| 1 | Electrical works |
| 2 | OD400340/2025-2026Supply and Installation of 100W LED Flood light output greater than 105lumen/W4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with powerfactor greater than 0.95 at full load, internal surge protection up to 8 KV,andAluminium pressure die-cast Powder coated housing, acrylic cover complete withTHD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired upfor use on 230 V AC supply. Driver compartment should be seperatly accessible formaintenance (2 years warranty for LED Flood Lights) |
| 3 | OD400366/2025-2026Supply and Installation of 150W LED Flood light output greater than 105lumen/W4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with powerfactor greater than 0.95 at full load, internal surge protection up to 8 KV, andAluminium pressure die-cast Powder coated housing, acrylic cover complete withTHD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired upfor use on 230 V AC supply. Driver compartment should be seperatly accessible formaintenance (2 Years Warranty for LED Flood Lights) |
| 4 | OD405432/2025-2026Supply and installation of dust and vermin proof, outdoor single Phase Polycarbonate/FRP/PVC /UPVC Meter Box suitable to install KSEB meter, fuse units etc., asrequired and including fixing it on Wall/ Angle iron Frame, making good, without thedamages color washing etc., as required.(Size 400 x 300 x 190) |
| 5 | OD405419/2025-2026Supply and installation of a Digital timer, operating at 220-250 VAC, 50Hz, with a25A/1.5HP capacity. It features 5 On/Off program settings for daily and weeklyschedules, along with manual start, ON delay, and OFF delay settings. Equipped witha high-precision, industrial-grade chip and strong anti-interference capabilities, thetimer can automatically turn on and off the power supply of various electricalequipment according to the time set by the user. The controlled objects can includestreet lights, light boxes, neon lights, and high/mini mast systems. It also includes asufficient battery backup for time memory in case of power failure, and comes withsuitable fittings for use in a distribution box or MV panel with FRLS PVC insulated .5mm single core cable suitable for control wiring towards contactor |
| 6 | OD405427/2025-2026Supply and installation of a double pole 25A Contactor, rated for 220-250 VAC, 50Hzoperation. It can control street lights, light boxes, neon lights, high/mini mast systems,and induction loads. |
| 7 | 2.10.3Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole |
| 8 | OD405449/2025-2026Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface/recessed steel/ PVC conduit as required. 2.5sq. mm Please Enable Macros to View BoQ information |