| 1 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 300 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 2 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 240 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 3 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 185 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 4 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 150 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 5 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 120 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 6 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 95 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 7 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 70 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 8 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 50 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 9 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 35 sqmm, 3.5 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 10 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 25 sqmm, 4.0 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 11 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 16 sqmm, 4.0 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge. |
| 12 | Supply, laying & testing of XLPE insulated, armoured with galvanized wire or galvanized steel strip, heavy duty LT power cable, with stranded aluminium conductor, 1100 volts grade, of size 16 sqmm, 2.0 core, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete all as specified and as directed by Engineer-in-charge.Note for Srl item No. 1.00 to 12.00:Excavation & Earthwork, cable protection etc. shall be measured and paid for separately. |
| 13 | M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick, buried directly in ground vertically to a depth not less than 2.25 metres deep below ground level with top edge of plate not less than 1.5 metre below normal gound level, connected to galvanized iron strip of size 32 x 6 mm dia bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3, connected to test point including testing complete including necessary excavation and earth work in any type of soil, PCC 1:3:6 type C-1 chamber, Cast Iron pit cover and frame, charcoal, salt, funnel, GI watering pipe 20 mm dia (medium grade), protection pipe 40 mm dia GI pipe (light grade) of length upto test point complete all as directed by Engineer-in-Charge. |
| 14 | Note: (i) If desirable earthing result not obtained, Earthing shall be re-done without any extra charge until required earth resistance obtained. (ii) The unit rate includes for protection pipe 40 mm dia and GI strip from top of the earth plate upto 7.5 metre length. |
| 15 | M&L for Earthing complete with and including galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick, surrounded by mixture of charcoal and salt in alternate layers, buried directly in ground vertically in a pit of depth not less than 2.25 metre deep below ground level with top as of the plate at a depth of not less than 1.5 metres below normal ground level connected to galvanized iron or steel earth lead wire 4.0 mm dia (8 SWG) by means of bolts, nuts, check nuts and washers of galvanised iron or steel earth wire protected by galvanised steel pipe 15 mm bore (light grade) and connected to main switch or main control board all as shown in electrical plate No. 3 of SSR - 2009 (Part I) & including necessary excavation and earth work in any type of soil. The rate also include charcoal and salt in alternate layers, 20 mm bore GI pipe (Medium grade) for watering, protection pipe funnel, wire mesh, PCC 1:2:4, type B-1 chamber, 50 mm thick precast RCC M-25 (Normal mix) cover duly reinforced with XPM (weight not less than 3 kg /sqm) and CI frame etc., and including provision of test point connecting to test point and testing on completion etc., complete all as specified and as directed by Engineer-in-Charge. |
| 16 | Note: (i) If desirable earthing result not obtained, Earthing shall be re-done without any extra charge until required earth resistance obtained.(ii) The unit rate includes for protecton pipe 15mm and GI earth strip 4mm from top of earth plate upto 7.50 metre above ground level. |
| 17 | M&L for cable route indicator made of cast iron plate, circular type, cable route indicator for HT 11 KV cable of size 10 cm (4\\") dia Cast Iron Round plate not less than 2.5 mm thick marked \\"MES LT cable\\" with arrow sign including stand made out of angle iron 45 (equal angle) and 45 cm long duly welded or bolted and grouted in ground with PCC 1:3:6 block including earth work as required complete all as specified and directed by Engineer-in-Charge. |
| 18 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 375 Amps capacity each including supply and fixing of following switchgears:-(Location: 57 Office Main Gate) |
| 19 | Incoming:(a) MCCB, 400 Amps, 4 pole, breaking capacity 35 KA, 415 Volts, with adjustable thermal and magnetic release – 01 Nos(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No(d) LED Indicator lamp in three colour RYB - 03 Nos |
| 20 | Outgoing(a) MCCB 250 Amps, 4 Pole, 25 KA, 415 Volts with adjustable thermal and magnetic release - 01 No. (b) MCCB 200 Amps, 4 Pole, 25 KA, 415 Volts, with adjustable thermal and magnetic release - 01 Nos. (c) MCCB 40 Amps, 4 Pole, 25 KA, 415 Volts, with adjustable thermal and magnetic release - 01 Nos.(d) Street Light Controller having digital timer - 01 Nos(e) Selector switch for manual and automatic operation - Each circuit having 01 Nos of 3 phase circuit (f) 100 Amp three phase contactor - 01 Nos(g) MCB, SP, 6-32 Amps, 240 V - 03 Nos |
| 21 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof cubical type fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 375 Amps capacity each including supply and fixing of following switchgears:-(Location: OTM 9) |
| 22 | Incoming(a) MCCB 200 Amps, 4 pole, breaking capacity 35 KA, 415 Volts, with adjustable thermal and magnetic release – 01 No(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No(d) LED Indicator lamp in three colour RYB - 03 NosOutgoing(a) MCCB 125 Amps, 4 Pole, 25 KA, 415 Volts with adjustable thermal and magnetic release - 01 No.(b) MCCB 40 Amps, 4 Pole, 25 KA, 415 Volts, with adjustable thermal and magnetic release -04 Nos. |
| 23 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof, cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 375 Amps capacity each including supply and fixing of following switchgears:-(Location: OTM 10) |
| 24 | Incoming(a) MCCB 125 Amps, 4 pole, ultimate breaking capacity 35 KA 415 Volts– 01 Nos.(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No(d) LED Indicator lamp in three colour RYB - 03 NosOutgoing(a) MCCB 40 Amps 4 Pole, 25 KA, 415 V - 04 Nos. |
| 25 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof, cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 200 Amps capacity each including supply and fixing of following switchgears:-(Location: Front 57 Offr Mess Gate) |
| 26 | Incoming(a) MCCB 630 Amps, 4 pole, ultimate breaking capacity 35 KA, 415 Volts - 01 No (b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No (c) Digital Volt Meter 0-500 Volts with selector switch - 01 No(d) LED Indicator lamp in three colour RYB - 03 NosOutgoing(a) MCCB 300 Amps 4 Pole, 25 KA, 415 V - 01 No.(b) MCCB 160 Amps 4 Pole, 25 KA, 415 V - 02 Nos.(c) MCCB 40 Amps 4 Pole,25 KA, 415 V - 01 No.(d) MCB DP 40 Amp 240 V - 01 No |
| 27 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof, cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 200 Amps capacity each including supply and fixing of following switchgears:-(Location: Near Bldg No T48) |
| 28 | Incoming(a) MCCB 300 Amps, 4 pole, ultimate breaking capacity 35 KA 415 Volts - 01 No.(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No.(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No.(d) LED Indicator lamp in three colour RYB - 03 Nos |
| 29 | Outgoing(a) MCCB 160 Amps, 4 Pole, 25 KA, 415 V - 01 No. (b) MCCB 40 Amps, 4 Pole, 25 KA, 415 V - 03 Nos. (c) MCB, DP, 40 Amp, 240 V - 05 Nos. (d) Street Light Controller having digital timer - 01 No(e) Selector switch for manual and automatic operation - Each cIrcuit having 01 Nos of 3 phase circuit(f) Power Contactor 100 Amp, three phase - 01 No.(g) MCB 16 Amps, 240 V, SP - 03 Nos |
| 30 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof, cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 200 Amps capacity each including supply and fixing of following switchgears:-(Location: Mandir) |
| 31 | Incoming:(a) MCCB 160 Amps ,4 pole, ultimate breaking capacity 35 KA 415 Volts - 01 No.(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No.(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No.(d) LED Indicator lamp in three colour RYB - 03 NosOutgoing:(a) MCCB 40 Amps, 4 Pole, 25 KA, 415 V - 04 Nos. |
| 32 | Supply, installation, testing and commissioning LT Panel, 3 phase and neutral, 415 volts, outdoor type, factory made, CPRI approved, free standing, floor mounted, dust and vermin proof, cubical type, fabricated from 3.15 mm thick CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), fully compartmentalized design with 4 Nos of aluminium bus bar with colour code of 200 Amps capacity each including supply and fixing of following switchgears:-(Location: Near JCO Line) |
| 33 | Incoming:(a) MCCB 160 Amps, 4 pole, ultimate breaking capacity 35 KA, 415 Volts - 01 Nos(b) Digital Ammeter 0-300 Amps CT Operated with selector switch - 01 No.(c) Digital Volt Meter 0-500 Volts with selector switch - 01 No.(d) LED Indicator lamp in three colour RYB - 03 Nos.Outgoing(a) MCCB 40 Amps, 4 Pole, 25 KA, 415 V - 05 Nos. |
| 34 | Supply, installation, commissioning and testing of feeder pillar box, outdoor type, kiosk type, CPRI approved LT (415 Volts, 50 Hz, 3 - Phase, 4 wire supply), floor mounted, factory assembled, double door weather and vermin proof made out of 3.15 mm thick CRCA sheet double door type openable from front and rear side, rubber lining, locking arrangement, painted externally and internally with power coated paint (first quality) complete mounted on MS channel of minimum size 75 x 40 mm including under mention items in independent compartment with sufficient working space complete all as spacified and directed by Engineer-in-Charge :-(i) Aluminium bus bar 375 Amps Capacity - 01 set (04 Nos) (ii) MCCB, 4 Pole, 415 V, 35KA, 250 Amps - 01 No (iii) Ammeter 0-400 Amps with selector switch -01 No(iv) Voltmeter 0-500V With selector switch - 01 No(v) Indicator lamps with control fush - 01 set (Each set of three) |
| 35 | Note for Srl item No. 16.00 to 23.00:(i) All MCCBs, instruments, MCBs, bus bar shall be housed in a separate housing with on-off latches in the housing.(ii) Space for provision of one extra MCCB should be provided in the panel. Panel should be installed in such a way that base of the panel is 45 cm above ground level. (iii) All MCCBs have ICS equals to 100% IC. Panel shall conform to IS 61439-1 and 2, up-to-date including IP-65 ingress protection. (iv) Panel shall be got manufactured from OEM only. No third-party approval shall be given. (v) Drawing of LT panel shall be got approved from GE. |
| 36 | S&F steel water tubing, galvanised, light grade, ISI marked, 80 mm bore with and including all fittings fixed to walls and ceilings or laid in floors complete all as specified and as directed by Engineer-in-Charge. |
| 37 | S&F steel water tubing, galvanised, light grade, ISI marked, 50 mm bore with and including all fittings fixed to walls and ceilings or laid in floors complete all as specified and as directed by Engineer-in-Charge. |
| 38 | S&F steel water tubing, galvanised, light grade, ISI marked, 40 mm bore with and including all fittings fixed to walls and ceilings or laid in floors complete all as specified and as directed by Engineer-in-Charge. |
| 39 | Supplying & fixing HDPE double walled corrugated (DWC) duct pipe of 110 mm outer dia conforming to IS-14930 (Part-II) of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge. |
| 40 | Supplying & fixing HDPE double walled corrugated (DWC) duct pipe of 75 mm outer dia conforming to IS-14930 (Part-II) of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge. |
| 41 | Supplying & fixing HDPE double walled corrugated (DWC) duct pipe of 50 mm outer dia conforming to IS-14930 (Part-II) of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge. |
| 42 | Supplying & fixing HDPE double walled corrugated (DWC) duct pipe of 40 mm outer dia conforming to IS-14930 (Part-II) of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge. |
| 43 | S&F PVC insulated flexible copper cable of size 2.5 Sqmm (nominal area), 3 core, FRLS, for connection of street light wherever required at site and as directed by Engineer-in-charge. |
| 44 | Demolition of un-reinforced concrete in ground floor and paving not exceeding 15 cm thickness complete all as specified and as directed by Engineer-in-Charge. |
| 45 | Excavating in trenches in soft/ loose soil, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth, for foundation, or for shafts, wells, cess pits, manholes, pier holes, laying of pipe/ cable etc., not exceeding 10 sqm on plan and getting out complete all as specified and as directed by Engineer-in-Charge. |
| 46 | All as per serial item No. 33.00 here-in-before but depth exceeding 1.5 metre and not exceeding 3.0 metre complete all as specified and as directed by Engineer-in-Charge. |
| 47 | Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick, filling back in trenches after cables have been laid and tested, complete all as specified and as directed by Engineer-in-Charge. |
| 48 | Removing of surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above starting point complete all as specified and as directed by Engineer-in-Charge. |
| 49 | S&F security light mounting bracket made out of 32 mm bore GI 'Medium grade' pipe 1.50 metre long bent to required shape as in bracket for street light fittings fixed with two pair of MS flat iron clamp of size 40 mm X 5 mm thickness of required shape with nuts, bolts and washers of suitable size and fixed to steel tubular pole including painting of bracket surface with two coats of aliminium paint over a coat of primer including taking out existing unserviceable rusted GI bracket complete all as specified and as directed by Engineer-in-Charge. |
| 50 | Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP–31), 9 metre long, complete with cast iron base plate, pole cap/ finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal welded throughout entire length of pole with and including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole finished with two coats of aluminium paint over a coat of primer and providing 30 cm wide alternate black and yellow strips up to 1.50 metre from GL complete all as specified and as directed by Engineer-in-charge.Note- Excavation, earth work and PCC shall be measured and paid separately under relevant items. |
| 51 | S&F energy saving LED street light, 60 watt luminaire with high power LEDs with lens of beam angle of 120 degree, luminaire made of pressure die cast aluminium body with built in heat sinks, painted with polyurethene/ powder coated paint, enclosed with toughened glass including separate compartment for cable and including sealed/ compact driver for easy access during maintenance, suitable for operating on voltage 120 - 270 volt, AC 50 HZ, with inbuilt surge protection device having maximum discharge surge current (Imax) - 10 kA (8/ 20 µs), Nominal discharge surge current (In) - 5kA (8/20 µs) and protection level (Up) upto 10 kv, output luminous efficacy not less then 110 Lumen/ Watt, CRI more then 70, conforming to IP-66, class 1 complete all as per manufacturer's specifications including taking down old unserviceable fittings of any size/ wattage complete all as directed by Engineer-in-Charge. |
| 52 | M&L for PCC 1:4:8, type D-2 (using 40 mm graded crushed stone aggregate) for foundation of poles complete all as specified and as directed by Engineer-in-Charge. |
| 53 | M&L for PCC 1:3:6, type C-1 (using 20 mm graded stone aggregate) for coping of poles including necessary form work complete all as specified and as directed by Engineer-in-Charge. |
| 54 | Supply and fix street light Junction box, 3 phase of PVC including MCB 10 Amp with clamps, nuts & blots and making connetion complete all as specified and as directed by Engineer-in-charge. |
| 55 | Dismantling and taking down of insulators of any type any size from its own position from existing pole structures, over head lines complete all as specified and as directed by Engineer-in-charge. |
| 56 | Dismantling of old unsv ACSR or AAC conductors, any size complete all as specified and as directed by Engineer-in-charge. |
| 57 | Dismantling & taking down earth wire, service feeder or distributor span from poles complete all as specified and as directed by Engineer-in-charge. |
| 58 | Dismantiling and taking down old/ rusted cross arms of MS channel or angle sections etc complete all as specified and as directed by Engineer-in-charge. |
| 59 | Taking out old unsv RCC Poles, any type or size complete all as specified and as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |