| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Garrison Engineer Kapurthala Name of Work : Repair/ replacment and maintenance of LT switchgears, distribution system and allied works at Mil Stn Beas and jandiala Guru under GE Kapurthala. Contract No : GE KPT- /2026-27 Bidder Name : SCHEDULE OF WORKS(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # S.No Description of work Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Taking down existing LT panel by disconnecting all incoming and outgoing cables, earthing connection, dismantling PCC and making good the disturbed surface all as directed |
| 3 | Supply fabricating erecting LT panel outdoor type CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts 50 cycles, AC supply factory made fully compart mentalized made out of 3.00 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of angle iron/flat iron frame work/ support minium 45 cm required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioning with including the following :- (a) Aluminium bus bar of capacity 400 Amps for Three phase and Neutral. -04 No's(b) Combined Voltmeter 415V, Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three), Indicator lampIncoming :- (i) MCCB 4P 250 Amps, 36 KA 415 Volts (Adjustable- 01 No Outgoing :- (i) MCCB FP 125 Amps 16 KA 415 Volts (adjustable 70% to 100%)- 02 N(ii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No's(iii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder, current capacity 16 Amps |
| 4 | Supply fabricating erecting LT panel outdoor type CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts 50 cycles, AC supply factory made fully compart mentalized made out of 3.14 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of angle iron/flat iron frame work/ support minium 45 cm required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioning with including the following :- (a) Aluminium bus bar of capacity 250 Amps for three phase and Neutral.-04 No's(b) Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three)Incoming :- (i) MCCB TPN 160 Amps, 36 KA 415 Volts - 01 No's Outgoing :- (i) MCCB 4 pole 100 Amps 16 KA 415 Volts - 02 No'(ii) MCCB 4 pole 63 Amps 16 KA, 415 Volts - 02 No's |
| 5 | S&F in replacement factory made power coated vertical DBs TPN 440 Volt 4 way , in double door suitable for flush mounting and surface mounting with 250 Amp copper busbar for each phase with 2 neutral bar, 2 earthbar and cable ties for cable management and fully insulated bus bar and shrounded neutral bus bar with provision of 100-160 Amp FP MCCB as Incommer and SP 6 to 32 Amp and 40 to 63 Amp for outgoing including taking down UNSV DBs complete all as specified and directed. |
| 6 | Taking down old unsv bus bar panel any type and S & F of new aluminium bus bar panel TPN 200 Amp , 415 Volt Complete all as specified and directed. |
| 7 | Taking down old unsv bus bar panel any type and S & F of new aluminium bus bar panel TPN 100 Amp , 415 Volt Complete all as specified and directed. |
| 8 | M&L for earthing complete with galvanized iron or steel or steel earth plate electrode of size 60cmx60cmx6.3mm thick buried directly in ground, vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI Strip of size 32x6 mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe light grade 20 mm bore for watering including providing funnel and wire mesh GI frame and 10 cm thick suitably reinforced RCC pit cover PCC chamber pit with PCC 1:3:6 type C2 using 40mm graded stone aggregates complete including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in plate No 5 of SRR-1991 Part-1 . |
| 9 | M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. |
| 10 | M&L for preparation to steel surface of existing LT panels, LT feeder pillars boxes of any size and description internally and externally after scraping and scratching the old paint with emery paper etc, and painting with two coat of gray painting with spray gun and writing feeder names and numbers with suitable capital letters in English with white paint on and a black paint strip of size 20 cm x 25 cm all as directed. |
| 11 | M&L for repair to LT panels feeder pillar box by dismantling old rusted and perished doors shutter and bus bar covers etc and providing new doors shutters, bus bar cover etc by cutting, welding, fabricating and made to existing shape with 3.15 mm plain black sheet and angle iron of required size including providing hinges and locking arrangement all as directed including M&L for two coat of painting with synthetic enameled Grey paint over a coat of red oxide primer. |
| 12 | S&F in replacement MCCB, 4 pole, 3 phase, 415 volts, 400 Amps, repturing capacity 35 KA with overload and thermal tripping features all as specified. |
| 13 | - ditti - all as per item No 11 here-in-before but 250 Amps repuring capacity 36 KA. |
| 14 | - ditti - all as per item No 11 here-in-before but 200 Amps repuring capacity 25 KA. |
| 15 | - ditti - all as per item No 11 here-in-before but TPN 160 Amps repuring capacity 25 KA. |
| 16 | - ditti - all as per item No 11 here-in-before but TPN 125 Amps repuring capacity 16 KA. |
| 17 | - ditti - all as per item No 11 here-in-before but TPN 25 to 100 Amps repuring capacity 16 KA. |
| 18 | S&F in repair on load change over switch 4 pole 400 Amps in sheet metal enclosure all as specified and directed |
| 19 | S&F in repair on load change over switch 4 pole 200 Amps in sheet metal enclosure all as specified and directed |
| 20 | S&F of aluminum thimbles/Lugs crimping type of size 16 to 25 Sq mm |
| 21 | S&F of aluminum thimbles/Lugs crimping type of size 50 to 120 Sq mm |
| 22 | S&F of aluminum thimbles crimping type of size 150 Sq mm to 240 Sq mm all as specified. |
| 23 | M&L for straight through joint (epoxy) for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testing size 185 to 240 Sqmm, 3.5 core |
| 24 | - ditti - all as per item No 22 here-in-before but cable size 120 to 150 Sqmm, 3.5 core |
| 25 | - ditti - all as per item No 22 here-in-before but cable size 70 to 95 Sqmm, 3.5 core |
| 26 | - ditti - all as per item No 22 here-in-before but cable size 25 to 50 Sqmm, 3.5 core |
| 27 | - ditti - all as per item No 22 here-in-before but cable size 10 to 16 Sqmm, 4.0/2.0 core |
| 28 | Dismantling & taking down existing ACSR conductor of any size by opening the binding wire from HT/LT electric poles complete all as specified. Note ACSR conductors wil be replaced with LT UG cable item no 27 to 35 where applicable or as directed. |
| 29 | Supply, stringing and fixing on existing poles, ACSR conductor of any type/ size including fixing to insulators with binding wire complete all as directed by Engr-in- Charge. |
| 30 | Taking out old defective underground cable from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including segregating the serviceable cable by cutting down defective portion after testing by meggar and relaying.Note :- Excavation and earth work will be measured separately under respective item. |
| 31 | Taking out old defective underground cable from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including segregating the serviceable cable by cutting down defective portion after testing by meggar.(Approx 700 is reduced for old ACSR where required.) |
| 32 | Supply, Laying, jointing and testing XLPE PVC insulated & PVC sheathed LT cable, 1100 volts grade (heavy duty )with stranded aluminium conductor, cross sectional area 10 Sqmm 2 core fixed along the poles or passing through pipes or laid under floors or through walls complete all as specified. Note:- Earthwork, sand cushioning, brick protection and GI pipe to be measured and paid for separately under respective items. |
| 33 | - ditti - all as per item No 31 here-in-before but cross sectional area 16 Sqmm 2 core complete all specified. |
| 34 | - ditti - all as per item No 31 here-in-before butt cross sectional area 16 Sqmm 4 core complete all specified. |
| 35 | - ditti - all as per item No 31 here-in-before but cross sectional area 25 Sqmm 3½ core complete all specified. |
| 36 | - ditti - all as per item No 31 here-in-before but cross sectional area 35 Sqmm 3½ core complete all specified. |
| 37 | - ditti - all as per item No 31 here-in-before but cross sectional area 50 Sqmm 3½ core complete all specified. |
| 38 | - ditti - all as per item No 31 here-in-before but cross sectional area 70 Sqmm 3½ core complete all specified. |
| 39 | - ditti - all as per item No 31 here-in-before but cross sectional area 95 Sqmm 3½ core complete all specified. |
| 40 | - ditti - all as per item No 31 here-in-before but cross sectional area 120 Sqmm 3½ core complete all specified. |
| 41 | - ditti - all as per item No 31 here-in-before but cross sectional area 150 Sqmm 3½ core complete all specified. |
| 42 | - ditti - all as per item No 31 here-in-before but cross sectional area 185 Sqmm 3½ core complete all specified. |
| 43 | Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and getting out including trimming of sides complete all as specified and directed by Engineer-in-Charge. |
| 44 | Returing, filling in, including spreading, leveling watering and well ramming inlayers not exceeding 25 cms thick each layer compete all as specified and directed. |
| 45 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge. |
| 46 | M&L for sand cushioning with a layer of sand 8cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. |
| 47 | Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-charge. (for LT Cable ) |
| 48 | M&L for road cutting for laying of LT UG cable /Galvanised Iron Pipe/Rex Pipe complete all as specified |
| 49 | M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate for fdn of poles, stay etc. |
| 50 | M&L for PCC 1:3:6 type C1 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement. |
| 51 | M&L for PCC 1:2:6 type B1 using 12.5mm graded for padestal coping incl necessary formwork finished fair using extra cement. |
| 52 | S&F in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified for 50mm dia |
| 53 | S&F in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified for 80mm dia |
| 54 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting at side for re-use with in 50m |
| 55 | M&L for mild steel cross arms,bracing,supports,clamps and back plates fabricated from structural steel section including nuts,bolts washers,welding,bending cold or hot, drilling holes for bolts in any shape/size as directed including painting with two coats of approved colour over a coat red oxide primer all as specified and directed by Engr-in-Charge |
| 56 | Dismantling stay assembly complete. (demolition of concrete, etc. and excavationmeasured separately) |
| 57 | M&L for stay assembly with accessories in replacement as shown in electrical plate No.1 complete with diameter of rod 20 mm. Note:- loop type insulator, stay clamps, excavation and concrete will be measured and paid separately. |
| 58 | M&L for galvanised stay strand size 7/4 mm complete all as specified and directed. |
| 59 | Taking down insulators off any size & type. |
| 60 | S&F of pin type, porcelain,vitreous,white brown or green insulator including one galvnised mild steel spindle, two nos galvanised iron washer and one galvnised iron nut, 100mm height,65mm dia for 1100v grade |
| 61 | S&F of shackle, porcelain,vitreous,white brown or green insulator including galvnised mild steel straps, washers,insulator, bolts, washers and nuts for size 100mm height and 115mm dia for working pressure 1100 Volts |
| 62 | M&L for dismantling of the existing old rusted Steel/RCC poles of any type and size |
| 63 | Supply and install in replacement of steel tubular swaged poles type 410 SP-31 (9 mtr long) complete with CI base plate and finial taper plug,bolts, nuts and screws as specified all as directed.Note :- Excavation, earth & PCC work only will be measured separetely all other accessories and work deemed to be included in quoted rates. |
| 64 | M&L for painting to steel tublar poles 9 m long with one coat of Synthetic enamel paint black/yellow combination Zebra marking up to 1 m from ground level /copping remaining Job portion painting with one coat of aluminium paint including preparation of old painted surfaces and painting the pole terminal etc. all as specified and as directed. |
| 65 | M&L for painting cement poles with one coat of cement based paint black/yellow combination Zebra marking up to 1 m from ground level /copping remaining Job including preparation of old painted surfaces and painting the pole terminal etc. all as specified and as directed. |
| 66 | S&F of volt meter 0-15KV with PT, digital type, suitable for LT panel 415V, as in replacement, complete all as specfied and directed. |
| 67 | S&F of ammeter, digital type, 200/5Amps & 100/5Amps, suitable for for LT panel 415V, as in replacement, complete all as specified and directed. |
| 68 | S&F ofnalog time switch 3 module of capacity 32A, suitable for LT panel 415V, complete all as specfied and directed. |
| 69 | S&F of modular contactor 3 module of capacity 16-40A alongwith add on block suitable for LT panel 415V, complete all as specfied and directed. |
| 70 | Cutting the tree branches which touches the LT OH lines and 2.5 m away from centre line of LT OH line span not exceeding 60mts distance between poles by using necessory T&P items and depositing the tree branches/leaves at 30m distance away from the site. Note:- Any number of tree branches cut in one span will be measured as one length for payment pupose Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |