| 1 | Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out in hard and dense soil, complete all as specified and directed. |
| 2 | Returning filling in (soil) including spreading, levelling, watering and well ramming in layers n.exc 25cms thick in any type of soil complete all as specified and directed. |
| 3 | Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed. |
| 4 | M&L for Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cms thick, complete all as specified and directed Note: Punned thickness shall be measured. |
| 5 | M&L for Sub class ‘A brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick including taking out old bricks, complete all as specified and directed. |
| 6 | M&L for demolition of exiting damaged pole canopy and built canopy using Plain cement concrete 1:2:4 ( nominal mix ) type B-1 (using 20 mm graded crushed stone aggregates) as in in lintels upto 1.5m clear span, cills, steps; seismic and other similar ands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs , water troughs and the like including weathering, slightly rounded or chamfered angles and throating, including necessary formwork where required complete all as specified and directed. |
| 7 | S&F in replacement XLPE HT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts (Earthed), grade cross sectional area 95 sqmm 3 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly. |
| 8 | S&F in replacement XLPE HT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts (Earthed), grade cross sectional area 120 sqmm 3 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly. |
| 9 | S&F in replacement drop out lift OFF fuse link HT 11 KV, 400 Amps consisting of channel iron base having 11 KV post type polymer insulators in stack & 2 stack per phase complete with fuse carrier of SRBP tube with heavily tinned non ferrous metal parts and spring loaded phosphor bronze contact complete manufactured as per IS 9385 complete all as specified and directed. Make:- Pactil/ Crompton/ ATLAS |
| 10 | S&F in replacement vertical type air break switch, gang operated, tripple pole, mechanically operated, outdoor type, with all fittings and accessories mounted on and including HT 11 KV polymer insulators and galvanised steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements , suitable for 11000 volts, 200 Amps current rating complete including dismantling existing air break switch all as specified and as directed. |
| 11 | S&F in replacement Structural steel work as in cross arms, bracings, supports, clamp and back plate fabricated from steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed by Engineer-in-Charge and applying two coats of aluminium paint over one coat of red oxide zinc chrome primer including preparation of surfaces and dismantling old structural steel work in cross arms and stacking at site, complete all as specified & directed. |
| 12 | S&F in replacement cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120sqmm including cutting and removing existing unserviceable joint, including earth work complete, near 2 pole structure / HT Panel board / transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed. |
| 13 | S&F in replacement cable jointing end termimation kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120sqmm including cutting and removing existing unserviceable joint, including earth work complete, near 2 pole structure / HT Panel board / transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed. |
| 14 | Renewal of cable jointing end termination kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95sqmm to 120sqmm including cutting and removing existing unserviceable joint, including earth work complete, near 2 pole structure / HT Panel board / transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed. |
| 15 | S&F in repair of pin type insulator porcelain, vitreous, white/brown or green including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm dia and 150mm height for working pressure 11000 volts grade includng taking down existing insulators and removing from site, complete all as specified. |
| 16 | S&F in replacement of disc type insulator, 145 mm height 255 mm dia suitable for 11000 volts HT grade porcelain vitreous white,brown or green including galvanized mild steel sectional straps 38X5mm, insulator bolts dia 20mm, washers and nuts includng taking down existing insulators and removing from site complete all as specified and directed. |
| 17 | S&F in repalcement of lightning arresters (Set of three) expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp for 11000 volts including taking out old unservicable arrester and removing from site complete all as specified and directed. |
| 18 | Supply and laying of hard core broken boulders of guage 40 to 63mm graded stone aggregate including levelling/spreading rolled in E/M Installations complete al as directed by Engr-in-Charge. (Note:- Rates are deemed to be included for bricks reqd for retaining the aggregate) |
| 19 | S&F in replacement Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 80mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed. |
| 20 | S&F in replacement GI pipe light grade with all fittings complete laid in trenches all as specified for 50 mm bore of pipe complete all as specified. Please Enable Macros to View BoQ information |
| 21 | S&F in replacement GI pipe light grade with all fittings complete laid in trenches all as specified for 50 mm bore of pipe complete all as specified. Please Enable Macros to View BoQ information |