Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | AUCTION HALL AND WHARF AREA |
| 2 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 3 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 4 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 5 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 6 | 90.12.24.1:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.2.5 sq mm |
| 7 | 90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm |
| 8 | 90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm |
| 9 | 1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm |
| 10 | 1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm |
| 11 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 12 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 13 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 14 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 15 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 16 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 17 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 18 | 1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module |
| 19 | 1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 20 | 1.28.3:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module |
| 21 | 1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module |
| 22 | 90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface |
| 23 | 90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 24 | 90.10.1.4:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )4 module moulded plastic box on surface |
| 25 | 90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface |
| 26 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 27 | 2.19:Supplying and fixing 20 A,415volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 28 | OD766/2026-2027:Supply ,Installation, testing and commissioning of pre - wired, weather proof LED luminaire IP65 rated having power consumption of 34 /40 W and light output not less than 2100 lm with system efficiency >120 lumens/watt. Luminaire housing made from superior quality of polycarbonate extrusion IP65 and and IK 08 protection. The luminaire should be having minimum 30000 Burning hours with CRI >=80 and co related colour temperature(CCT)of 6500K. of all types, complete with all accessories etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 29 | OD767/2026-2027:Supply and installation of 9W LED Lamp complete. |
| 30 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 31 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 32 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 33 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 34 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 35 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 36 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 37 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 38 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 39 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 40 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 41 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat |
| 42 | OD759/2026-2027:Supply and installation of thermoplastic circuit breker boxes IP65 with metrick knock out for cable entry, including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. with PE+N terminals fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. complete as required 3 row 36 module size 400 x 333 x 129 or nearest suitable size . |
| 43 | OD760/2026-2027:Supply and fixing Cable Junction Boxes IP 65 for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm nearest suitable size and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required |
| 44 | OD768/2026-2027:Supply and installation of Cable termination box wall mounting cubicle type dust and vermin proof size 4 , 315x600x214 mm, hinged lid thermoplastic box including Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL including Supply and fixing rotary handle ,including BUC handle with door interlock for the MCCB , including giving connection using suitable rated pvc insulated copper wire, and supply and installation of 2A SPMCB -3nos with RYB indication lamp -set interconnection the circuit with 2.5 sqmm copper wire complete as required. |
| 45 | OD942/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)- |
| 46 | OD943/2026-2027:Supply Conveyance, installation, testing and commissioning of 150 W LED Flood light output greater than 130lumen/W 5700 K with IP 66 protection, IK 08, with power factor greater than 0.95 at full load, internal surge protection up to 4 KV, and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be separately accessible for maintenance. complete as required |
| 47 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 48 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 49 | 90.12.5.30:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 70 sq mm |
| 50 | 90.12.7.30:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm |
| 51 | 7.9:Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
| 52 | 9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm) |
| 53 | 14.13.2:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required80 mm dia |
| 54 | 90.12.9.5:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench90/75 mm or nearest size |
| 55 | 14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. |
| 56 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 57 | OD801/2026-2027:Supply and fixing 3mtr long tubular pole made out of 50 mm Diameter (Class B) GI pipe with ISI Mark, on roof slab by using flange and muffings 0.3x.3x.3m near to the column, clamping the pipe to the RCC column using MS clamps made out of 25x5 mm MS flat and anchor bolts, filling the space between slab and pole using PCC 1:11/2:3 (M20), constructing muffing of size 30 cmx30cmx30cm in M20 mix. The top of the pole must be closed with Table E MS flange and dummy flange, bolted with stainless steel nut and bolts and it must have an inverted Y arrangement using 25mm Gl medium pipe 10cm long welded to the pole 10 cm below the top flange to take outgoing wire. The tubular post shall be painted with two coats of epoxy primer and epoxy paint of approved make and colour. |
| 58 | OD802/2026-2027:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of Vertical TPN DB - IP65, Weather proof Polycarbonate , dust protected, , inclusive of 125 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MMCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 Way including all accessories complete as required. |
| 59 | 90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 60 | OD803/2026-2027:Supplying and fixing following way, MCB distribution board, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, with PE+N terminals, thermoplastic circuit breaker boxes IP65 with metric knock out for cable entry, 1 row 18 module size 400 x 333 x 129 or nearest suitable size with PE+N terminals including earthing etc. as required. (But without MCB/RCCB/Isolator) 1 row 18 module with PE+N terminals complete . |
| 61 | OD825/2026-2027:Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required |
| 62 | GATE HOUSE |
| 63 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 64 | 1.10.2:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group B |
| 65 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 66 | 1.11:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 67 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 68 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 69 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 70 | 90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm |
| 71 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 72 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 73 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 74 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 75 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 76 | 7.9:Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
| 77 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 78 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 79 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 80 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 81 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 82 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 83 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 84 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 85 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 86 | 1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 87 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 88 | OD954/2026-2027:Supplying and fixing following way, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, with PE+N terminals, thermoplastic circuit breaker boxes IP65 with metric knock out for cable entry, 1 row 12 module size 295x333x129 or nearest suitable size with PE+N terminals including earthing etc. as required. (But without MCB/RCCB/Isolator) 1 row 12 module with PE+N terminals complete as required. |
| 89 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 90 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 91 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 92 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 93 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 94 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 95 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 96 | 5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 97 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 98 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 99 | 14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 100 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 101 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 102 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 103 | OD945/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip make with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)-. complete as required. |
| 104 | OD944/2026-2027:Supply Conveyance, installation, testing and commissioning of 100 W LED Flood light output greater than 130lumen/W 5700 K with IP 66 protection, IK 07, with power factor greater than 0.95 at full load, internal surge protection up to 4 KV, and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be separately accessible for maintenance.complete as required. |
| 105 | OD433/2026-2027:Supply and installation of 2x6 W bidirectional symmetrical light beam up and down rectangular outdoor decorative wall light having 2700 K warm white polycarbonate body with Aluminium housing IP54 rated fixture suitable for outdoor applications. The fixture should have 2 year warranty and surge protection up to 2.5 KV including with fixing accessories complete as required. |
| 106 | OD437/2026-2027:Supply and installation of LED Bulk Head fitting 10W with Aluminum die-cast housing and polycarbonate optic materials including connection, fixing etc complete as required. The luminaire shall have IP66 protection, luminous flux 1100 lm, luminous efficiency 110 lumens/watt, cool daylight colour and 6500k colour temperature .complete as required. |
| 107 | 90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 108 | 90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp |
| 109 | 90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 110 | 9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 111 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 112 | 90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm |
| 113 | 90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm |
| 114 | OD814/2026-2027:Supply and providing Electric Shock Treatment Chart Standard Size 600 x 450 mm have in bilingual format (English and Malayalam). It must be laminated or framed to prevent damage from humidity and oil fumes and fixed in a conspicuous location for clear vision including all fixing accessories complete as required. |
| 115 | OD815/2026-2027:Supply and providing 4Kg, IS 15683 mark ,stored pressure ABC Powder type Fire Extinguisher with hose and clamps including all fixing accessories and fixing it to wall as directed by Department officials complete as required. |
| 116 | OD816/2026-2027:Supply and providing 2.5 mm thick,1m x 2m Synthetic polymer/PVC blend electrical grade Checkered type rubber mat suitable for Medium Voltage installations have IS 15652:2006 Standard ,Class B,Dielectric Strength of 45 kV AC for 1 minute,Self-extinguishing,Anti-skid checkered or dotted top surface and plain at bottom at site complete as required. |
| 117 | OD817/2026-2027:Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required |
| 118 | OD818/2026-2027:Painting letters or figure of following sizes with enamel paint as identification mark to SB,DB,panel board etc as required. 2.50 cm, 4 cm or 5cm height. |
| 119 | OD820/2026-2027:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of Vertical TPN DB - IP65, Weather proof Polycarbonate , dust protected, , inclusive of 125 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MMCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 Way including all accessories complete as required. |
| 120 | 90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 121 | OD821/2026-2027:Supply of 9-Watts Multipack B22 LED Cool Day White LED Bulb. |
| 122 | OD822/2026-2027:Supplying and fixing 2A rating, c curve 240/415 volts, 10 kA, miniature circuit breaker suitable for protection of meter control and auxiliary circuit having following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 123 | OD823/2026-2027:Supply and fixing of Panel mounting type LED Indication lamp R ,Y, B with Multi-chip technology for uniform brightness made of Polycarbonate material ,with a diameter of 22.5mm cut out ,operating voltage of 230V AC 50Hz ,IP65, Screw-type terminals for secure wire connection ,50,000 burning hours .complete as required. |
| 124 | OD824/2026-2027:Supply and fixing Cable Junction Boxes IP 65 weather proof type for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm , ,80 X 80X 52 mm and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No, including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required . |
| 125 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat |
| 126 | OD831/2026-2027:Supply and installation of wall mounting control cubicle enclosure Glass Fibre Reinforced Polyester IP66 ,1K 10 with hinged door 600 X 400 X 230 mm with supply and fixing of upto160A, 35kA,4P,MCCB 1 NO With BUC rotary drive kit, inter connection using suitable rated cable/wire and sockets . Necessary holes are to be provided in the box for entry and exit of wire and and have the provision for sealing the box etc with all fixing accessories complete as required. |
| 127 | OD832/2026-2027:Supply and installation of wall mounting cubicle type dust and vermin proof 900 x 400 x 200 mm Glass Fibre Reinforced Polyester Enclosure with hinged door, IP66, IK 10 outdoor meter box or equivalent with base plate for fixing of CT type KSEB meter, cut out &Neutral link and with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 3 No 200A HRC fuse units with 160A HRC fuse link and 1No 200A 2way neutral link in the meter portion. Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using suitable size cable complete as required. |
| 128 | OD833/2026-2027:Supply Installation testing and commissioning of (SMDB) Sub Main Distribution board of OEM withMCCB as incomer and MCCB as out going. Supply installation testing and commissioning of wall mount following type(SMDB) Sub Main Distribution board Conforms to IEC 61439-2 DEKRA and ASTA certified have Short-time withstand current » 250A at 36 kA 1s , IP 43 having 8 number of outgoing ways Ready to use, including suitable cable Metering Extension Box ,Bottom Cabling Box, Corner Box, Mounting base and Side Cabling Box etc accessories complete as required. The sub main distribution board have Incomer 160A 35kA 4P MCCB-1no ,Outgoing 100A, 35kA 4P MCCB-2 Nos ,63 A, 35kA 4P MCCB-4 no, 50A, 35kA 4P MCCB-2Nos including metering block side 1Ph LED Ammeter Cl 1-3 nos with suitable CT ,1Ph LED voltmeter Cl 1-1 nos ,selector switch -1 no. Indication lamp RYB -1set top bottom cover and corner box including all fixing accessories complete as directed by the Engineer in charge at site |
| 129 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 130 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 131 | OD439/2026-2027:Providing and fixing 12 SWG insulated GI wire for service wire binding along with service line complete with all accessories complete as required. |
| 132 | OD813/2026-2027:KSEB documentation charge for new connection including preparation of essential drawing file wire submission of application arrangement for getting connection (Remitting statutory fees at KSEB will be paid separately by submitting Invoice in original) etc complete for new connection and work at site complete as required. |
| 133 | DUPLEX SHOP ROOM |
| 134 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 135 | OD784/2026-2027:Supply and installation of LED type Bulk Head fitting 10W with Aluminium die-cast housing and polycarbonate optic materials including connection etc as required. The luminaire shall have IP66 protection, luminous flux 1100 lm, luminous efficiency 110 lumens/watt, cool daylight colour and 6500k colour temperature including connection complete as required. |
| 136 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 137 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 138 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 139 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 140 | 1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 141 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 142 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 143 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 144 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 145 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 146 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 147 | 1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 148 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 149 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 150 | 1.49:Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required. |
| 151 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 152 | OD783/2026-2027:Supply of 9-Watts Multipack B22 LED Cool Day White LED Bulb. |
| 153 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 154 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 155 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 156 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 157 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 158 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 159 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 160 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 161 | OD921/2026-2027:Supplying and fixing following way, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, with PE+N terminals, thermoplastic circuit breaker boxes IP65 with metric knock out for cable entry, 1 row 12 module 295x333x129 or nearest suitable size with PE+N terminals including earthing etc. as required. (But without MCB/RCCB/Isolator) 1 row 12 module with PE+N terminals complete as required. |
| 162 | 90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 163 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 164 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 165 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 166 | OD924/2026-2027:Supply and installation of wall mounting cubicle type Control cubicle enclosure Glass Fibre Reinforced Polyester IP66 ,1K 10 with hinged lid door Size 3 box with high lid 300 x 450 x 214 or nearest suitable size with supply and fixing of 16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL- 1 NO With BUC rotary drive kit, inter connection using suitable rated cable/wire and sockets . Necessary holes are to be provided in the box for entry and exit of wire and and have the provision for sealing the box for KSEB etc with all fixing accessories complete as required. |
| 167 | OD785/2026-2027:Supply and installation of wall mounting cubicle type metering board made of thermoplastic polycarbonate energy meter enclosure with hinged lid 600 x 400 x 230 mm , IP66 IK10 with base plate for fixing KSEB meter, cut out & Neutral link and 32A , 10kA DP MCB, C curve , with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 1No 32A,10kA ,DP MCB C curve ,-1 No 32A HRC fuse units with 32A HRC fuse link - 1No 32A 2way neutral link in the meter portion-1No . Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using 4sq.mm copper wire complete as required at site . |
| 168 | OD923/2026-2027:Supply and installation of wall mounting cubicle type dust and vermin proof Size 4 box with high lid 315 x 600 x 214 or nearest suitable size in wall with all fixing accessories and cutting holes for bus bar arrangement and enclosure locking or sealing arrangement provision must be provided . The enclosure must have the provision for integrating with other enclosures including all fixing accessories complete as required. |
| 169 | OD955/2026-2027:Supply and installation of wall mounting cubicle type dust and vermin proof Size 2 box with high lid 300 x 300 x 214 or nearest suitable size in wall with all fixing accessories and cutting holes for bus bar arrangement and enclosure locking or sealing arrangement provision must be provided . The enclosure must have the provision for integrating with other enclosures including all fixing accessories complete as required. |
| 170 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 171 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 172 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 173 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat |
| 174 | OD782/2026-2027:Providing and fixing 12 SWG insulated GI wire for service wire binding along with service linecomplete with all accessories complete as required. |
| 175 | OD781/2026-2027:KSEB documentation charge for new connection including preparation of essential drawing file wire submission of application arrangement for paying fees etc complete for new connection at site complete as required. |
| 176 | TOILET BLOCK |
| 177 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 178 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 179 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 180 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 181 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 182 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 183 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 184 | 1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 185 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 186 | 1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 187 | 1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 188 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 189 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 190 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 191 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 192 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 193 | OD956/2026-2027:Supplying and fixing following way, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, with PE+N terminals, thermoplastic circuit breaker boxes IP65 with metric knock out for cable entry, 1 row 12 module size 295x333x129 or nearest suitable size with PE+N terminals including earthing etc. as required. (But without MCB/RCCB/Isolator) 1 row 12 module with PE+N terminals complete as required. |
| 194 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 195 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 196 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 197 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 198 | OD946/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip make ree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) complete as required. |
| 199 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 200 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 201 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat |
| 202 | 90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 203 | OD792/2026-2027:Supplying, installing, testing and commissioning of 300 mm (12 inch) sweep, 1400 RPM, 230V, single phase, AC medium duty/industrial propeller type exhaust fan fitted with statically and dynamically balanced metal blades, complete with automatic louvers/shutters, galvanized bird-mesh protection guard, mounting frame/sleeve, rawl plugs, anchor bolts, grouting layout finishing, connections with 3-core flexible copper cable and loop earthing the body complete as required. |
| 204 | OD925/2026-2027:Supply and installation of LED type Bulk Head fitting 10W with Aluminium die-cast housing and polycarbonate optic materials including connection etc as required. The luminaire shall have IP66 protection, luminous flux 1100 lm, luminous efficiency 110 lumens/watt, cool daylight colour and 6500k colour temperature including connection complete as required. |
| 205 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 206 | 90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 207 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 208 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 209 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 210 | OD793/2026-2027:Supply and installation of wall mounting cubicle type metering board made of thermoplastic polycarbonate energy meter enclosure with hinged lid 600 x 400 x 230 mm , IP66 IK10 with base plate for fixing KSEB meter, cut out & Neutral link and 32A , 10kA DP MCB, C curve , with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 1No 32A,10kA ,DP MCB C curve ,-1 No 32A HRC fuse units with 32A HRC fuse link - 1No 32A 2way neutral link in the meter portion-1No . Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using 4sq.mm copper wire complete as required at site . |
| 211 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 212 | OD791/2026-2027:Providing and fixing 12 SWG insulated GI wire for service wire binding along with service linecomplete with all accessories complete as required. |
| 213 | OD835/2026-2027:KSEB documentation charge for new connection including preparation of essential drawing file wire submission of application arrangement for paying fees etc complete for new connection at site complete as required. |
| 214 | NETMENDING SHED |
| 215 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 216 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 217 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 218 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 219 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 220 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 221 | 1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 222 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 223 | OD774/2026-2027:Supplying and fixing following way, MCB distribution board, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, with PE+N terminals, thermoplastic circuit breaker boxes IP65 with metric knock out for cable entry, 1 row 18 module size 400 x 333 x 129 or nearest suitable size with PE+N terminals including earthing etc. as required. (But without MCB/RCCB/Isolator) 1 row 18 module with PE+N terminals complete. |
| 224 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 225 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 226 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 227 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 228 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 229 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 230 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 231 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 232 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 233 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 234 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 235 | 90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 236 | 90.10.1.4:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )4 module moulded plastic box on surface |
| 237 | 90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface |
| 238 | 90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface |
| 239 | 90.12.41.35:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 240 | 90.12.5.42:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm |
| 241 | 9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 242 | 90.12.9.3:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench63/50 mm or nearest size |
| 243 | 14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. |
| 244 | 7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 245 | OD773/2026-2027:supply Installation testing and commissioning of weather proof LED luminaire having power consumption not more than 36/ 40 W and light output not less than 4500 lm with system efficiency >120 lumens/watt. Luminaire housing made from superior quality of polycarbonate extrusion IP65 and and IK 08 protection. The luminaire should be having minimum 30000 Burning hours with CRI >=80 and co related colour temperature(CCT)of 6500K. complete as required. |
| 246 | OD947/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)- complete as required. |
| 247 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 248 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat |
| 249 | OD772/2026-2027:Supply and installation of Cable termination box wall mounting cubicle type dust and vermin proof size 4 , 315x600x214 mm, or neaest suitable size hinged lid thermoplastic box or equivalent including Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL including Supply and fixing rotary handle ,including BUC handle with door interlock for the MCCB , including giving connection using suitable rated pvc insulated copper wire, and supply and installation of 2A SPMCB -3nos with RYB indication lamp -set interconnection the circuit with 2.5 sqmm copper wire complete as required. |
| 250 | OD771/2026-2027:Supply and fixing Cable Junction Boxes IP 65 weather proof type for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No, Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required .complete as required. |
| 251 | OD927/2026-2027:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of Vertical TPN DB - IP65, Weather proof Polycarbonate , dust protected, , inclusive of 125 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MMCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 Way including all accessories complete as required. |
| 252 | 90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 253 | 90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm |
| 254 | YARD LIGHTING |
| 255 | OD949/2026-2027:Supply Conveyance, installation, testing and commissioning of 200 W LED Flood light output greater than 130 lumen/W 5700 K with IP 66 protection, IK 07, with power factor greater than 0.95 at full load, internal surge protection up to 4 KV, and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant and including SPD , duly wired up for use on 230 V AC supply . Driver compartment should be separately accessible for maintenance . |
| 256 | OD911/2026-2027:Supply and installation of Mast foot box of wall mounting cubicle type thermoplastic polycarbonate with hinged lid 315x 450 x 170 mm size-3 box IP65 with base plate for fixing RCCB and MCB and suitable connectors for upto 16 sqmm aluminum cable 2nos including din rail ,Terminals: 35 sq.mm Channel-mounted Elmex Connectors4 Nos,.interconnection using 2.5sqmm cu wire of suitable length complete as required . the box must have the din rail for accommodating RCCB ,isolator and MCB .The mast foot box excluding RCCB and MCB as required. Necessary holes are to be provided in the box for entry and exit of cable. The inter connection should be done using 2.5sq.mm copper wire complete as required. |
| 257 | 90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm |
| 258 | OD912/2026-2027:Supply and fixing Cable Junction Boxes IP 65 for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm or nearest suitable size and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required |
| 259 | 2.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole |
| 260 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 261 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 262 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 263 | 5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 264 | 5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 265 | 5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required. |
| 266 | 5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 267 | 90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG) |
| 268 | OD914/2026-2027:Supply and installing RCC precast well steining of size 750mm dia and 300m height complete with all expense at site as required. |
| 269 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). |
| 270 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 271 | 90.12.5.42:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm |
| 272 | 90.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm |
| 273 | 90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm |
| 274 | 90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 275 | 90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 276 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 277 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 278 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 279 | 9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 280 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 281 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 282 | 7.9:Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
| 283 | 14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia |
| 284 | 90.15.3.5:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x12 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc. complete 7 Meters |
| 285 | 90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm |
| 286 | OD948/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)- complete as required. |
| 287 | 5.1:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 288 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 289 | OD915/2026-2027:Supply and installation of extra length of foundation bolt of size 16mm diameter 200mm pitch circle diameter manufactured from special steel ( suitable for 10 M octogonal pole) in existing cement concrete complete as required. |
| 290 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 291 | OD930/2026-2027:Scaffolding Charges for mounting the flood light fixture in existing street light pole upto a length upto 15 mtr from ground level. The charges including hire charge, transportation, loading, unloading and all expense complete as required. |
| 292 | OD932/2026-2027:Engaged Labour for maintenance work for dismounting/fixing the existing light fittings, cables and other electrical accessories from the existing poles upto 12 meter including rectifying minor defects, tightening nut and bolts ,overall check-up, change the cable and welding and fabrication work for minor defects including materials complete as directed by engineer in charge at site including all maintenance work complete as required. |
| 293 | CIVIL WORK |
| 294 | 5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars |
| 295 | 7.5:Extra for random rubble masonry with hard stone curved on plan for a mean radius not exceeding 6 m. |
| 296 | 15.2.1:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) |
| 297 | 15.3:Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge. |
| 298 | 13.52.1:Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail