| 1 | Dismantling carefully old unserviceble ACSR conductor from LT OH lines of any size complete all as specified and directed. |
| 2 | Dismantling carefully old unserviceble earth wire LT OH line complete all as specified and directed. |
| 3 | Dismantling of insulators of any type and size complete all as specified and directed. |
| 4 | Supply, laying, jointing, testing and commissioning in replacement LT cable of size 10 sqmm 4 core, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches/ fixed on wall/ floor/ road/ culverts/ pole or encased in GI pipe complete all as specified and directed.Note : Excavation, earth work, sand cushion & brick protection shall be paid separately. |
| 5 | All as per item No 04 above but of size 16 Sqmm 4 core. |
| 6 | All as per item No 04 above but of size 35 Sqmm 3.5 core. |
| 7 | All as per item No 04 above but of size 50 Sqmm 3.5 core. |
| 8 | All as per item No 04 above but of size 95 Sqmm 3.5 core. |
| 9 | All as per item No 04 above but of size 120 Sqmm 3.5 core. |
| 10 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil for laying of cables, GI pipe or filling of earth resistance enhance compound and getting out including levelling of bottom suface to required level complete all as specified and directed. |
| 11 | Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 19430 Part - I of size 50mm outer dia and 38 mm inner dia complete all as specified and as directed. |
| 12 | Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 19430 Part - I of size 110mm outer dia and 90 mm inner dia complete all as specified and as directed. |
| 13 | Returning filling in including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and as directed. |
| 14 | Removing excavated material (i.e. soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed. |
| 15 | M&L for demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and as directed. |
| 16 | M&L for cement concrete type B-2, 1:2:4 (40mm graded aggregate) complete all as specified and as directed. |
| 17 | M&L for boring of hole under road/ pavement/ hard standing or any other situation by mannual means and suitable for passing of GI pipe upto 80 mm bore and making good both ends all specified and directed. |
| 18 | Supply, installation, commissioning and testing of LT Panel , 415 Volts, 50 Hz , 3-phase,4 wire supply, size of LT panel not less than 1.0 m high x 1.5 m width x 0.5 depth, CPRI approved/tested, factory assembled, outdoor type, weather and vermin proof (Protection Class IP-54) made out of 3.15 mm (for external) and 2.00 mm (for internal) thick CRCA sheet with both side (front and back) hinged, double door opening for external, rubber lining, locking arrangement, painted internally and externally with powder coating of grey shade (RAL-7032) as per seven tank process complete mounted on angle iron 50mm x 50mm x 5 mm legs 45 cm high above GL and 15 cm embedded in ground with and including blocks of PCC 1:2:4 type C1 of block size 30x30x30 cm including bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, bus bar must be colour coded heat shrinkable as well as outgoings shall have aluminium four pole (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCB s comprising of the following :- (a) INCOMING :- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 630 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-800 Amp digital type with 3 way rotary selector switch - 01 No (iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOING :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 200 Amps 36 KA - 4 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 25 KA -2 Nos. Notes : (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimbles. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB will adjustable thermal and fixed magnetic, Ics = 100% Icu |
| 19 | All as per item No 18 here-in-before, but size of LT panel not less than 1.0 m high x 1.0 m width x 0.5 m depth and incommer & outgoing as per the following:- (a) INCOMING :- (i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three(v) CT of suitable size class-1 ISI marked - 01 Set of three(b) OUTGOINGS (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 36 KA 63 Amps - 05 No. (III) MCB SPN 63 Amps-04 Nos |
| 20 | All as per item No 18 here-in-before, but of size of LT panel not less than 1.0 m high x 1.0 m width x 0.5 m depth but incommer & outgoing as per the following:- (a) INCOMING :- (i) MCCB 4 pole, LT 415 Volts, 50 Hz AC grade of 200 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-200 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three(v) CT of suitable size class-1 ISI marked - 01 Set of three(b) OUTGOING :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 36 KA 63 Amps - 04 No. (III) MCB TPN 63 Amps-03 Nos |
| 21 | Disconnecting and taking down from poles existing street light fittings of any type or any watt and size and refixing the street light after disconnecting the ACSR conductor complete all as specified and directed. |
| 22 | S&F FRLS PVC insulated and PVC sheathed 1.5 sqmm 3 core multistranded copper conductor cable from street light including PVC wire connectors for making connection complete all as specified and directed. |
| 23 | S&F 20mm rigid non-metallic PVC conduit inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified & directed. |
| 24 | S&F street light bracket made to shape out of GI pipe 32 mm bore light grade, 1.5 meter length fixed complete all as specified and directed. |
| 25 | S&F PVC junction box suitable for street light of size not less than 350mm x 250mm x 150mm, made out of polycarbonate having front side openable shutter duly provided with locking arrangement and provided with 04 Nos aluminium bus bar of rating 200 Amp including neutral terminals alongwith 01 No MCB 6 Amp SP and provision of 02 Nos cable entries of size upto 16 sqmm 4 core, fixed on any type of street light pole with proper size MS clamp with nut & bolt and connected assessories complete all as specified and directed. |
| 26 | M&L for cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps stay clamps, D clamps, nuts, bolts, washers welding bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed. |
| 27 | M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth streep 25x4 mm by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/ Testpoint/ panel/ equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete all as specified & as directed. Please Enable Macros to View BoQ information |