| 1 | Schedule ‘A’ Part I to XIII under Ser No. 1.00 to 13.00 are prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 2 | Lump sum price worked out for BUILDINGS/ STRUCTURES as listed in Sch 'A' Part-I |
| 3 | Lump sum price worked out for EXCAVATION, EARTH WORK AND SITE CLEARANCE as listed in Sch 'A' Part-II |
| 4 | Lump sum price worked out for INTERNAL WATER SUPPLY as listed in Sch 'A' Part-III |
| 5 | Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch 'A' Part-IV |
| 6 | Lump sum price worked out for ROAD/ PATH as listed in Sch 'A' Part-V |
| 7 | Lump sum price worked out for AREA DRAINAGE as listed in Sch 'A' Part-VI |
| 8 | Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch 'A' Part-VII |
| 9 | Lump sum price worked out for SEWAGE TREATMENT PLANT as listed in Sch 'A' Part-VIII |
| 10 | Lump sum price worked out for EXTERNAL WATER SUPPLY as listed in Sch 'A' Part-IX |
| 11 | Lump sum price worked out for EXTERNAL ELECTRIFICATION as listed in Sch 'A' Part-X |
| 12 | Lump sum price worked out for FENCING/ GATE/ RETAINING WALL as listed in Sch 'A' Part-XI |
| 13 | Lump sum price worked out for LIGHTENING PROTECTION as listed in Sch 'A' Part-XII |
| 14 | Lump sum price worked out for DG SET as listed in Sch 'A' Part-XIII |
| 15 | PROVISIONAL SUMMaterial and labour for construction of RCC PLATFORM OF SIZE 18 M X 10 M X 0.15 M complete all as directed by Engr-in-charge, with necessary PCC , formwork, RCC, reinforcement etc. and extra items involved for completion of work complete all as specified and directed by GE.(Note : Excavation and earthwork required under this item shall be measured and paid for seperately under respective items of Schedule 'A' Part II) |
| 16 | SCHEDULE 'A' PART - XIV MISCELLANEOUS ITEMS is not prepriced by MES and prepriced rates indicated blank under column 5 signifies this fact only. Bidder shall insert their rates in Green filed under Col-6. |
| 17 | SEWAGE DISPOSAL |
| 18 | Supply, laying and testing of double wall corrugated polyethylene pipes (DWCPE) of 150mm internal dia and stiffness class-8 (SN-8) with ISI mark (with CML no), with and including all fittings and jointed complete with collars for sewage line complete all as specified and as directed. |
| 19 | Material and labour for construction of manhole type A, circular type, in brick masonry, having inside diameter of 900 mm for fixed depth upto 1 metre (for 150 mm to 500 mm dia sewer) including SFRC frame and cover etc. complete all as specified and as shown in drawing No. CEAG/THANE/STP/52/2026 sht 1/6 dt 07.05.2026. |
| 20 | Material and labour for construction of manhole type A, circular type, in brick masonry, having inside diameter of 900 mm for varying depth upto 1.5 metre (for 150 mm to 500 mm dia sewer) including SFRC frame and cover etc. complete all as specified and as shown in drawing No. CEAG/THANE/STP/52/2026 sht 1/6 dt 07.05.2026. |
| 21 | Material and labour for construction of manhole type B, circular type, in RCC and brick masonry, having inside diameter of minimum 1200 mm for fixed depth upto 1.5 metre (for 150 mm to 600 mm dia sewer) including SFRC frame and cover etc. complete all as specified and as shown in drawing No. CEAG/THANE/STP/52/2026 sht 1/6 dt 07.05.2026. |
| 22 | Material and labour for construction of manhole type B, circular type, in RCC and brick masonry, having inside diameter of minimum 1200 mm for varying depth upto 3 metre (for 150 mm to 600 mm dia sewer) including SFRC frame and cover etc. complete all as specified and as shown in drawing No. CEAG/THANE/STP/52/2026 sht 1/6 dt 07.05.2026. |
| 23 | Material and labour for construction of vertical drop arrangement of 0.6 m and more height as required with DWC pipe at 100 mm c/c at required level including providing and jointing specials such as double T, bend etc. required and cutting, jointing and filleting as per specifications complete all as specified and directed. |
| 24 | SEWAGE TREATMENT PLANT |
| 25 | Supply, design, construction, hydraulic testing, commissioning and giving satisfactory trials of Sewage Treatment Plant of capacity 140 KLD consisting of compact package type STP along with the following accessories; to the desired capacity of 140 KLD rated net output, complete as turnkey job with all associated electrical and mechanical components with all duties and taxes, complete all as specified and directed by Engineer-in-Charge for satisfactory performance of plant and required treated water parameters as per latest E-in-C policy and NGT guidelines. STP shall consist of the following:-(a) Fine bar screen (manual) of SS 304 for screening 5 to 6 mm particles at inlet of MBBR tank(b) Non-clog submersible raw sewer pump of discharge capacity 10 cum/hr @ 10 mtr head of suitable capacity 2.0 HP/ 1.5 KW (01W+01S= 02 Nos)(c) Centrifugal type filter feed pump of discharge capacity 10 cum/ hr @ 25 mtr head capacity (01W+01S= 02 Nos)(d) Moving Bed Bio Reactor (s) with plastic media (of appropriate density, size and volume having minimum surface loading rate 400 sqm/cum) with 02 Nos of unit which can cater 50% of load.(e) Twinlobe air blower of 113 cum/hr @ 0.3 kg/ cm2 pressure capacity 5.0 HP (1W+1S= 02 Nos) with SS pipe aeration grid at MBBR tank(f) DO meter (01 No.)(g) Sludge setting arrangement(h) Chlorine Dosing System (01W+01S= 02 Nos)(j) Poly Dosing System (01W+01S= 02 Nos)(k) Filter Feed Tank including Tertiary Treatment of capacity 10 cum/ hr with head 15-20 mtr of capacity 2.0 HP/ 1.5 KW (01W+ 01S= 02 Nos) |
| 26 | (l) Multi grade filter FRP type of capacity 10.0 cum/hr (size 36\\" x 72\\") with multi-port valve and piping(m) Activated Carbon Filter FRP type of capacity 10.0 cum/hr (Size 36\\" x 72\\") with multi-port valve and piping(n) Electromagnetic flow meter for suitable outlet pipe size(o) Sludge handling unit (with sludge pump and filter press)(p) Foundation of all E/M equipment(q) Air diffuser (suitable qty)(r) Valves, Gates, Level Switches, Pressure Gauges, Drains, Pathways as per requirement for 140 KLD STP complete.(s) RCC raw water collection sump of capacity 20 KL complete - 01 No (cost of this component shall be measured and paid separately under respective item of schedule) (t) RCC Bar screen Chamber, O&G trap and GT of suitable capacity for 140 KLD STP complete - 01 No (cost of this component shall be measured and paid separately under respective item of schedule) (u) (i) Electrical Control Panel: Fabrication, installation and testing of LT Panel factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 2.0 mm thick CRCA sheet of suitable size to accommodate accessories with interconnecting cable of requried size for above given components/ units/ equipments/ accessories of package MBBR based STP.(ii) Necessary copper cable for interconnecting from STP panel to various drives, pumps shall be provided complete all as specified and directed. |
| 27 | (v) (i) STP shall have with anoxic zone for total Nitrogen removal is as per design and indicative, however OEM can add/ alter/ omit the given components as per their design to achieve desired capacity and treated water parameter with same technology as per E-in-C Branch latest guidelines/ policies.(ii) Mode of Construction (MOC) of compact package STP should be as given below:MS based or 100% pure FRP based packaged sewage treatment plant, MS plate having minimum 8mm thick base plate, side wall plate thickness 6mm minimum, relevant size of structural steel members with inside epoxy coating and outside epoxy paint on primer; FRP based packaged sewage treatment plant, FRP material supplied should be tested by NABL approved lab for pressure test on minimum 5 psi and vacuum test on minimum 5 psi, Barcol hardness 43 minimum and flexural strength minimum 12600 lb/in2. Notes:- (i) The STP tank shall be placed on 100 mm thick PCC lean concrete 1:4:8 and laid on stable compacted ground.(ii) If STP vendor provides any additional equipments required for the operation and performance of the plant, no extra cost shall be paid to the contactor on this account.(iii) Maintenance staff for services should reach in 4 hrs of time period and shall be available 24 x 7. (iv) STP should function from minimum 10% load to 100% peak load. |
| 28 | Supply, laying, jointing and testing of Ductile Iron (DI), pressure pipes with spigot and socket ends, centrifugally cast, class K-9 of size 80 mm dia, with cement mortar lining in inner side as per IS:8329/ 2000 (latest revision) and other relevant standards and metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and as directed. |
| 29 | Material and labour for ductile iron fitting for spigot socket pipe such as bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc), tee pieces, single branch, \\"Y\\" junction, double branch, cross (all socket or socket and spigot), collars, restrained joint, mechanical joint, caps and plugs; 80 mm to 250 mm dia bore including cutting and jointing old/ new positions complete all as specified and directed. |
| 30 | Supply, install, testing and commissioning of submersible non clog vertical pump set (raw sewage pump), multistage as per IS with electric motor of capacity 3.0 HP, 1440 to 1500 RPM, 3 phase, 440 volts, 50 Hz heavy duty capacity and pumping sewage water to a head 14-20 mtr and discharge capacity of 10 cum/ hr (170 LPM), with chrome steel impeller and cutter, non-clog to pass 40 mm size particles including supply, installation with guide rail and lifting chain including all necessary accessories and fittings including pressure gauge at delivery side, PVC insulated and PVC sheathed three core copper cable from motor terminal to starter panel suitable size of pump set and with 2 years maintenance spares for Intermediate Lift Pumping Stations-03 Nos at different locations (each lift pumping station- 02 Nos pumps 01 W+ 01 S) complete all as specified and directed (at Node No 14 , 20 & Lift Stn No- 03) |
| 31 | Supply, installation, testing and commissioning (SITC) of float type level switch (vertical) for pumping station complete all as specified and directed. |
| 32 | Supply, fabrication, installation and testing of Motor Control LT Panel factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side, with IP 54 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands, Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:- |
| 33 | INCOMING:-(a) Copper strip busbar of 100 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) 4 Pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader link- 01 No.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/ 250 volts, AC- 01 set (set of three) (d) Digital ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch - 01 set(e) Digital voltmeter of range (0-500) Volts, flush mounting type with selector switch - 01 No. OUTGOING:-(a) MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos (b) MCB SPN 32 Amps - 02 Nos(c) DOL starter suitable for 3HP/ 2.25 KW pump motor- 02 Nos(d) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel. |
| 34 | Material and labour for construction of brick masonry valve pit of internal size 600mm x 600mm x 900mm including necessary excavation and earth work, brick work, plastering, white wash, PCC coping, MS frame made out of angle iron of size 40mmx40mmx6mm, MS sheet cover of 5 mm thick fixed to angle iron frame by means of hinges welded to frame and painting with 2 coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces and grouting the frame in PCC 1:2:4 type B-1 including handle and locking arrangement with one number 50 mm dia brass pad lock complete all as specified and directed.Note:- (i) Brick wall shall be 23 cm thick built in cement mortar (1:6) (ii) Internal plaster shall be 15 mm thick in cement mortar (1:4)(iii) PCC in foundation shall be 15 cm thick in cement concrete (1:3:6) type C2 using 40 mm graded stone aggregate extended 15 cm all around from the external face of the walls (iv) PCC coping shall be 15 cm thick in cement concrete (1:2:4) type B1 using 20 mm graded stone aggregate including grouting of angle iron frame in PCC(v) Three coats of white wash to internal surfaces of valve pit shall be provided(vi) Depth of valve pit shall be reckoned from the top of PCC in foundation |
| 35 | EXTERNAL WATER SUPPLY |
| 36 | Supply and fix HDPE/ PP-R gate valves (Brass Insert) including necessary jointing material as required complete all as specified and as directed for 110 mm outer dia of pipe. |
| 37 | Supply and fix HDPE/ PP-R gate valves (Brass Insert) including necessary jointing material as required complete all as specified and as directed for 90 mm outer dia of pipe. |
| 38 | Supply and fix path indicator/ marker for HDPE pipe made of RCC 1:2:4 (using 20 mm graded crushed stone aggregate), reinforced with 8 mm dia TMT bars 100 mm c/c horizontally and vertically of size 200 mm x 100 mm x 600 mm height with \\"SEWAGE TREATED WATER PIPE/ MES\\" embossing on route indicator/ marker including painting as per approved colour and buried in ground 450 mm depth including necessary earthwork (as required/ ordered at site) complete all as specified and as directed. |
| 39 | Supply, installation, testing and commissioning of electric motor driven submersible pump set suitable for lifting water from UG sump of capacity 3.0 HP for 170 LPM water flow and 25 mtr head with AC, 3 phase, 50 Hz, 415 Volts, submersible motor of suitable capacity including suitable sizes of non return valve- 01 No, GI delivery pipe upto ground level to connect the PPR pipe and 3 core submersible cable from motor panel to pump terminal all as per IS:8034-198 as required complete all as specified and directed (1W + 1S). |
| 40 | Supply, fabrication, installation and testing of Motor Control LT Panel factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 2.0 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side, with IP 54 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provison for termination with incoming and outgoing cables with cable glands, Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:- |
| 41 | INCOMING:-(a) Copper strip busbar of 63 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) 4 Pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader link- 01 No.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/ 250 volts, AC- 01 set (set of three) (d) Digital multifunctional meter, flush mounting type with CT’s and selector switch- 01 set. OUTGOING:-(a) MCB TPN 32 Amps 4 pole, 415 Volts, 10 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nosb) DOL starter with suitable relay range conforming to IS, suitable for discharge capacity 170 LPM (10.20 cum/hr) at 25 mtr head, 2.28 KW/ 3.0 HP, including overload relay and single phase preventer, digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) & bakelite fuse showing RYB phase etc. complete- 02 Nos Please Enable Macros to View BoQ information |
| 42 | INCOMING:-(a) Copper strip busbar of 63 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) 4 Pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader link- 01 No.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/ 250 volts, AC- 01 set (set of three) (d) Digital multifunctional meter, flush mounting type with CT’s and selector switch- 01 set. OUTGOING:-(a) MCB TPN 32 Amps 4 pole, 415 Volts, 10 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nosb) DOL starter with suitable relay range conforming to IS, suitable for discharge capacity 170 LPM (10.20 cum/hr) at 25 mtr head, 2.28 KW/ 3.0 HP, including overload relay and single phase preventer, digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) & bakelite fuse showing RYB phase etc. complete- 02 Nos Please Enable Macros to View BoQ information |