| 1 | Dismantling of MS channel or Angle iron or flat iron sections from LT poles complete all as directed by Engineer-in-Charge. |
| 2 | Dismantling of insulators of any type and any size from LT poles complete all as directed by Engineer-in-Charge.. |
| 3 | Dismantling of ACSR Conductorany size from LT poles complete all as directed by Engineer-in-Charge. |
| 4 | Dismantling & Removing carefully Old unserviceble LT cables/ Service cable of size 16 sqmm to 35 sqmm from LT Pole to Bldg MCB DB complete all as directed by Engineer-in-Charge. |
| 5 | S&F in Replacement of LT Panel compartmentalised cubical Outdoor type Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminium bus bar of rating 1200 Amp installed on proceline/ SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finesh over one coat of red oxide on out side surface and painted in side with two coated of red oxide primer and rear opening type with apran for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary PCC platform of suitable size. (Loc :- JCO/ORs TRF No 1)INCOMING:- (i) ACB drawn-out type with adjustable microprocessor release confirm to IS/IEC:60947-2, 4 pole , LT 415 Volts, 50 Hz AC grade of 800 Amps rating 50 KA rupturing capacity with suitable for adjustable over load current and short circuit and earth fault protection - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 800/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 315 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 01 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos, (iii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 100 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos, (iii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos, |
| 6 | All as per item No 05 but bus bar of rating 1500 Amp. (Loc :-JCO/ORs TRF No 2)INCOMING:- (i) ACB drawn-out type with adjustable microprocessor release confirm to IS/IEC:60947-2, 4 pole , LT 415 Volts, 50 Hz AC grade of 1000 Amps rating 50 KA rupturing capacity with suitable for adjustable over load current and short circuit and earth fault protection - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 1000/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 315 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 01 Nos, (iii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 100 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos, (iv) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos, |
| 7 | S&F of LT feeder pillar compartmentalised cubical outdoor type Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminium bus bar of rating 400 Amp installed on proceline/ SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finesh over one coat of red oxide on out side surface and painted in side with two coated of red oxide primer and rear opening type with apran for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary PCC platform of suitable size.(Loc :- Near STP)INCOMING:- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 250/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 100 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos.(ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 40 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos. |
| 8 | S&F of LT feeder pillar compartmentalised cubical outdoor type Floor mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminium bus bar of rating 400 Amp installed on proceline/ SMC insulator. The panel should be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 50X50X6 mm thick MS angle iron frame work, powder coated finesh over one coat of red oxide on out side surface and painted in side with two coated of red oxide primer and rear opening type with apran for cable entry, closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size and comprising of the following including necessary PCC platform of suitable size.(Loc :- Near P-9)INCOMING:- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 250/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 06 Nos.(ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 40 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 01 Nos. |
| 9 | All as per item No 07 but bus bar of rating 500 Amp. (Loc :- Near P 67,P-69 & P-70 ) INCOMING:- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 315 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 315/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 08 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 40 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 01 Nos. |
| 10 | All as per item No 07 but bus bar of rating 200 Amp.(Loc :- Near Childerns School)INCOMING:- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 100 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 160/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCB 4 pole , LT 415 Volts, 50 Hz AC grade of 40 Amps rating 10 KA - 06 Nos. . |
| 11 | All as per item No 07 but bus bar of rating 200 Amp.(Loc :-Near Peer Panjal)INCOMING:- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 100 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases - 01 No.(ii) Digital Voltmeter 0-500 volts, square, 96 mm,flush pattern with 3 way selector switch - 01 No(iii) Digital Ammeter 96mm x 96 mm, flush pattern with 3 way selector switch - 01 No.(iv) 3 Nos of CTs of ratio 160/5 copper wound, Class 1.0, 10 VA – 1 Set(iv) Indicating lamps R,Y and B Phase : 01 set of three OUTGOING (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 25 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos. (i) MCB 2 pole , LT 220 Volts, 50 Hz AC grade of 40 Amps rating 10 KA rupturing capacitiy 'C' Curve, - 02 Nos. |
| 12 | Supply, installing, testing and commissioning of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 500 Amps aluminium bus bar and with 315 Amp MCCB, 4 pole, 25 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 13 | Supply, installing, testing and commissioning of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 200 Amps aluminium bus bar and with 100 Amp MCCB, 4 pole, 25 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level. |
| 14 | Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 marked, suitable for LT 1100 Volt system, laid in trenches fixed to poles, including jointing & testing complete all as specified and directed of following sizes:-Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately under respective items of schedule. |
| 15 | 16 Sqmm 2 core |
| 16 | 16 Sqmm 4 core |
| 17 | 25 Sqmm 4 core |
| 18 | 35 Sq mm 3.5 core. |
| 19 | 50 Sq mm 3.5 core. |
| 20 | 70 Sqmm 3.5 core |
| 21 | 95 Sqmm 3.5 core |
| 22 | 240 Sqmm 3.5 core |
| 23 | 630 Sqmm Single core |
| 24 | M&L for Earthing complete with GI earth plate 60x60cmx6mm thick electrode and 32x6mm GI strip as earthing lead burried directly in ground (Earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metre below normal ground level, conneceted to GI strip 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 and incl earth work, PCC pit and RCC cover, watering pipe 20mm dia light grade, funnel, wire mesh, charcoal dust, 40mm dia light grade protection pipe and salt etc and connected to earthing test point complete all as specified and directed. |
| 25 | S&F KIOSK box weather proof made out of PVC, one piece moulded SMC base and out door pole mounted hinged door size 333 x 233 x 120 mm out side and 300 x 200 x 105mm inside dimensions comprising of aluminum bus bar 4 strips for 3 phase and neutral 63 Amp and 6 Amp MCB SP with base for controlling the street light, FI clamps 30x4 mm with necessary MS nuts bolts and washers including embossing/painting of Danger notice of size not less than 10 cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as directed by Engineer-in-Charge. |
| 26 | Supply drawing, connecting and testing of 3 core, 1.5 Sqmm PVC insulated and PVC round sheathed copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from KIOSK box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge. |
| 27 | M/L for HDPE pipe PE 100, PN6 with fittngs laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed of following sizes :- |
| 28 | 40 mm dia |
| 29 | 50 mm dia |
| 30 | 90 mm dia |
| 31 | M&L for Demolation of road, path, drain and concrete in ground floors, RCC/Brick wall (below or above ground level) complete all as specified and as directed. |
| 32 | M&L for providing cement concrete 1:2:4 type B-2 (using 40 mm grade crushed stone aggregate) complete all as specified and as directed by Engr in charge. |
| 33 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge. |
| 34 | Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed. |
| 35 | Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge. |
| 36 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified. |
| 37 | S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge. |
| 38 | Notes :- Amount of Credit Schedule for Schedule 'A' Part-ll shall be deducted from total quoted amount of BOQ to arrive at the contract sum. Please Enable Macros to View BoQ information |