| 1 | BOQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) File No 8139/E8 Tender Inviting Authority: GARRISON ENGINEER GOLCONDA Name of Work: SPL REPAIR/ REPLACEMENT TO OVERHEAD LT CABLE TO UG CABLE AT IB LINE UNDER GE GOLCONDA Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevant columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of work Item Code / Make No or Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder including all TaxesRs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | Dismantling old ACSR conductor of any size from over head lines complete all as specified and directed |
| 3 | Dismantling old Cross-arms of MS channel including clamps, nuts and bolts or angle sections etc. of any size from over head lines complete all as and directed |
| 4 | Dismantling old insulators of any type and size from over head lines complete all as specified and directed |
| 5 | Dismantling old service wire of any type and size from over head lines complete all as specified and directed |
| 6 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size185 sq. mm 3.5 core in trenches/ fixed to walls/ poles etc. including taking out of existing cable complete all as specified and directed. |
| 7 | All as per item No.5 but 120 Sqmm x 3.5 Core |
| 8 | All as per item No.5 but 95 Sqmm x 3.5 Core |
| 9 | All as per item No.5 but 25 Sqmm x 3.5 Core |
| 10 | All as per item No.5 but 10 Sqmm x 2 Core |
| 11 | Supply, install, testing and commissioning of new Out door LT feeder panel, factory fabricated, CPRI approved and tested , cubicle type, 3.15 mm thick CRCA sheet vermin proof with 3 phase and neutral Aluminium bus bar of current capacity 400 A of suitable size, phase and neutral colour coded with heat shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, front and rear opening double door locking arrangements and painting with one coat of red oxide primer and two coats of powder coated paint, suitable size of panel control copper wiring, accessories fitted on suitable insulator all housed in suitable bus bar chamber and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps (R,Y,B) along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc. , including PCC foundation and necessary earth work complete all as specified and directed and consisting and including of the following :- (a) 4 Pole MCCB 320 Amp 50 Hz 415 V with rupturing capacity 36 KA,Adjustable thermal & Magnetic setting(Incoming ) - 01(b) 4 Pole MCCB 100A 50 Hz 415 V with rupturing capacity 25 KA,Adjustable thermal & Fixed Magnetic setting - 05 Nos ( 01 Stand by for Sub Panel)(c) Three phase Digital voltmeter 0-500 Volts with selector switch - 01 Set(d) Three phase digital Ammeter 0-500 Amps with selector switch and CTs - 01 Set(e) Phase Indicating lamp LED type for Red, Yellow and Blue - 01 Set |
| 12 | Supply, install, testing and commissioning of new Out door LT feeder panel, factory fabricated, CPRI tested , cubicle type, 3.15 mm thick CRCA sheet vermin proof with 3 phase and neutral Aluminium bus bar of current capacity 200A of suitable size, phase and neutral colour coded with heat shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, front and rear opening double door locking arrangements and painting with one coat of red oxide primer and two coats of powder coated paint, suitable size of panel control copper wiring, accessories fitted on suitable insulator all housed in suitable bus bar chamber and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc., including PCC foundation and necessary earth work complete all as specified and directed and consisting and including of the following :-(a) 4 Pole MCCB 100 Amp 50 Hz 415 V with rupturing capacity 36 KA,Adjustable thermal & Magnetic setting(Incoming ) - 01(b) 2 Pole MCB 32A 50 Hz 415 V with rupturing capacity 25 KA,Adjustable thermal & Fixed Magnetic setting - 13 Nos ( 01 Stand by for Bldg)(c) Three phase Digital voltmeter 0-500 Volts with selector switch - 01 Set(d) Three phase digital Ammeter 0-500 Amps with selector switch - 01 Set(e) Phase Indicating lamp LED type for Red, Yellow and Blue - 01 Set |
| 13 | Supply, install, testing and commissioning of new Out door LT feeder panel, factory fabricated, CPRI tested , cubicle type, 3.15 mm thick CRCA sheet vermin proof with 3 phase and neutral Aluminium bus bar of current capacity 200A of suitable size, phase and neutral colour coded with heat shrinkable PVC sleeves, with necessary supports, angle iron frame work and stand, front and rear opening double door locking arrangements and painting with one coat of red oxide primer and two coats of powder coated paint, suitable size of panel control copper wiring, accessories fitted on suitable insulator all housed in suitable bus bar chamber and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc., including PCC foundation and necessary earth work complete all as specified and directed and consisting and including of the following :- (a) 4 Pole MCCB 160 Amp 50 Hz 415 V with rupturing capacity 35 KA,Adjustable thermal & Magnetic setting(Incoming ) - 01(b) 4 Pole MCB 63 A 50 Hz 415 V with rupturing capacity 25 KA,Adjustable thermal & Fixed Magnetic setting - 5 Nos ( 01 Stand by for Bldg)(c) Three phase Digital voltmeter 0-500 Volts with selector switch - 01 Set(d) Three phase digital Ammeter 0-500 Amps with selector switch and CTs - 01 Set(e) Phase Indicating lamp LED type for Red, Yellow and Blue - 01 Set |
| 14 | M&L Earthing complete with galvanized steel with plate electrode 60 cm x 60 cm x 6.3mm thick buried directly in ground (earth kit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part-I connected to earth test point including necessary earth work and excavation, PCC 1:3:6 type C1 using 20mm graded stone aggregate for earth chamber with RCC cover 50mm thick 1:2:4 mix type B1, using 8mm dia TMT bars reinforcement @ 140mm c/c both ways, watering funnel with GI pipe 20 mm dia medium grade and protection pipe GI 40 mm dia medium grade testing after completion all as specified and directed. |
| 15 | Excavation in trenches not exceeding 1.5 M wide and not exceeding 1.5 M deep and getting out in soft / loose soil for laying of cable. |
| 16 | Returning filling in including spreading, levelling, watering and well ramming, in layers not exceeding 25cm in soil obtained from excavation all as directed. |
| 17 | Removal of surplus soil to a distance not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above starting point. |
| 18 | Supply and lay spread dry clean sand in trenches for cable cushioning complete all as specified and as directed (only punned thickness will be measured and paid ) |
| 19 | Supply and lay common burnt, clay building bricks sub class B of standard size for cable protection in trenches complete all as specified and as directed |
| 20 | M & L for cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and moorum filling including excavation for laying of cable/pipe all as directed and making good the road/hard standing by using all old/new materials and with PCC (1:2;4) etc., required to match with the existing surface complete all as specified and directed. |
| 21 | Supply and lay GI tube light grade 100 mm bore, ISI marked with all fittings, complete, fixed to walls, pole ceiling or laid in trenches/floor for cable protection at road crossing/ on poles etc. complete all as specified and directed. |
| 22 | Supply and lay GI tube light grade 40 mm bore, ISI marked with all fittings, complete, fixed to walls, pole ceiling or laid in trenches/floor for cable protection at road crossing/ on poles etc. complete all as specified and directed. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |