| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth, for laying LT under ground cables/ GI pipes and getting out in soft/loose soil, complete all as specified and directed. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in soft/loose soil, complete all as specified and directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed |
| 4 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 25 sqmm 4 core. |
| 5 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 35 sqmm 3.5 core. |
| 6 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 50 sqmm 3.5 core. |
| 7 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 70 sqmm 3.5 core. |
| 8 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 95 sqmm 3.5 core. |
| 9 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 120 sqmm 3.5 core. |
| 10 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 185 sqmm 3.5 core. |
| 11 | Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed armoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable cable for 240 sqmm 3.5 core. |
| 12 | Note for item 4.00 to 11.00: Earth work, excavation, DWC pipes, GI pipe etc shall be measured separately under relevant items of this schedule. |
| 13 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core / 4 core, 25 to 35 sqmm. |
| 14 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 50 sqmm. |
| 15 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 70 sqmm. |
| 16 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 95 sqmm. |
| 17 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 120 to 150 sqmm. |
| 18 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 185 sqmm. |
| 19 | M&L in repair for heat shrinkable straight-through joint for LT underground cable including jointing kit complete for making joints, suitable for aluminium conductor cable of size 3.5 core, 240 sqmm. |
| 20 | Note for item no 12.00 to 18.00: Earth work, DWC pipes GI pipe etc shall be measured separately under relevant items of this schedule. |
| 21 | M&L in repair MCCB, 3-pole, 415 volts, 25 to 100 amps, with a breaking capacity of 16 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of ICU, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 22 | M&L in repair MCCB, 3-pole, 415 volts, 125 amps, with a breaking capacity of 16 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 23 | M&L in repair MCCB, 3-pole, 415 volts, 160 amps, with a breaking capacity of 25 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 24 | M&L in repair MCCB, 3-pole, 415 volts, 200 amps, with a breaking capacity of 25 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 25 | M&L in repair MCCB, 3-pole, 415 volts, 250 amps, with a breaking capacity of 36 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 26 | M&L in repair MCCB, 3-pole, 415 volts, 400 amps, with a breaking capacity of 36 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 27 | M&L in repair MCCB, 3-pole, 415 volts, 630 amps, with a breaking capacity of 50 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 28 | M&L in repair MCCB, 4-pole, 415 volts, 100 amps, with a breaking capacity of 16 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 29 | M&L in repair MCCB, 4-pole, 415 volts, 125 amps, with a breaking capacity of 16 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 30 | M&L in repair MCCB, 4-pole, 415 volts, 160 amps, with a breaking capacity of 25 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 31 | M&L in repair MCCB, 4-pole, 415 volts, 200 amps, with a breaking capacity of 25 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 32 | M&L in repair MCCB, 4-pole, 415 volts, 250 amps, with a breaking capacity of 36 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 33 | M&L in repair MCCB, 4-pole, 415 volts, 400 amps, with a breaking capacity of 36 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 34 | M&L in repair MCCB, 4-pole, 415 volts, 630 amps, with a breaking capacity of 50 kA, thermal magnetic release, and adjustable settings from 80% to 100%, with ICS = 100% of Icu, fixing to the existing panel board, matching the existing slots, including any required alterations, and with extension links properly connected to the busbar. The work includes disconnecting the incoming and outgoing cable connections and reconnecting them using suitable aluminium lugs/ferrules, after taking out the existing unserviceable unit and making good the disturbed surface. |
| 35 | M&L in repair for servicing indoor/outdoor LT panel board by opening all cubicle doors, cleaning with air blower, removing burnt/unserviceable instruments, copper wiring kit and extended copper terminals/ copper cable, and replacing with new copper extended terminal bus bars of suitable size with nuts, bolts and washers; replacement of measuring instruments such as ammeter with existing size of the CT, voltmeter, and LED type indicating lamps ‘RYB’; cleaning of serviceable parts such as MCCBs and terminals with CTC; replacement of damaged aluminium lugs of any description for LT underground cables (incoming/outgoing), replacement of deteriorated copper wiring with suitable copper conductor including circuit indicator, replacement of sheared rubber beadings for panel doors; preparing existing surface and spray painting to powder coated surface with two coats of synthetic enamel paint over red oxide primer of approved colour by airless spray technology (maximum working pressure of 3300 PSI) ; marking incoming/outgoing feeders with fluorescent stickers including preparation of the surface of panel, complete all as specified and directed. |
| 36 | Notes for item no.33:(i) The unit rate quoted shall be deemed to include cleaning with CTC oil, termination of LT UG cables any description, copper wiring kits with suitable copper conductor along with connector, painting, and marking with Incoming & Outgoings details of the panels with fluorescent stickers and necessary bolt, nut and washers etc.(ii) Spare parts such as aluminium lugs, sheared rubber gaskets of panel doors, indicator lamps, voltmeters, ammeters (with CTs), selector switches, copper conductors (other than wiring kits) shall be measured and paid separately under relevant items as “Supply only”. |
| 37 | Supply only the following items:-Volt meter digital type 0-500 Volts |
| 38 | Ammeter digital type suitable to 0 - 100 Amps |
| 39 | Aluminium lugs suitable for 25 sqmm to 50 sqmm cables |
| 40 | Aluminium lugs suitable for 70 sqmm to 150 sqmm cables |
| 41 | Aluminium lugs suitable for 150 to 300 sqmm cables |
| 42 | Sheared rubber gasket suitable to LT panel board of any description |
| 43 | Indicator lamp LED type 'RYB' |
| 44 | GI tubing 'Light' grade 50 mm bore with all fittings for cable protection fixed on poles/walls/laid under roads crossing etc and made good the disturbed surfaces/area. |
| 45 | GI tubing 'Light' grade 80 mm bore with all fittings for cable protection fixed on poles/walls/laid under roads crossing etc and made good the disturbed surfaces/area. |
| 46 | GI tubing 'Light' grade 100 mm bore with all fittings for cable protection fixed on poles/walls/laid under roads crossing etc and made good the disturbed surfaces/area. |
| 47 | M&L in repair for earthing complete with galvanized steel earth plate electrode 600 mm × 600 mm × 6 mm thick, buried vertically in ground not less than 2.25 m deep, with top edge of plate not less than 1.5 m below normal ground level, connected to galvanized iron earth strip 32 × 6 mm size, by means of galvanized bolts, nuts and washers, and 32mmx6mm earth lead protected by provision of GI medium grade pipe 40mm bore including provision 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40mmx40mmx6mm with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, common salt and charcoal filling, 15 CM alternate layer of charcoal and salt around all sides of earth plate with fixing arrangements, funnel, wire mesh and earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre complete all as per plate No 03 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Please Enable Macros to View BoQ information |
| 48 | M&L in repair for earthing complete with galvanized steel earth plate electrode 600 mm × 600 mm × 6 mm thick, buried vertically in ground not less than 2.25 m deep, with top edge of plate not less than 1.5 m below normal ground level, connected to galvanized iron earth strip 32 × 6 mm size, by means of galvanized bolts, nuts and washers, and 32mmx6mm earth lead protected by provision of GI medium grade pipe 40mm bore including provision 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40mmx40mmx6mm with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, common salt and charcoal filling, 15 CM alternate layer of charcoal and salt around all sides of earth plate with fixing arrangements, funnel, wire mesh and earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre complete all as per plate No 03 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Please Enable Macros to View BoQ information |