| 1 | Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Grundfos/ Kirloskar / BE / Maxflow / Beaconweir Sabar make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB & suitable for operation on 415 (+/-) 10% volts 50 cycle per second 3 phase AC electric supply conforming to BIS 900- 1972 and IS:12615:2011 with IE-2 specifications, 2900 RPM (latest upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :- |
| 2 | Discharge(Q) = 11.07 LPS for each pump |
| 3 | Total Dynamic heads:- 435 Meter |
| 4 | LWL in sump well(h) 1719 Meter |
| 5 | Shaft Level 1718 Meter |
| 6 | Level at Discharge point 2138 Meter |
| 7 | Suction Lift '+ve |
| 8 | Discharge Head 420 Meter |
| 9 | Static head 420 Meter |
| 10 | Rising Main |
| 11 | Length 1100 Meter |
| 12 | Dia 125 mm |
| 13 | Pumping Hours 8 Hours |
| 14 | Altitude of installation above MSL 1718 Meter |
| 15 | Characterstics of water Clear Water with turbidity up to 5 PPM |
| 16 | Temperature 25 degree centigrade |
| 17 | Supply , Installation, Testing and Commissioning of Star Delta Starter panel for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 1 Nos. pumps (1 working & 0 stand bye) each of the rating 125 HP through Star Delta Starter mechanism. Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators.Make: JSV ApprovedQuantity =1. No |
| 18 | Star Delta and Mains Power Contacts of required ratings as per type-2 co-ordination for 125 HP starterQuantity= 1 Set |
| 19 | Voltage Protection device to protect panel from over voltage and under voltage Quantity= 1 no |
| 20 | Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage.Quantity= 1 no |
| 21 | Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make :- JSV Approved.Quantity= 1 no |
| 22 | Main incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).Quantity= 1 no |
| 23 | Individual Starter incomer MCCB/MCB of suitable capacity of L&T / Schnieder/ ABB make on the feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).Quantity= 1 no |
| 24 | LED three phase indicating lamps complete with toggled switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.Quantity= 1 set |
| 25 | LED On / Off & Trip indicator and push buttons, Control and power wiring, Power capacitor,Cooling fan 230 VAC, Control terminal, Bus Bar, i.e.Bolt, insulator, etc.Quantity= 1 set |
| 26 | Actuated Gate Valve at delievery of each pumpQuantity= 1 no |
| 27 | Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.Quantity= 1 no |
| 28 | Control Transformer to provide a stable control volatge to safegaurd the control circuit of all the components from the voltage surges and spikes.Quantity= 1 no |
| 29 | Independent control panel with switch Fuse unit and fuse of suitable amperage to eliminate the kitkat fuses of HPSEB make Siemens/ Schnieder/ L&T.Quantity= 1 set |
| 30 | Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amnmendments)Quantity= 1 No |
| 31 | Providing double flanged cast steel sluice valve, ASA-300 of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses make and one step higher then delivery line of pump and capable of withstanding normal seat pressure 52 kg cmsq as per BIS standards with upto date amnmendments)Quantity= 1 no |
| 32 | Providing double flanged cast steel reflux valves class, ASA-300 of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses make for rising main and capable of withstanding normal seat pressure 52 kg cmsq as per BIS standards with upto date amnmendments)Quantity= 1 no |
| 33 | Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments. Quantity= 1 no |
| 34 | Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.Quantity= 1 no |
| 35 | Installation of all the items apparing as per the schematic drawing.Quantity= 1 job |
| 36 | Providing and laying copper PVC insulated armoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest with upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/ NATIONAL/ GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. |
| 37 | Motor side 3 core (From switch to starter and starter to motor)Quantity= 10 Rmt |
| 38 | Supply side 3.5 core (From Meter of HPSEB to bus bar and switch)Quantity= 10 Rmt |
| 39 | Providing and fixing double loop earthing with GI plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.Quantity= 1 Job |
| 40 | Providing, laying, jointing (by way of circumfrential butt welded joints in three layers by electrical arc welding) andtesting of API/ MSERW pipe of following dia meters confirming to ISO 3183-2012, (latest with upto date amendments) havingwall thickness and grade as specified below with bevelled ends and capable of withstanding required test pressure in a random length of 4 to 7 meters, including manufacturing reducers / tapers , all short pieces, beds etc. as per siterequirement made from parent tubes . The laying of pipe shall include all operation such as cutting, welding, jointing,fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. Thefabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipes shallbe factory galvanized (zinc coating both inside and outside) as per IS:4736-1986 (with upto date ammendments) withmass og Zinc Coating as per relevant IS Code. |
| 41 | 125mm dia -API/MSERW pipe 6.60mm thick |
| 42 | Excavation in foundations, trenches etc. in earth work, lift up to 1.50 mtrs. stacking the excavated soil not more than 3 mtrs. clear from the as of excavation and then returning the excavated soil in 15 cm. layers when required into plinths sides of foundations etc., consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated soil as directed within a lead of 20 mtrs.- P-J Work. complete in all respect including all leads and lifts and to the Entire Satisfaction of the Engineer-in-Charge. |
| 43 | Providing Form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm so as to give a fair finish including centring , shuttering, strutting & propping etc. with wooden battens & ballies, height of propping & centring below supporting floor to ceiling not exceeding 4 mtrs.& removal of the same for insitu reinforced concrete & plain concrete work in. Vertical surfaces such as walls (any thickness) partitions and the like including attached pillasters, buttresses,plinth and string courses and the like. |
| 44 | Providing and laying cement concrete 1:3:6 (1cement:3sand:6graded stone agg.20mm nominal size) and curing complete excluding cost of form work in :- a) Foundation and plinth. |
| 45 | Providing and laying cement concrete work 1:1.5:3(1cement:1.5 sand:3 graded stone agg. 20mm nominal size) and curing complete excluding cost of form work and reinforcement for reinforced concrete work in:- Fondations footings bases of columns and mass concrete. |
| 46 | Providing mild steel/Tor steel reinforcement for RCC work including bending, binding and placing in position complete in all respect including all leads and lifts and to the Entire Satisfaction of the Engineer-in-Charge. Please Enable Macros to View BoQ information |