| 1 | Supply, Instalaltion, Testing and comissioning of following configuration 415V, 3-phase, 4 wire, double door,with R Y B Phase indication and mcb position indication through glass front, IP-54, Prewired with HFFR/ FRLS copper wires, horizontal type, metallic Double Door, Phase Segregated three pole and neutral MCB Distribution Board fabricated out of 2 mm thick ,powder coated with RAL7035 shade , pre-galvanised G.I. sheet steel, suitable for surface mounting/ installation in existing enclosure complete with appropriate rating of tinned copper bus bar/ Cu wire, neutral bus bar, earth bar, din bar,brass neutral link, brass earthing studs, phase distribution drawing, danger board, name plate, 2 mm thick removable gland plate on both top and bottom side with required number of knock out holes , neoprene gasket, etc as as per drawing, specifications & generally as per relevant IS & as per instructions of Engineer-in-charge. |
| 2 | 6 way MCB DB with Incomer of 25A, Isc=10kA, Type C, TPN MCB with 2-Pole, 25A, Isc=10kA, (100mA) RCBO for each phase and 18 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 3 | Supply |
| 4 | Installation, Testing and Commissioning |
| 5 | 4 way MCB DB with Incomer of 25A, Isc=10kA, Type C, TPN MCB with 2-Pole, 25A, Isc=10kA, (100mA) RCBO for each phase and 12 nos. of 16A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 6 | Supply |
| 7 | Installation, Testing and Commissioning |
| 8 | 4 way MCB DB with Incomer of 16A, Isc=10kA, Type C, TPN MCB with 2-Pole, 16A, Isc=10kA, (100mA) RCBO for each phase and 12 nos. of 6A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 9 | Supply |
| 10 | Installation, Testing and Commissioning |
| 11 | 8 way MCB DB with Incomer of 16A, Isc=10kA, Type C, TPN MCB with 2-Pole, 16A, Isc=10kA, (100mA) RCBO for each phase and 24 nos. of 6A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 12 | Supply |
| 13 | Installation, Testing and Commissioning |
| 14 | 12 way MCB DB with Incomer of 25A, Isc=10kA, Type C, TPN MCB with 2-Pole, 25A, Isc=10kA, (100mA) RCBO for each phase and 36 nos. of 6A, Isc=10kA, Type C, SPN Ougoing MCB feeder as per SLD and technical specification. |
| 15 | Supply |
| 16 | Installation, Testing and Commissioning |
| 17 | Supply, Instalaltion, Testing and comissioning of following configuration 240V, 1-phase, 2 wire, double door,with Phase indication and mcb position indication through glass front, IP-54, Prewired with HFFR/ FRLS copper wires, horizontal type, metallic Double Door, MCB Distribution Board fabricated out of 2 mm thick ,powder coated with RAL7035 shade , pre-galvanised G.I. sheet steel, suitable for surface mounting/ installation in existing enclosure complete with appropriate rating of tinned copper bus bar/ Cu wire, neutral bus bar, earth bar, din bar,brass neutral link, brass earthing studs, phase distribution drawing, danger board, name plate, 2 mm thick removable gland plate on both top and bottom side with required number of knock out holes , neoprene gasket, check nuts etc as required as as per drawing, specifications & generally as per relevant IS & as per instructions of Engineer-in-charge. |
| 18 | 12-way having 1 no. main incomer of 16A DP MCB and 12 nos. outgoing of 6A, 10 kA DP MCB (Isc=10kA) (DB for RMS instruments) |
| 19 | Supply |
| 20 | Installation, Testing and Commissioning |
| 21 | 6-way having 1 no. main incomer of 25A DP MCB and 6 nos. outgoing of 16A, 10 kA DP MCB (Isc=10kA) (DB for RMS instruments) |
| 22 | Supply |
| 23 | Installation, Testing and Commissioning |
| 24 | 4-way having 1 no. main incomer of 16A DP DC MCB and 4 nos. outgoing of 6A, 10 kA DP DC MCB (Isc=10kA) (DB for RMS instruments) |
| 25 | Supply,Installation, Testing and Commissioning |
| 26 | SITC of LED 4ft Slim LED Tube light fixture with 2 no. of LED Tube having a nominal system lumen output of minimum 2340 lumens and a minimum system efficacy of 130 lm/W per tube. The luminaire should have a CCT of 6500K and CRI>80. The luminaire shall meet IP20 rating with THD<15%, PF>0.9, SDCM< 7 and RoHS compliant. The luminaire housing should made of Extruded Aluminium with extruded PC diffuser & should have anodised finish. The total power consumption should not exceed 36W (including driver). |
| 27 | Supply |
| 28 | Installation, Testing and Commissioning |
| 29 | SITC of 4ft Functional Batten (approx dim.140mm x 105mm x 1219mm)with 40W LED Tubelight (acid & corrossion proof) with a nominal system lumen output of 4800 lumens and a minimum system efficacy not less than 120lm/W. The luminaire should have a color temperature of 6500K and CRI>80. The luminaire shall meet IP65 rating with THD < 10% and PF > 0.95. The luminaire housing should made of • Body - glass reinforced polyester (GRP), RAL 7035 • Gasket - polyurethane • Diffuser - UV stabilised prismatic acrylic material. The total power consumption should not exceed 40W(including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 30 | Supply |
| 31 | Installation, Testing and Commissioning |
| 32 | SITC of LED 4ft Slim LED Tube light fixture with one no. of LED Tube having a nominal system lumen output of minimum 2340 lumens and a minimum system efficacy of 130 lm/W. The luminaire should have a CCT of 6500K and CRI>80. The luminaire shall meet IP20 rating with THD<15%, PF>0.9, SDCM< 7 and RoHS compliant. The luminaire housing should made of Extruded Aluminium with extruded PC diffuser & should have anodised finish. The total power consumption should not exceed 18W (including driver). |
| 33 | Supply |
| 34 | Installation, Testing and Commissioning |
| 35 | SITC of LED Bulkhead fitting (for exit lights & lift shaft) with a nominal system lumen output of 700 lumens and a minimum system efficacy of 105 lm/W. The luminaire should have a colour temperature of 6500K, CRI>80 and SDCM<5. The luminaire shall meet IP65 rating and IK08 rating with THD<20% and PF>0.9. The luminaire housing should made of Pressure Die Cast Aluminium with high quality PC diffuser. The power consumption should not exceed 6.5W (including driver). The driver shall have 2.5KV Surge protection. Submission of LM80-08 for LED source & LM79-08 for Luminaire from NABL Accredited Lab mandatory. BIS certified. |
| 36 | Supply |
| 37 | Installation, Testing and Commissioning |
| 38 | SITC of LED street light fitting of not more than 35W having System Efficacy >120lm/W, system output >=4200 Lumens, THD<10%, Power Factor >=0.95, CRI >70, CCT 5700K, SDCM<5, IP66 protected pressure die cast aluminium housing having PC diffuser with IK08.The luminaire shall be supplied with pipe of suitable dia for mounting of the same. Luminaire shall sustain 325V/440V stress voltage protection for 8Hrs, HV cutoff: 325V/440V. Driver shall have 4KV Surge protection. Submission of LM80-08 for LED source & LM79-08 for Luminaire from NABL Accredited Lab mandatory. BIS certified. |
| 39 | Supply |
| 40 | Installation, Testing and Commissioning |
| 41 | SITC of LED light fittings complete with light fitting accessories, including supply of fixing SS accessories, flexible GI metallic conduit sleeves, PVC conduit bushes, Cu cable lugs, suitable PVC terminal box, LED Highbay with a nominal system lumen output of 18000 lumens and a minimum system efficacy of not less than 140 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70B50. The luminaire should have a CCT of 5700K and CRI > 70 and SDCM<5. The luminaire shall meet IP66 and IK 08 rating with THD < 10% and PF > 0.95 and in-built surge protection of 4kV. The luminaire housing should made of High Pressure die cast Aluminium with wide beam optics and having gasket of heat proof silicone rubber ring. The total power consumption should not exceed 130W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 42 | Supply |
| 43 | Installation, Testing and Commissioning |
| 44 | SITC of LED integral driver Flood light with a nominal system lumen output of 8400 lumens and a minimum system efficacy of 120 lumen/watt. The luminaire should have a CCT of 5700K and a CRI>70. The luminaire shall meet IP66 rating with THD<10% and PF>0.95. The luminaire housing should be made of pressure die cast aluminium and front toughened glass cover. The total power consumption should not exceed 70W (including driver). |
| 45 | Supply |
| 46 | Installation, Testing and Commissioning |
| 47 | SITC of light fitting, LED Recessed 2ft x 2ft type with a nominal system lumen output of 4100 lumens and a minimum system efficacy of 130 lm/W. The luminaire should have a CCT of 5700K and CRI>80. The luminaire shall meet IP20 rating with THD<5% and PF >0.95, L70B50 shall be 50000 hours, complete with light fitting SS accessories, flexible GI metallic conduit sleeves, Cu lugs, 3 inch pvc terminal box.The luminaire housing should have made of powder coated metallic CRCA with high efficiency optic diffuser.The total power consumption should not exceed 32W (including BIS Compliant integrated driver) and other requirements shall be as per tender technical specifications. |
| 48 | SITC of LED Circular Recessed downlighter with a nominal system lumen output of 1500lm and a minimum system efficacy of 100lm/W. The luminaire should have a CCT of 6500K and CRI> 80. The luminaire shall meet IP20 rating with THD<10%, PF>0.95. The luminaire housing should made of polycarbonate with high effeciency diffuser. The total power consumption should not exceed 14W (including driver). |
| 49 | Supply |
| 50 | Installation, Testing and Commissioning |
| 51 | Supply and Installation of 2 nos. of 6/16A (compatible with both 6A and 16A with shutter), Single phase Modular Decorative Type Socket with Polycarbonate box as required, 16A Switch and heavy duty polycarbonate Face Plate, 2 nos. of 16A plug tops and suitable mounting arrangements as per technical specification |
| 52 | Supply |
| 53 | Installation on brick/RCC wall and Testing |
| 54 | Supply and Installation of modular heavy duty polycarbonate, Fire Retardant, ISI marked 1 no. of 3M Surface box, 1 no. of 3M combined face plate, 1 no. of 6A/16A 2M Shuttered socket, 1 nos. of 1M 16Amp switch, and 1 no. of 2M 16Amp Plug Top |
| 55 | Supply |
| 56 | Installation on brick/RCC wall and Testing |
| 57 | Supply and Installation of switch box set consisting of 1 nos. of 6A, Piano type Modular Switch with heavy duty polycarbonate box and face plate and suitable mounting arrangements as per technical specification. |
| 58 | Supply |
| 59 | Installation on brick/RCC wall and Testing |
| 60 | Supply and Installation of switch box set consisting of 2 nos. of 6A, Piano type Modular Switch with heavy duty polycarbonate box and face plate and suitable mounting arrangements as per technical specification. |
| 61 | Supply |
| 62 | Installation on brick/RCC wall and Testing |
| 63 | Supply and Installation of switch box set consisting of 3 nos. of 6A, Piano type Modular Switch with heavy duty polycarbonate box and face plate and suitable mounting arrangements as per technical specification. |
| 64 | Supply |
| 65 | Installation on brick/RCC wall and Testing |
| 66 | Supply and Installation of RCC hume pipe having dia 250mm and length 1.2 mtrs for cable entry from outside and as per tender technical specifications. |
| 67 | Supply and laying of following size earthing conductor on surface/concealed including clamping/cleating on structure/floor/ceiling/wall/tray, making chase, repairing the same, interconnection through brazing/bolting etc. as per tender technical specifications. |
| 68 | 10 sq. mm stranded bare tinned copper conductor (conductor shall be connected to earth pad at one end & DB at other end) |
| 69 | 14 SWG solid bare tinned copper conductor (conductor shall be connected to earth pad at one end & LPBS at other end) |
| 70 | Supply and laying of 95 sq. mm stranded bare tinned copper conductor at 1000 mm below ground level including excavation, connection to earth pits including brazing, refilling the trench etc. as per tender technical specifications. |
| 71 | Supply and Laying of 2 x 10 sq. mm insulated stranded copper conductor in 25mm HDPE pipe (supply and fixing of HDPE pipe included in Contractor's scope) as per tender technical specifications. |
| 72 | Supply and Installation of 25 mm X 3 mm thick tinned copper strip including connection/ terminating with nut, bolt, spring, washer etc. as required. |
| 73 | Supply of 25 mm X 3 mm thick copper strip |
| 74 | Installation & Testing of 25 mm X 3 mm thick copper strip |
| 75 | Supply and installation of test link box and termination of earthing conductor from earthing protection system and earth pit and should consist of 2mm thick powder coated pre-galvanised G.I. weather proof sheet enclosure with cover, having 2 parallel paths of 30 mm x 6mm copper strip link, teflon sealing after connection, earthing stud, suitable for connecting of 8 nos. of 95sqmm earthing conductors etc and as per tender technical specifications. |
| 76 | Supply and installation of test link box and termination of earthing conductor from Lightning protection system and earth pit and should consist of 2mm thick powder coated pre-galvanised G.I. weather proof sheet enclosure with cover, having 30 mm x 6mm copper strip link, teflon sealing after connection, earthing stud, suitable for connecting of Cu strip and 2 nos. of 95sqmm earthing conductors etc and as per tender technical specifications |
| 77 | Supply and fixing of vertical air termination made up of 20 mm dia., 1 mtr. long copper rod attached to 50 mm dia. Copper sphere having drilled and tapped holes for fixing 5 nos. of 150 mm long spikes and square copper base plate of 150 mm length and 10 mm thickness as per latest IS & technical specification and approved drawing. |
| 78 | Supply and erection of plate earth electrode pit comprising of 600 X 600 X 3.15mm thick tinnedcopper earth plate, 50mm dia class B watering pipe of 2.7 mtr length, funnel, earth conductorconnection, test link, concrete inspection pit with GI cover having lifting arrangement, etc. as perIS:3043-2001. |
| 79 | Supply and erection of rod earth electrode pit comprised of 25mm dia. and 3mtr long tinnedcopper earth rod, connection of 2 x 95 sq mm conductor, 50mm dia class B watering pipe of 3 mtrlength, funnel, earth conductor connection clamp, test link, concrete inspection pit with GI coverhaving lifting arrangement, etc. as per IS:3043-2001. |
| 80 | Supply and embedment of heavy duty hot dipped 25 mm GI conduit pipe as per IS 9537 along with all accessories such as inspection bends, junction box, socket, check nut, fish wire etc. including making threads, bends, removing burrs, connection of accessories, drawing of fish wire, beam and wall, cutting & Laying in brick wall, etc. as required under the instruction of Engineer-in-incharge. Surface mounted Junction box of suitable size as required suit at site shall be provided. |
| 81 | Supply and fixing of heavy duty hot-dip Galvanised steel (G.I.) ERW 40mm conduit pipe as per IS 9537 along with all accessories such as bends, junction box, socket, check nut, etc. including making threads, removing burrs, connection of accessories, cleating with heavy duty GI saddles or suit to site clamps on RCC wall, column, steel structural, etc. and as per technical specifications. Surface type Inspection box shall be provided as per requirement |
| 82 | Supply of following size flexible GI conduit pipe including cleating with heavy duty GI saddles or suit to site clamps on RCC wall, column, steel structure, etc. as required under the instruction of Engineer-in-charge and as per tender specification. |
| 83 | Supply of flexible GI conduit pipe of size 26 MM |
| 84 | Supply of flexible GI conduit pipe of size 50 MM |
| 85 | Installation of following size flexible GI conduit pipe including cleating with heavy duty GI saddles or suit to site clamps on RCC wall, column, steel structure, etc. as required under the instruction of Engineer-in-charge and as per tender specification. |
| 86 | Installation of flexible GI conduit pipe of size 26 MM |
| 87 | Installation of flexible GI conduit pipe of size 50 MM |
| 88 | Supply and laying of ETP grade14 SWG tinned solid copper conductor throughout along the conduit including fixing with hose clips, lugs, brazing etc as required. |
| 89 | Supply |
| 90 | Installation |
| 91 | Supply of Single Core HFFR wires (Copper) of size mentioned below in voltage grade 1100 V as per the IS 17048: 2018 (latest edition) and as per conductor class 2 of IS: 8130 / 1984 as per technical specification |
| 92 | 1.5 Sq. mm |
| 93 | 2.5 Sq. mm |
| 94 | Installation/drawing through concealled/ surface conduit and wiring and termination at both ends of Single Core HFFR wires (Copper) of size mentioned below in voltage grade 1100 V as per the IS 17048 : 2018. As per conductor class 2 of IS: 8130 / 1984 as per technical specification |
| 95 | 1.5 Sq. mm |
| 96 | 2.5 Sq. mm |
| 97 | Making the opening in brick masonry for door / window / clear story opening including dismantling in floor or walls by cutting masonry and making good the damages to walls, flooring and jambs complete to match existing surface including disposal of mulba/rubbish to the nearest dumping ground. |
| 98 | Supply and installation of tinned Cu Lugs and Brass bolt suitable to following sizes of earthing conductors as per attached technical specification |
| 99 | Copper lug suitable for 10 Sq.mm stranded tinned copper conductor |
| 100 | Supply and installation of M10 brass nut bolt, 3/4\\" long suitable for 10mm threaded hole for making connection to earth pad. |
| 101 | Copper lug suitable for 95 Sq.mm stranded tinned copper conductor |
| 102 | Supply of Busbar Insulator of size M8 x 40mm, MOC: Epoxy as per tender specification. |
| 103 | Installation of Busbar Insulator of size M8 x 40mm for fixing of downcomer conductor from lightening arrestor as per tender specification. |
| 104 | Supply and Installation of GI Anchor Fastner of size M8x80 MM by drilling through concrete block as per site requirement for fixing plate Eps or other structures as per the tender specification. |
| 105 | Supply of GI Anchor Fastner of size M8x80 MM |
| 106 | Installation of GI Anchor Fastner of size M8x80 MM |
| 107 | Providing and fabrication of structural steel (IS 2062 E250 BR) supports, embedded parts, bracket etc. with the usage of suitable size angle, channel, strip, plate, pipe, including cutting, welding, fabrication, painting etc. as per tender technical specifications |
| 108 | Supply and Installation of 2mm thick pre-galvanished GI sheet including marking,cutting (as per site requirement)and erection on top of JB openings on wall and ceiling at approximate height of 7 mtrs. |
| 109 | Supply & installation of wall mounted PA Main Junction Box (PJB) fabricated out of 2 mm thick Pregalvanised GI sheet Powder coated, punched hole for conduit entry on all sides and suitable for incoming cable of size 10 pair x 1.5 sq.mm. armoured twisted pair cable. The junction box shall consist of 20 nos. terminals suitable for 1.5 sq.mm. |
| 110 | Supply & installation of wall mounted Junction box for PA speakers fabricated out of 2 mm thick Pre Galvanised GI sheet steel Powder coated, punched hole for conduit entry on all sides and having 4 nos. of terminals, suitable for terminating 1.5 sq. mm PA cable. |
| 111 | Supply, drawing/ laying & termination of 1 pair x 1.5 sq. mm flexible, overall aluminium mylar screened with drain wire, copper, multi stranded conductor, unarmoured, FRLS, sheathed ( inner and outer), as per attached specification. |
| 112 | Supply & installtion of wall mounted EPABX Main Junction Box (EJB) indoor type with 20 Pair KRONE block suitable for connection of 0.6 mm dia. wire with insertion tool mounted in suitable size enclosure. |
| 113 | Supply and Installation of Indoor type (M.O.C: Pre-Galvanized G.I sheet steel) powder coated MDF box with krone connector made of 14SWG for 50+50 pairs of Telephone cable as per the technical specification. |
| 114 | Supply & installation of Prefabricted GI box to accomodate modular type RJ-11 socket unit suitable for surface mounting. |
| 115 | Supply and Installation of 2-way heavy duty polycarbonate, Fire Retardant, ISI marked Front plate with modular type 4 pin RJ-11 socket unit. |
| 116 | Supply and drawing of 2 Pair 0.6sqmm copper conductor Telephone cable from EPABX Main JB upto RJ-11 socket unit of individual telephone instrument through concealed conduit including end termination in RJ-11 socket units. Please Enable Macros to View BoQ information |