| 1 | Dismantling of the existing 50 KVA E/A set from the existing i/c dismantling the exhaust pipe, silencer, cabling, control panel, fuel tank, earthing connections and keeping the E/A set & shifting to Main TE Bldg from narow approch road of distance approximately 30 mtrs as required. | Dismantling of the existing 50 KVA E/A set from the existing i/c dismantling the exhaust pipe, silencer, cabling, control panel, fuel tank, earthing connections and keeping the E/A set & shifting to Main TE Bldg from narow approch road of distance approximately 30 mtrs as required. |
| 2 | Dismantaling the above faulty alternator (Make- Crompton greaves , Model- NoG2R00SB /G2R50/43) of above 50 KVA EA set , loading into vehicle at TE Londha, transporting to work shop at Belgaon & return to site & unloading at TE. Londha, and fixing to 50 KVA EA set i/c alignment etc. complete as required. | Dismantaling the above faulty alternator (Make- Crompton greaves , Model- NoG2R00SB /G2R50/43) of above 50 KVA EA set , loading into vehicle at TE Londha, transporting to work shop at Belgaon & return to site & unloading at TE. Londha, and fixing to 50 KVA EA set i/c alignment etc. complete as required. |
| 3 | Rewinding of Faulty alternator (Make- Crompton greaves , Model- NoG2R00SB/G2R50/43) of capacity 50 KVA capacity 3 phase icluding rewinding of main rotor, stator,exciter rotor, replacement of rectifier diodes varnishing the same , drying it remove the moisture etc as complete as required. | Rewinding of Faulty alternator (Make- Crompton greaves , Model- NoG2R00SB/G2R50/43) of capacity 50 KVA capacity 3 phase icluding rewinding of main rotor, stator,exciter rotor, replacement of rectifier diodes varnishing the same , drying it remove the moisture etc as complete as required. |
| 4 | Supplying & fixing new AVR suitable for above 50 KVA 3 phase Alternator etc as required. | Supplying & fixing new AVR suitable for above 50 KVA 3 phase Alternator etc as required. |
| 5 | ITC of the shifted 50 KVA E/A set ,control panel with the existing diesel tank, fixing of silencer, making fuel pipe connections i/c making necessary alterartions required as per site condition,testing of EA set on exchange load for 30 minutes, recording of all important parameters etc complete as required. | ITC of the shifted 50 KVA E/A set ,control panel with the existing diesel tank, fixing of silencer, making fuel pipe connections i/c making necessary alterartions required as per site condition,testing of EA set on exchange load for 30 minutes, recording of all important parameters etc complete as required. |
| 6 | Carrying out B check of 50 KVA EA set i/c replacement of Lub oil of 15w/40 rating, replacament of fuel filters, Lub oil filters , cleaning of fuel tanks , harnessing of control panel wiring, cleaning of EA set etc complete as required | Carrying out B check of 50 KVA EA set i/c replacement of Lub oil of 15w/40 rating, replacament of fuel filters, Lub oil filters , cleaning of fuel tanks , harnessing of control panel wiring, cleaning of EA set etc complete as required |
| 7 | Extension of Earthings (Neutral & Body from Existing shed to new place or nearest location) with 25 mm X 3 mm G.I. strip etc as reqd. | Extension of Earthings (Neutral & Body from Existing shed to new place or nearest location) with 25 mm X 3 mm G.I. strip etc as reqd. |
| 8 | S/L of 3.5 Core x 35 Sq.mm PVC insulated PVC sheathed Al conductor XLPE armoured UG Cable of 1.1KV grade on surface / recess etc complete as required | S/L of 3.5 Core x 35 Sq.mm PVC insulated PVC sheathed Al conductor XLPE armoured UG Cable of 1.1KV grade on surface / recess etc complete as required |
| 9 | Supplying and making end termination with brass compression gland and aluminium lugs for 3.5X50 size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | Supplying and making end termination with brass compression gland and aluminium lugs for 3.5X50 size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |