| 1 | Supply, Install, Testing and Commissioning in replacement of factory made outdoor type dust and vermin proof (IP 65 protection) feeder Pillar LT Panel board cubicle double door hinged type of suitable size 415V AC, 50Hz, fabricated of GP/CRCA sheet 3.15mm(10 SWG) thick machine pressed complete including 4 Pole aluminum Bus Bar of 200 Amp mounted on porcelain insulator ,concealed hinged door with 3 Positioning door locking arrangement and enclosed in chamber made out of 2mm sheet thick GP/ CRCA sheet machine pressed and connection from incoming and outgoing electric cable with suitable size thimbles/lugs cable gland with open able shutters on both side and comprising of following(i)MCCB 160 Amps 25KA 4pole with microprocessor release adjustable type with spreader link :- 01 (Incoming)(ii) MCCB 160 Amp 36 KA, 4 P, 415V with spreader link and change over switch :- 01 (Incoming)(iii) Aluminium Busbar of 200 Amps phase x 3 +Nutral with insulated(iv) Digital Ammeter 0-200 Amp Digital inbuilt ASS (v) LED indicator lamp Red/yellow/Blue colour (vi) Digital Voltmeter 0-500 Amp Digital inbuilt VSS (vii) one set of CTs 150/5AComplete all as specified and directed |
| 2 | Supply and fixing in replacement of sheet metal enlosure for DBs when MCBs to be used double door factory made flush fixed complete with 200 amps rated bus-bar 240 volts single phase 12 ways including necessary brick work and plaster to match with the existing surface complete all as specified. |
| 3 | S&F in replacement MCBs single pole (SP) 6 to 32 Amps with 10 KA breaking capacity of 'B' series in distribution boards complete all as specified and directed |
| 4 | S&F in replacement MCBs single pole and neutral (SPN) 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed |
| 5 | S&F in replacement MCBs single pole 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed |
| 6 | Supply and fixing in replacement of MCCB 100 Amps , AC 415 Volts 16KA 4 pole,ics=100% icu, Thermal and magnetic adjustable with spreader terminal including making connections with suitable size lugs complete all as specified and directed |
| 7 | Supply and fixing in replacement of MCCB 125 Amps , AC 415 Volts 16KA 4 pole,ics=100% icu, Thermal and magnetic adjustable with spreader terminal including making connections with suitable size lugs all as specified and directed. |
| 8 | Supply and fixing in replacement of sheet steel enclosure distribution boards, double door factory made TPN Vertical 4 way 3 phase 415 volts 4 way with 200 amps rating copper bus bar and PVC insulated copper jumpers of suitable size from the MCCB to the out going circuits one incoming MCCB and 12 outgoing MCBs circuits comprising of 3 phase 4 wire of suitable rating complete all as specified and directed with the following accessories :- (a) MCCB 100 amps, 16 KA, ics=100% icu,thermal and magnetic adjustable with spreader terminal, FP, 415 volts, 50 Hz = 01 No. (Note:- Out going MCB shall be measured and paid for separately) |
| 9 | S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 6.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 6.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed by Engineer in charge Note :-Two Nos of 6.0 Sqmm Wire and one No of 6.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length. |
| 10 | S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 4.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 4.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed by Engineer in charge Note :-Two Nos of 4.0 Sqmm Wire and one No of 4.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length. |
| 11 | Supply and fixing in replacement of security light fitting LED 35 Watt with dusk and dawn sensor aluminium pressure dia cast housing with touched glass cover IP-66 protection complete mounted including connection with 3 core PVC insulated overall sheathed flexible cable with multi-stranded copper conductor of size not less than 1.0 Sqmm from ceiling rose to fitting terminal including taking down old CFL security light fitting all as specified and as directed. |
| 12 | M&L in replacement for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 15 mm bore( light grade) and watering pipe 20 mm bore GI pipe (light grade ) and chamber of pcc 1:4:8 type D2 using 40 mm graded stone aggregate and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PART 1 , with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switche, DBs) complete all as specified & testing on completion. |
| 13 | S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 10.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 10.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed by Engineer in charge Note :-Two Nos of 10.0 Sqmm Wire and one No of 10.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length. |
| 14 | M&L in replacement of single core wiring 6 Sqmm multi-strand PVC insulated copper conductor FRLS cable including connections of cable with MCBs or bus bars complete all as specified and directed. |
| 15 | Supply and fixing of single core wire 1.5 Sqmm multi-strand PVC insulated copper conductor FRLS cable including connections of cable with MCBs or bus bars complete all as specified and directed. |
| 16 | Supply and Laying in replacement in trenches or passing through pipe or fixing to pole/wall UG cable XLPE, of cross section area 50 sqmm 3.5 core, PVC insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade. Note : (I) Earth work/ sand cushioning shall be measured and paid separately . complete all as specified and directed |
| 17 | Excavation in trenches in soft/loose soil n.exc. 1.5mtr wide and n. exc. 1.5mtr in depth and getting out for laying of cables all as specified and directed |
| 18 | Removing excavated material n. exc. 50m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed. |
| 19 | Returning, filling in, and including spreading, levelling,watering and well ramming in layers not exceeding 25 cm thick complete all as specified. |
| 20 | Supply,laying & fixing in replacement double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints,Sockets,Elbows,bends and End caps etc.. all as specified and directed by Engr in Charge of size 63 mm outer dia and 50 mm inner dia |
| 21 | Labour for drilling hole under the road with the help of drilling machine without damaging the road horizonally for rod crossing for cable protection complete all as sp an directed. Please Enable Macros to View BoQ information |