| 1 | Taking down old/burnt cable of any size and Supply and fixing Aerial bunched cable (AB) LT of size 3 core- x50sqmm+1-core x35 sqmm with three power cores stranded compacted circular aluminium conductor screened with black extruded semiconducting compound, natural coloured XLPE insulated core screened with black extruded semi conducting compound and one layer of copper tape and covered with black extruded PVC(core identification by colour tape marking red, yellow and blue with colour tape placed longitudinally under the copper tape) and one bare messenger wire shall be stranded non compacted circular aluminium alloy conductor all as specified and directed. Make-KEI, Havells, Gloster, PolycabNote:- The following hardware fittings and accessories shall be used to install erect and join the AB cable(i) Suspension clamp with eye hook(ii) Suspension fittings and corresponding eye hook(iii) Dead eye fittings(iv) Nylon Tie(v) connectors |
| 2 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 6 sqmm 2 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 3 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 10 sqmm 3 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 4 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 16 sqmm 4 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 5 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 25 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 6 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 35 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 7 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 50 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 8 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 70 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 9 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 95 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 10 | Taking down burnt cable and supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 120 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. |
| 11 | LT cable joint kit complete set of heat shrink type, straight through of size 16 sqmm to 50 sqmm 04 core incl excavation and returning filling and making good distrubed surface in repairs complete all as specified and directed. |
| 12 | LT cable joint kit complete set of heat shrink type, straight through of size 70 sqmm to 95 sqmm 04 core incl excavation and returning filling and making good distrubed surface in repairs complete all as specified and directed. |
| 13 | Cutting/trimming/Chopping of tree branches along the over head lines of LT upto 5 mtr from elect line on both sides of the span and disposing off the cut trees/branches to a distance of n.exc 50m and clearing the site as directed. |
| 14 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 16 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 15 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 25 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 16 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 35 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 17 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 50 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 18 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 70 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 19 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 95 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 20 | Aluminium cable thimbles / line connector/pin terminal/ ring terminal/insulated ring terminal/fork type terminals/bi-metallic terminals etc of size 120 Sqmm UG Cable including in repairs complete connection and crimping complete all as specified and directed. |
| 21 | Earthing complete with galvanized steel earth plate electrode 600mm x600mm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground leel, connecting to the Galvanised earthing lead strip 32x6mm size, by means of bolts, nuts, heck nuts and washers of galvanized iron and earth lead protected by provision of GI medium grade pipe 65mm bore incl provision of concrete pit in PCC 1:2:4 type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC 1:2:4 reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 02 Nos and with 6mm dia MS bar handle made to shape Gl medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt & charcoal filling, test point made out of 40mm x 8mm Fl with fixing arrangement, funnel, wire mesh and earth work in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtrs, all as per electrical plate No 5 of SSR-1991 Part I and connected to earth test point all as specified or indicated incl testing on completion. |
| 22 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying cable including getting out in any type of soil complete all as specified and directed. |
| 23 | Returning filling including spreading watering and well ramming in layers not exc 25 cm complete all as specifed .. |
| 24 | Removing surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed |
| 25 | Sand cushioning to under ground cable, 8 cms thick before laying the cable and 15 cms thick after laying and stretching the cable in trenches including hand punning and consolidating, punned to 18cm thickness, complete all as specified and directed. Note : For payment purpose, only punned thickness shall be measured. |
| 26 | Supply and laying sub class `B` bricks laid dry flat transversely along the length of cable with width equal to the length of bricks over sand cushioning as protection cover of cable laid, complete all as specified and directed. |
| 27 | Steel tubular swaged type LT poles 9 meters long, pole should be in one piece only and smooth finishing and smooth finishing of pole, ISI marked complete with all accessories such as cast iron base plate, finial taper plug,bolts, nuts, screws, washers and drilling of holes for continuous Gl earth wire as specified type 410 SP-31 including applying two coats of aluminium paint over one coat of red oxide zinc chrome primer and embedded portion shall be painted with two coats of black paint after preparation of surface incl taking down old PCC/Steel tubular pole in repairs complete all as specified and directed. |
| 28 | PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete all as specified. |
| 29 | PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in pole coping, roof kerbs including necessary form work, complete all as specified and directed. |
| 30 | MCCB, 4 Pole, Adjustable thermal & fixed magnetic, braking capacity 16 KA, 100 Amp complete incl fixing in existing LT panel with necessary arrengment complete all as specified and directed |
| 31 | MCCB, 4 Pole, Adjustable thermal & fixed magnetic, braking capacity 36 KA, 125 Amp complete incl fixing in existing LT panel with necessary arrengment complete in repairs all as specified and directed. |
| 32 | MCCB, 4 Pole, Adjustable thermal & fixed magnetic, braking capacity 36 KA, 160 Amp complete incl fixing in existing LT panel with necessary arrengment in repairs complete all as specified and directed. |
| 33 | MCCB, 4 Pole, Adjustable thermal & fixed magnetic, braking capacity 36 KA, 160 Amp complete incl fixing in existing LT panel with necessary arrengment in repairs complete all as specified and directed. |
| 34 | On load change over switch, 4 pole, capacity 160 Amp with SS enclosure complete including fixing in replacement on wall, open execution type with necessary fixing arrangement complete all as specified and directed. |
| 35 | On load change over switch, 4 pole, capacity 200 Amp with SS enclosure complete including fixing in replacement on wall, open execution type with necessary fixing arrangement complete all as specified and directed. |
| 36 | 40mm bores of tubes 'light grade' galvanised with all fittings and fixed complete with electric pole, laid in trenches for passing of XLPE cable in repairs complete all as specified and directed |
| 37 | Supply, installation, commisining and testing CPRI approved of double door out door type LT switch gear control panel board feeder pillar panel 440 volt AC 3 phase, 4 wire for out door installation\\" KIOSK TYPE\\" with sloping canopy fabricated out of steel sections ie., CRCA sheet 3.15mm thickness, angle/channel and flat iron sections of suitable size with opening on front, door in two halves fitted with handle and bolts for pad lock. The panel door shutters fixed with stainless steel hinges, heavy duty and with door stoppers. The door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard with phosphatised powder coating painting externally and internally to protect against corrosion. The panel shall be mounted on suitable size of channel section having ground clearance 60 cms from grouting bolts, complete foxing with danger notice board with necessary PCC work of 1:2:4 duly incorporated with following accessories |
| 38 | Incommer(a) MCCB 250 Amp,36KA, Four Pole, thermal magnatic released with spreader links-1 No(b) Digital VAF Meter with Volt, Ampere, frequency selecter switch(c) LED Indicator RYB-1 Set(d) CT Coil 100/5 Amp-3 Nos(e) TPN Aluminium bus bar 300 Amp rating capacity.Out going(a) MCCB 125 Amp,4 pole breaking capacity 10 KA-03 NosMCCB 100 Amp 4 pole breaking capacity 10 KA-01 |
| 39 | Supply, installation, commisining and testing CPRI approved of front & back door, out door type LT bus bar panel with TPN aluminium bus bar of capacity 300 Amp with suitable size distance insulator mounted, 440 volt AC 3 phase, 4 wire for out door installation \\"KIOSK TYPE\\" with sloping canopy fabricated out of steel sections Le., CRCA sheet 3.15mm thickness, angle/channel and flat iron sections of suitable size with opening on front, door in two halves fitted with handle and bolts for pad lock. The panel door shutters fixed with stainless steel hinges, heavy duty and with door stoppers. The door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 65 standard with phosphatised powder coating painting externally and internally to protect against corrosion. The panel shall be mounted on suitable size of channel section having ground clearance 60 cms from grouting bolts, complete with necessary PCC work of 1:2:4 duly incorporated with all as directed. |
| 40 | Supply, installation, commisining and testing CPRI approved of double door out door type LT switch gear control panel board feeder pillar panel 440 volt AC 3 phase, 4 wire for out door installation\\" KIOSK TYPE\\" with sloping canopy fabricated out of steel sections ie., CRCA sheet 3.15mm thickness, angle/channel and flat iron sections of suitable size with opening on front, door in two halves fitted with handle and bolts for pad lock. The panel door shutters fixed with stainless steel hinges, heavy duty and with door stoppers. The door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard with phosphatised powder coating painting externally and internally to protect against corrosion. The panel shall be mounted on suitable size of channel section having ground clearance 60 cms from grouting bolts, complete foxing with danger notice board with necessary PCC work of 1:2:4 duly incorporated with following accessories |
| 41 | Incommer(a) MCCB 200 Amp,36KA, Four Pole, thermal magnatic released with spreader links-1 No(b) Digital VAF Meter with Volt, Ampere, frequency selecter switch(c) LED Indicator RYB-1 Set(d) CT Coil 100/5 Amp-3 Nos(e) TPN Aluminium bus bar 300 Amp rating capacity.Out going(a) MCCB 125 Amp,4 pole breaking capacity 25 KA thermal magnatic released with spreader links-1 Nos(b)MCCB 100 Amp 4 pole breaking capacity 25 KA thermal magnatic released with spreader links-01 Nos(c)MCCB 63 Amp, 4 Pole breaking capacity 25 KA thermal magnatic released with spreader links-1 Nos |
| 42 | Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. Clamps, bolts and nuts of aproved size, for Lt, 20x15 cm size complete all as specified and directed. |
| 43 | Stay assembly complete with stay plate bow, stay rod of dia 16 mm and gavanised iron stay wire stranded of size 7/4mm and accessories as shown in electric plate No 1 of SSR Part-I (loop type insulator, stay clamps, excavation and concrete shall be measured separately) in repairs complete all as specified and directed. |
| 44 | Scraping of old paint from two pole structure without removing accessories and preparation of surfaces for repainting. Repainting the poles with one coat of alternative white and black straps of 30 cm each upto 1.5 mtr height using synthetic enamell paint .Repainting the remaining Iron parts i.e. cross arms, supporting angles, XPM jali, clamps, GI bkt etc and steel pole above 1.5 mtr height by applying one coat of alumn paint or PCC pole with snowcem of approved color all as required at site or directed |
| 45 | ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre to centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag, jointing jumpers, etc in repairs complete all as specified and directed. |
| 46 | Shackle type insulators, porcelain, vitreous, brown or green insulator including galvanised mild steel straps, washers, insulators, bolts, washers and nuts, working pressure 1100 votls and size of 100 in height and 115 mm dia in repairs complete all as specified and directed. |
| 47 | Pin type, porcelin, vitreous, white, brown or green insulator, size 100 mm height, 65 mm dia for 1100 volts grade, conforming to IS: 7321-1931, in repairs complete all as specified and as directed. |
| 48 | PVC Spacer 2/4/5 way for LT over head line 1100 V complete all as specified and directed |
| 49 | Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as directed and inclusive of one primer coat, one under coat and one finishing coat of synthetic enamel paint all as specified and directed. |
| 50 | Taking down old unsv street lights of any description and M&L for 60 Watt LED street light fitting made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOP opening seperate driver compartment with IP66 protection and impact resistance of IK07 and making connection with copper flexible cable of suitable size to light fitting fixed, complete all as specified and directed. Please Enable Macros to View BoQ information |