoing ,Ampere meter,Voltmeter and Phase selector switch,LED indication lamps etc as specified and directed by the deptt. The panel board is to be erected in 1 : 3 : 6 PCC foundation including excavation of trench and brick soling etc. complete . confirming to IP 65 protection .The drawing should be approved by the deptt. |
| 45 | Supplying of the following specification as hot dip Galvanized Steel tubular pole manufacturing out from electrically welded in 3 (three section having a base plate including providing all required building materials as directed and specified by the deptt. (BANSAL/Nezone or equivalent make)SP 43 Length of pole = 10.00 metre., Length of sections, Bottom = 5.20 M, Middle = 2.40 M, Top = 2.40 M, Out side dia. & Thickness Bottom = 165.10 x 4.50 mm, Middle =138.70 x 4.50 mm, Top =114.3 x 3.65 mm Please Enable Macros to View BoQ information |