| 1 | Taking out unservicable street light / security light/ flood light/ post top light fitting complete from different locations and heights, walls of building/poles of any type, sizes, makes, model after disconnecting the electrical connections and refixing after replacement of defective items including replacement of defective wiring, cleaning of acrylic cover/ diffusers, replacement of unservicable screws and nuts complete all as required and directed. Note:- Replacement of defective items shall be measured and paid seprately. |
| 2 | Supply & Fixing in replacement of high energy efficent constant current electronic driver suitable for 230v, 50hz, LED street light fitting 60-72 Watts LED luminaires complete all as specified and directed. |
| 3 | Supply & Fixing in replacement of high energy efficent constant current electronic driver suitable for 230v, 50hz, LED street light fitting 90-150 Watts LED luminaires complete all as specified and directed. |
| 4 | S&F in replacement loop-in-loop out fuse junction (SMC) box of internal dimension 240 x 130 x 110 mm made out of FRP sheet and locking screw fitted with and incl 0.5 Amps MCB - 1 No, 20 Amps rated 4 way connectors for 3 phase and neutral incoming/ out going, mounted in the box, fixing on any type of poles including necessary clamps, suitable glands, Connector, lugs, GI nut and bolts complete all as specified and directed.Make : Sintex/ Hensel/National |
| 5 | All as per item No. 4 but of size 140 x 140 x 95 mm |
| 6 | S&F in repair GI bracket made out of GI pipe 32 mm bore light grade bent to required shape of 1.20 mtr long and fixing to pole/wall with suitable size of nut, bolts and clamps including painting with two coats of aluminium paint over a coat of red oxide primer after preparation of surface complete all as specified and directed. Note :- MS articles such as clamp, nut, bolts etc. will be measured and paid seperately under respective item. |
| 7 | S&F in replacement LED street light fitting 70/72 Watts, having pressure die cast aluminium alloy housing with high power LED as lightning source and lens embedded PC cover having top opening seperately including Driver having IP-66 protection, including surge protection device 5 KV and making electrical connection to the fitting with Suitable size of service wire complete as as directed.Make- Crompton CRP-409-70-57-SL-GL-NSG/ Havells Cat no: ENDURASUNDOWNNXT SL70WLEDCWPASYBOPC/ Bajaj ZELA P 86L WH PO TG SD JNote :- Connection cable will be measured and paid seperately under respective item |
| 8 | S&F in replacement LED street light fitting 90 Watts, having pressure die cast aluminium alloy housing with high power LED as lightning source and lens embedded PC cover having top opening seperately including Driver having IP-66 protection and making electrical connection to the fitting with Suitable size of service wire complete as as directed.Make- Crompton CRP-411-90-57-SL-GL-NSG/ Havells Cat no: ENDURASUNDOWNNXT SL90WLEDCWPASYBOPC/ Bajaj ZELA P 108L WH PO TG SD Note :- Connection cable will be measured and paid seperately under respective item |
| 9 | S&F in replacement LED street light fitting 120 Watts, having pressure die cast aluminium alloy housing with high power LED as lightning source and lens embedded PC cover having top opening seperately including Driver having IP-66 protection and making electrical connection to the fitting with Suitable size of service wire complete as as directed.Make- Crompton CRP-411-120-57-SL-GL-NSG/ Havells Cat no: ENDURASUNDOWNNXT SL120WLEDCWPASYBOPC/ Bajaj ZELA P 144L WH PO TG SD Note :- Connection cable will be measured and paid seperately under respective item |
| 10 | S&F in replacement LED flood light fitting 120 Watts, IP 66, having pressure die cast aluminium alloy housing with high power LED as lightning source and lens embedded PC cover having top opening seperately including Driver having IP-66 protection and making electrical connection to the fitting with Suitable size of service wire complete as as directed.Make- Crompton CFS-504-120-57-60D-SL-GL-NSG/ Havells Cat no: JETALEGANZAFLS120WLED757P60DTOTG/ Bajaj PRAZE F 168L WH NB-A5 TG SD Note :- Connection cable will be measured and paid seperately under respective item |
| 11 | S&F in replacement LED flood light fitting 200/210 Watts, IP 66, having pressure die cast aluminium alloy housing with high power LED as lightning source and lens embedded PC cover having top opening seperately including Driver having IP-66 protection and making electrical connection to the fitting with Suitable size of service wire complete as as directed.Make- Crompton LFLN-200-CDL/60-M/ Havells Cat no: JETALEGANZAFLS200WLED757P60DTOTG/ Bajaj PRAZE F 280L WH NB-A5 TG SD Note :- Connection cable will be measured and paid seperately under respective item |
| 12 | S&F PVC sheathed 1100 V grade two core multistranded aluminium conductor of size 4 sqmm including PVC conduit pipe 20 mm of size complete all as specified. |
| 13 | Supply and fix Prestressed concrete pole, 9.0 metres long, 102 mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10 incl dismantling old UNSV pole of any type complete all as specified and directed |
| 14 | Taking down existing MS articles and S&F new Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including applying of two coats of aluminium paint over a coat of red oxide primer complete all as directed. |
| 15 | S&L in replacement XLPE LT UG cable PVC insulated, bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 35 Sqmm 3.5 core including gland, lugs etc. laid in trenches or fixed on wall/floor/poles complete all as specified and directed. |
| 16 | S&L in replacement XLPE LT UG cable PVC insulated, bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 16 Sqmm 4 core including gland, lugs etc. laid in trenches or fixed on wall/floor/poles complete all as specified and directed. |
| 17 | S&L in replacement XLPE LT UG cable PVC insulated, bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 10 Sqmm 4 core including gland, lugs etc. laid in trenches or fixed on wall/floor/poles complete all as specified and directed. |
| 18 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep in hard/dense soil for foundation, etc. or for laying of pipe line/ cable etc. n exc 10 sqm on plan and getting out complete all as specified and as directed. |
| 19 | Excavation in trenches in soft/disintegrated rock, n exc 1.5 m wide and n exc 1.5m in depth; for foundation, etc. or for laying of pipe line/ cable etc. n exc 10 sqm on plan and getting out complete all as specified and as directed. |
| 20 | Returning filling in including spreading watering and well raming in layer excedding 25 cm each in any type of soil/rock complete all as specified and directed. |
| 21 | Removing excavated material (Soils/rock) to a distance not exceeding 50 m and depositing where directed at a level n.exc. 1.5 m above the starting point complete all as specified and directed. |
| 22 | Supply & laying double walled corrugated (DWC) HDPE full rounded pipe conforming to IS 16205 Pt-24 of approved colour complete with fittings for cable protection of size 50 mm inner dia and 63 mm outer dia complete all as directed. |
| 23 | M&L for earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised iron Wire 4.0 mm dia by means of bolts, nuts check nuts and washers of galvanised iron or steel connected to earthing test point all as specified incl 15 mm GI tubing medium grade and necessary fitting for protection of GI wire incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5 mm graded stone aggregate reinforced with 6 mm dia round bar @ 75 mm C/C both ways with MS handle 8 mm dia, plastering 15 mm thick CM (1:6) externally upto 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl. excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR (2009) and connected to earth test point incl testing complete all as specified an directed.Note:- The unit rate includes the cost of GI pipe medium grade for protection of earth wire and 4mm dia earh lead wire upto 7.5 M. |
| 24 | Supply and fixing in replacement of existing old un-serviceable Earth continuity conductor of size 25 x 4 mm GI strip fixed to wall and batton or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other situation for loop earthing etc. complete all as specified and directed. |
| 25 | M&L for replacement of GI tubing light grade 80 mm bore for passing through cables laid under the floor, along the wall or along the pole complete all as specified and directed . Please Enable Macros to View BoQ information |
| 26 | M&L for replacement of GI tubing light grade 80 mm bore for passing through cables laid under the floor, along the wall or along the pole complete all as specified and directed . Please Enable Macros to View BoQ information |