| 1 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 2 | 4 x 10.0 sq.mm |
| 3 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 4 | Armoured Cable |
| 5 | 185.0 Sq.mm |
| 6 | 3.5 core |
| 7 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 8 | 185.0 Sq.mm |
| 9 | Excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 100 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically (Longest side is vertical to cable) along the cable , (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 10 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 11 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 12 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 13 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 14 | 8 SWG G.I. ( Hot Dipped ) Wire |
| 15 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 16 | 100 mm dia. |
| 17 | labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.: |
| 18 | All kind of Soils |
| 19 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 20 | 110 mm |
| 21 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 22 | 3 core 185.0 Sq.mm |
| 23 | Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 24 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 25 | 11 KV End Termination Kit Indoor type |
| 26 | 3 core 120/150/185 Sq.mm |
| 27 | 11 KV End Termination Kit Outdoor type |
| 28 | 3 core 120/150/185 Sq.mm |
| 29 | S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 ( Correspnding level as per BIS amended upto date of receipt of tender) & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, undirectional rollers as required including carrying of pre-commission Testing & Charging of Transformer complete in all respect . Factory Tests : The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) in OEM's own lab and same shall be witnessed by Department engineer. Site Tests : Following tests shall be carried out on each transformer at site by OEM engineer in presence of department's site engineer:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor) |
| 30 | Note :Manufacturer's testing laboratory should be certified by NABL and have an in house core cutting facility to ensure proper control & monitoring of quality. This is crutial to prevent the mixing of prime core materials with Second grade or defective materials. The core should be constructed from high grade, non ageing, PRIME GRADE CRGO steel with M4 Grade or Better, using silicon steel laminations, and should be of boltless design. The core and coil assembly should be undergo drying process using a highly efficient vacuum drying autoclave to remove moisture through heating and drying. |
| 31 | 315 KVA with Off -LTC (+5% to - 10% @ 2.5%) with % impedance 4.5 |
| 32 | Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: |
| 33 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 34 | Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more required complete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of size complete in all respect. . |
| 35 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing. |
| 36 | 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 37 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 38 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 39 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 40 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 41 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 42 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 43 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 44 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 45 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 46 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 47 | Electrolytic grade Aluminium bus bar 6010 grade |
| 48 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 49 | Three phase Ammeter with Inbuilt Selector Switch |
| 50 | Three phase Voltmeter with Inbuilt Selector Switch |
| 51 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 52 | Ring type tape wound CT |
| 53 | C T Class 1, Ratio up to 150/5, Burden 5 VA |
| 54 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 55 | Red/yellow/Green colour |
| 56 | Providing & Fixing of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid aberration marks and pasting the mat with synthetic rubber adhesive as required. |
| 57 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 58 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, life expectancy greater than 100000hrs (temp class - 25 D) in 440 V including making connections, testing etc. as required. |
| 59 | Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor (Bank) |
| 60 | Providing & Fixing of microprocessor based 3 CT’s for all 3 phase sensing compensation power factor correction relay with Approx. Size 139 mm x 139 mm, Operating Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analyzing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, High voltage, THD-I & THD-V insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi Built in MFM with PF Controller LCD Display, CT polarity auto correction % THD up to 30 harmonics level, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5 Cast Resin CT for sensing the relay including making connection with 1.5 Sq.mm copper wire etc. as required. |
| 61 | 12 to 16 stage |
| 62 | Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. |
| 63 | up to 6 KVAR |
| 64 | 8.5 KVAR |
| 65 | 10 KVAR |
| 66 | 12.5 KVAR |
| 67 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 68 | 4 pole MCCB With Thermal Magnetic release |
| 69 | 160 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 70 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 71 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 72 | Providing & Fixing of on load change over switch, front handle operated, four pole 415 V confirming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. |
| 73 | Open execution type |
| 74 | 400 A |
| 75 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required. |
| 76 | 50mm x 50mm x 6mm |
| 77 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization catagory, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 25sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. |
| 78 | Triple pole Isolator |
| 79 | 63 A rating |
| 80 | Providing & Fixing of 10 A Cam operated rotary (Local- Remote, Auto - manual) switches on existing panel with 1 pole 2 way and off position using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . |
| 81 | 32 AMP |
| 82 | Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per IS :2551-1982 & specification of Discom on the existing poles complete in all respectas as required. Please Enable Macros to View BoQ information |